Magnum MS2000 User manual

MS Series
Pure Sine Wave
Inverter/Charger
Owner’s Manual
TM

Page i © 2012 Magnum Energy, Inc.
Disclaimer of Liability
The use of this manual and the conditions or methods of installation, operation, use, and
maintenance of the MS Series inverter/charger is beyond the control of Magnum Energy, Inc.
Therefore, this company does not assume responsibility and expressly disclaims liability for loss,
damage, or expense whether direct, indirect, consequential or incidental that may arise out of or
be any way connected with such installation, operation, use, or maintenance.
Due to continuous improvements and product updates, the images shown in this manual may not
exactly match the unit purchased.
Restrictions on Use
The MS Series inverter/charger may only be used in life support devices and systems with the
express written approval of Magnum Energy. Failure of this inverter can reasonably be expected
to cause failure of that life support device or system, or to affect the safety or effectiveness of
that device or system. If the MS Series inverter fails, it is reasonable to assume the health of the
user or other persons may be endangered.
Copyright Notice
Copyright © 2012 by Magnum Energy, Inc. All rights reserved. Permission to copy, distribute, and/or
modify this document is prohibited without express written permission from Magnum Energy, Inc.
Document Information
Description – MS Series Owner’s Manual
Part Number and Revision – 64-0007 Rev D
Date Published – August 2012
This entire manual is available for download—with many of the diagrams available in color—under
the Document Library tab on our website at: www.magnumenergy.com.
Contact Information
Magnum Energy, Inc.
2211 West Casino Rd.
Everett, WA 98204
Phone: 425-353-8833
Fax: 425-353-8390
Web: www.magnumenergy.com
Statement of Appreciation
Thank you from all of us at Magnum Energy for purchasing this MS Series inverter/charger.
We understand that you have many purchasing options in the marketplace, and are pleased that
you have decided on a Magnum Energy product. This MS Series inverter/charger was proudly
assembled and tested in the United States in our Everett, Washington, facility.
At Magnum, we are committed to providing you with quality products and services, and hope that
your experience with us is pleasant and professional.
Magnum Energy® is a registered trademark of Magnum Energy, Inc.
Record unit’s model & serial number in case you need to provide this information in the future.
Model: Serial Number:
MS2000 (-15B/-20B) T1
MS2012 (-15B/-20B) J1
MS2812 H1
MS2024 AJ
MS4024 K1

Safety Information
© 2012 Magnum Energy, Inc.Page ii
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS FOR THE MS SERIES INVERTER/CHARGER
THAT SHALL BE FOLLOWED DURING THE INSTALLATION AND OPERATION OF THIS PRODUCT.
Before using the MS Series, read all instructions and cautionary markings. Also, be sure to review
the individual manuals provided for each component of the system. The installation instructions
are for use by qualified personnel only. Do not perform any installation or servicing other than
that specified in this owner’s manual unless you are qualified to do so. Incorrect installation or
servicing may result in a risk of electric shock, fire, or other safety hazard.
Safety Symbols
The following safety symbols have been placed throughout this manual to indicate dangerous and
important safety instructions.
WARNING: This symbol indicates that failure to take a specified action could result in
physical harm to the user.
CAUTION: This symbol indicates that failure to take a specified action could result in
damage to the equipment.
Info: This symbol indicates information that emphasizes or supplements important
points of the main text.
Safety Precautions
• All electrical work must be performed in accordance with local and national electrical codes.
• This product is designed for indoor/compartment installation. It must not be exposed to rain,
snow, moisture, or liquids of any type.
• Use insulated tools to reduce the chance of electrical shock or accidental short circuits.
• There are no user-serviceable parts contained in this product.
• This unit is provided with integral protection against overloads.
• Live power may be present at more than one point since an inverter utilizes both DC (batteries,
PV, etc.,) and AC (utility or generator) power. To reduce risk of electric shock, ensure all DC
and AC wiring is disconnected prior to installing or performing maintenance on the inverter.
Turning off the inverter will not reduce this risk, the inverter must be totally disconnected from
all sources.
• Use Class 1 wiring methods for field wiring connections to terminals of a Class 2 circuit.
• Listed or labeled equipment shall be installed and used in accordance with any instructions
included in the listing or labeling.
• Always verify proper wiring prior to starting the inverter.
• Use only copper wires with a minimum temperature rating of 75°C.
• AC wiring must be no less than 10 AWG (5.3 mm²) gauge copper wire.
• Battery cables should be no less than #4/0 AWG for 12 and 24-volt systems. Crimped and
sealed copper ring terminal lugs with a 5/16 hole should be used to connect to the DC
terminals on the inverter.
• Torque all AC wiring connections and DC cable connections to the required torque values.
• The inverter must be properly mounted, see Section 2.2 “Mounting the Inverter” in this
manual.
• Overcurrent protection for the battery supply is not provided as an integral part of this
inverter. Overcurrent protection of the battery cables must be provided as part of the system
installation. Refer to Section 2.4 “DC Wiring” for more information.

Safety Information
Page iii
• Overcurrent protection for the AC output wiring is not provided as an integral part of this
inverter. Overcurrent protection of the AC output wiring must be provided as part of the
system installation. Refer to Section 2.5 “AC Wiring” for more information.
• The AC output neutral conductor and the DC negative conductors are not connected (bonded)
to the inverter chassis. Both the input and output conductors are isolated from the enclosure
and each other. System grounding, if required, is the responsibility of the system installer and
must comply with local and national electrical codes and standards. Refer to the Section 2.6
“Grounding Inverters” for more information.
Battery Safety
• Use insulated tools and be very careful when working around batteries, they can produce
extremely high currents if short-circuited (e.g., dropping a metal tool across the battery
terminal), which could cause a fire or explosion.
• Read and follow the battery manufacturer’s safety precautions before installing the inverter
and batteries. Always verify proper polarity and voltage before connecting the batteries
to the inverter. Once the batteries are connected to the inverter, ensure the maintenance
and charging requirements (i.e., charge voltage and charge rate) provided by the battery
manufacturer are followed to extend the life of the batteries and to prevent damage to the
batteries while charging.
• Wear eye protection such as safety glasses, and avoid touching your eyes and face when
working with batteries to keep any fluid/corrosion on the battery from coming in contact
with eyes and skin. Have plenty of fresh water and soap nearby and thoroughly wash in case
battery acid contacts skin, clothing, or eyes. In the event of exposure to the eyes, flood them
for at least 15 minutes with running water and seek immediate medical attention. Baking soda
neutralizes lead acid battery electrolyte and vinegar neutralizes spilled NiCad and NiFe battery
electrolyte; depending on your battery type, keep a supply on hand near the batteries.
• Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing
maintenance on the batteries and inverter. A battery can produce a short-circuit current high
enough to weld metal jewelry, causing severe burns.
• Never work alone. Always have someone within the range of your voice or close enough to
come to your aid when working around batteries.
• Use proper lifting techniques when working with batteries.
• Never use old or untested batteries. Check each battery’s label for age, type, and date code
to ensure all batteries are identical.
• Batteries are sensitive to changes in temperature. Install batteries in a stable environment.
• Batteries can produce explosive gasses, so install batteries in a well-ventilated area. For
compartment or enclosure installations, always vent batteries from the highest point to the
outside. Design the battery enclosure to prevent accumulation and concentration of hydrogen
gas in “pockets” at the top of the compartment.
• Provide at least one inch of air space between batteries to provide optimum cooling.
• Never smoke or allow a spark near batteries.
• To prevent a spark at the battery and reduce the chance of explosion, always connect the
cables to the batteries first. Then connect the cables to the inverter.
• Never charge a frozen battery.
• The battery bank should be installed in a clean, dry, ventilated environment where they are
protected from high and low temperatures. If installed in a vehicle/boat, the batteries must be
mounted upright (if using liquid batteries) and securely fastened. The location must be fully
accessible and protected from exposure to heat producing devices, and away from any fuel
tanks.

Safety Information
© 2012 Magnum Energy, Inc.Page iv
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
CE MANUEL CONTIENT DE IMPORTANTES POUR LA SÉRIE MS ONDULEUR/CHARGEUR QUI DOIVENT
ETRE SUIVIES PENDANT L’INSTALLATION ET FONCTIONNEMENT DE CE PRODUIT. Avant d’utiliser la
série MS, lire toutes les instructions etles mises en garde. Aussi, n’oubliez pas depasser en revue les
différents manuels fournispour chaque composant du système. Lesinstructions d’installation sont pour
une utilisationpar du personnel qualifié. Ne pas effectuer une installation ou d’entretien autres que
ceux spécifiés dans ce manuel, sauf si vous êtes qualifié pour le faire. Une mauvaise installation ou
d’entretien peut entraîner un risque de choc électrique, un incendie ou autre danger pour la sécurité.
Symboles de sécurité
Les symboles de sécurité suivants ont été placéstout au long de ce manuel pour indiquer des
conditions dangereuses et les consignes de sécurité importantes.
AVERTISSEMENT: Ce symbole indique que le défaut de prendre une action spécifiée
pourraitcauser des dommages physiques à l’utilisateur.
ATTENTION: Ce symbole indique que le défaut de prendre une action spécifiée peut
entraîner des dommages à l’équipement.
Info: Ce symbole indique une information qui met l’accent ou des suppléments points
importants du texte principal.
Consignes de sécurité
• Tous les travaux électriques doivent être effectués en conformité avec les codes locaux et
nationaux électriques.
• Ce produit est conçu pour l’installation / du compartiment intérieur. Il ne doit pas être exposé
à la pluie, la neige, l’humidité ou des liquides de tout type.
• Utiliser des outils isolés pour réduire le risque de choc électrique ou courts-circuits accidentels.
• Il n’y a pas réparable par l’utilisateur contenues dans ce produit.
• Cet appareil est fourni avec une protection intégrale contre les surcharges.
• Puissance en direct peuvent être présents à plus d’un point depuis un onduleur utilise à la fois
DC (piles, PV, etc) et AC (utilitaire ou générateur) d’alimentation. Pour réduire le risque de
choc électrique, assurez-vous que tout le câblage DC et AC est débranchée avant l’installation
ou la maintenance sur le variateur. Mise hors tension de l’onduleur ne réduira pas ce risque,
l’onduleur doit être totalement déconnectée de toutes les sources.
• Utiliser des méthodes de câblage classe 1 pour les connexions de câblage sur le terrain aux
bornes d’un circuit de Classe 2.
• Coté ou étiquetés équipement doit être installé et utilisé conformément aux instructions
figurant dans la liste ou l’étiquetage.
• Toujours vérifier le câblage avant de commencer l’onduleur.
• Utilisez des fils de cuivre seulement avec une cote de température minimale de 75° C.
• AC câblage ne doit pas être inférieure à 10 AWG (5.3 mm²) de cuivre de calibre.
• Les câbles de batterie ne doit pas être inférieur à # 4/0 AWG pour 12 et 24-volts systèmes.
Frisées et scellé cosses en cuivre anneau des bornes avec un trou de 5/16 doit être utilisé
pour se connecter à des bornes de courant continu sur l’onduleur.
• Couple toutes les connexions de câblage ca et les connexions de câbles à courant continu à
des valeurs de couple nécessaires.
• L’onduleur doit être correctement monté, voir le montage de la section onduleur dans le
chapitre Installation de ce manuel.
• Protection contre les surintensités pour l’alimentation de la batterie n’est pas fourni en tant
que partie intégrante de cet inverseur. La protection contre les surintensités des câbles de
batterie doivent être fournis dans le cadre de l’installation du système. Reportez-vous à la
section Câblage cc dans le chapitre d’installation pour plus d’informations.

Safety Information
Page v
• Protection contre les surintensités pour le câblage de sortie AC n’est pas fourni en tant que
partie intégrante de cet onduleur. Protection contre les surintensités du câblage de sortie CA
doit être fournie dans le cadre de l’installation du système. Reportez-vous à la Section 2.5
Câblage ca dans le chapitre d’installation pour plus d’informations.
• Le conducteur de sortie CA conducteurs neutre et continue négative ne sont pas connectés
(servitude) au châssis inverseur. La fois l’entrée et des conducteurs de sortie sont isolés de
l’enceinte et l’autre. La terre du système, si nécessaire, est de la responsabilité de l’installateur
du système et doit se conformer à des codes locaux et nationaux et les normes électriques.
Reportez-vous à la Section 2.6 Mise à la terre Onduleurs dans le chapitre d’installation pour plus
d’informations.
Sécurité de la batterie
• Utiliser des outils isolés et être très prudent lorsque vous travaillez près des batteries, elles peuvent
produire des courants extrêmement élevés si en court-circuit (par exemple, échapper un outil
métallique à travers la borne de la batterie), ce qui pourrait provoquer un incendie ou une explosion.
• Lisez et suivez les consignes de sécurité du fabricant de la batterie avant d’installer l’onduleur
et des batteries. Toujours vérifier la polarité et la tension avant de brancher les batteries à
l’onduleur. Une fois que les batteries sont connectées à l’onduleur, assurer la maintenance et
les exigences de charge (c.-à-tension de charge et taux de charge) fournis par le fabricant de
la batterie sont suivies pour prolonger la vie des batteries et pour éviter d’endommager les
batteries pendant la charge.
• Porter des lunettes de protection tels que des lunettes de sécurité, et évitez de toucher vos yeux
et le visage lorsque l’on travaille avec des piles de garder tout fluide / corrosion sur la batterie
d’entrer en contact avec les yeux et la peau. Ayez suffisamment d’eau fraîche et de savon à
proximité et se laver dans le cas d’acide contact avec la peau de la batterie, les vêtements ou les
yeux. Dans le cas d’exposition pour les yeux, les inonder pendant au moins 15 minutes à l’eau
courante et consulter immédiatement un médecin.Le bicarbonate de soude neutralise l’acide
de plomb électrolyte de la batterie et le vinaigre neutralise renversé NiCad et NiFe batterie à
électrolyte; en fonction de votre type de batterie, gardez sous la main près des batteries.
• Enlevez tous les bijoux tels que bagues, montres, bracelets, etc, lors de l’installation ou la
maintenance sur les batteries et l’onduleur. Une batterie peut produire un court-circuit assez
de courant élevé pour souder les bijoux en métal, provoquant de graves brûlures.
• Ne jamais travailler seul. Toujours avoir quelqu’un au sein de la gamme de votre voix ou
suffisamment près pour vous venir en aide lorsque vous travaillez près des batteries.
• Utiliser des techniques de levage appropriées lorsque vous travaillez avec des piles.
• Ne jamais utiliser de piles usagées ou non testés. Vérifiez l’étiquette de chaque batterie à
l’âge, le type et le code de date afin d’assurer toutes les batteries sont identiques.
• Piles sensibles aux changements temporaires, installer dans un environnement stable.
• Les batteries peuvent produire des gaz explosifs, etc installer les piles dans un endroit bien
ventilé. Pour les installations compartiment ou une enceinte, toujours évacuer les piles du
plus haut point à l’extérieur. Concevoir le boîtier de piles pour éviter l’accumulation et la
concentration de gaz d’hydrogène dans “poches” en haut du compartiment.
• Fournir au moins un pouce de l’espace aérien entre les batteries pour fournir un refroidissement optimal.
• Ne jamais fumer ou laisser une étincelle près des batteries.
• Pour éviter une étincelle à la batterie et de réduire le risque d’explosion, toujours connecter
les câbles aux batteries en premier. Ensuite, connectez les câbles à l’onduleur.
• Ne jamais charger une batterie gelée.
• La banque de la batterie doit être installé dans un endroit propre, sec, aéré et où ils sont
protégés contre les températures élevées et basses. S’il est installé dans un véhicule / bateau,
les batteries doivent être monté en position verticale (si vous utilisez des piles liquides) et
solidement fixés. L’emplacement doit être pleinement accessible et protégé contre l’exposition
à la chaleur la fabrication de dispositifs, et loin de toute réservoirs de carburant.

© 2012 Magnum Energy, Inc.Page vi
Table of Contents
Important Safety Information...............................................................ii
1.0 Introduction..................................................................................1
1.1 Features and Benefits................................................................................. 2
1.2 How an Inverter/Charger Works................................................................... 5
1.3 Advantages of a Pure Sine Wave vs Modified Sine Wave Inverter...................... 6
1.4 Appliances and Run Time............................................................................ 7
2.0 Installation ...................................................................................8
2.1 Pre-Installation.......................................................................................... 8
2.2 Mounting the Inverter ...............................................................................11
2.3 Wiring the Inverter - General Requirements .................................................13
2.4 DC Wiring................................................................................................14
2.5 AC Wiring ................................................................................................21
2.6 Grounding Inverters..................................................................................34
2.7 Inverter Notification Requirements ..............................................................41
2.8 Final Inspection........................................................................................41
2.9 Functional Test .........................................................................................42
3.0 Operation....................................................................................44
3.1 Inverter Mode ..........................................................................................44
3.2 Standby Mode ..........................................................................................45
3.3 Battery Charging ......................................................................................45
3.4 Transfer Time...........................................................................................47
3.5 Battery Temperature Sensor.......................................................................47
3.6 Protection Circuitry Operation.....................................................................48
3.7 Inverter Startup .......................................................................................49
3.8 Factory Default Values...............................................................................50
3.9 Inverter Fan Operation ..............................................................................51
3.10 Using a Remote with the MS Series Inverter.................................................51
4.0 Maintenance and Troubleshooting...............................................52
4.1 Recommended Inverter and Battery Care.....................................................52
4.2 Storage for Mobile Installations...................................................................52
4.3 Troubleshooting........................................................................................53
4.4 Performing an Inverter Reset......................................................................54
4.5 Performing a Power Reset ..........................................................................54
Appendix A – Specifications and Optional Equipment..........................55
A-1 Inverter/Charger Specifications ..................................................................55
A-2 Inverter Efficiency.....................................................................................56
A-3 AC Input Voltage to Output Charge Amps........................................................... 56
A-4 Optional Equipment and Accessories............................................................57
Appendix B – Battery Information.......................................................58
B-1 Battery Location .......................................................................................58
B-2 Battery Types...........................................................................................58
B-3 Battery Temperature .................................................................................58
B-4 Battery Bank Sizing ..................................................................................58
B-5 Battery Bank Sizing Worksheet...................................................................59
B-6 Battery Wiring Configurations.....................................................................60
Appendix C – Inverter/Charger Terminology.......................................63
Limited Warranty ................................................................................65
How to Receive Repair Service ............................................................65

Page vii © 2012 Magnum Energy, Inc.
List of Figures
Figure 1-1, Power Switch, Status LED, and Accessory Connection Ports................................ 2
Figure 1-2, Electrical Connection Points ........................................................................... 3
Figure 1-3, Left Side Features (MS2012, MS2812, MS2024, MS4024) .................................. 4
Figure 1-4, Left Side Features (MS2000 Series) ................................................................ 5
Figure 1-5, AC Waveforms ............................................................................................. 6
Figure 2-1, Simplified Installation Diagram for Permanent Installations ................................ 9
Figure 2-2, Approved Mounting Positions ........................................................................11
Figure 2-3, MS Series Dimensions and Side Reference......................................................12
Figure 2-4, DC and Battery Temperature Sensor Wiring ....................................................15
Figure 2-5, Battery Hardware Installation .......................................................................17
Figure 2-6, Inverter DC Hardware Installation .................................................................17
Figure 2-7, Battery Temperature Sensor .........................................................................19
Figure 2-8, AC Terminal Block .......................................................................................22
Figure 2-9, AC Wiring for Single In – Single Out (30 A) Configurations................................25
Figure 2-10, AC Wiring for Single In – Single Out (60 A) Configurations ..............................26
Figure 2-11, AC Wiring for Single In – Dual Out Configurations ..........................................27
Figure 2-12, AC Wiring for Dual In – Single Out Configurations ..........................................28
Figure 2-13, AC Wiring for Dual In – Dual Out Configurations ............................................29
Figure 2-14, AC Wiring for MS2000 Models .....................................................................32
Figure 2-15, AC Wiring for MS2000-15B/-20B Models .......................................................33
Figure 2-16, Grounding System for MS Series .................................................................34
Figure 2-17, Multiple Connections to DC Ground Rod (Method 1)........................................35
Figure 2-18, Multiple Connections to DC Ground Rod (Method 2)........................................36
Figure 2-19, Single Connection to DC Ground Rod (Method 3) ...........................................36
Figure 2-20, Neutral-to-Ground Connection (Inverter Mode)..............................................39
Figure 2-21, Neutral-to-Ground Connection (Standby Mode)..............................................39
Figure 2-22, Disconnecting the Neutral-to-Ground Connection ...........................................40
Figure 2-23, Connecting a Large DC Ground Wire ............................................................40
Figure 2-24, Warning Label...........................................................................................41
Figure 2-25, AC Voltage Checks.....................................................................................43
Figure 2-26, AC Voltage Checks (MS2000 models) ...........................................................43
Figure 2-27, AC Voltage Checks (MS2000-15B/-20B models).............................................43
Figure 3-1, Power Flow – Inverter Mode..........................................................................44
Figure 3-2, Power Flow – Standby Mode .........................................................................45
Figure 3-3, Automatic 4-Stage Charging Graph................................................................46
Figure 3-4, BTS Temperature to Charge Voltage Change ...................................................47
Figure 3-5, Power Switch and Status Indicator.................................................................49
Figure 4-1, Performing an Inverter Reset ........................................................................54
Figure A-1, MS Series Efficiency Chart ............................................................................56
Figure A-2, MS Series VAC Input to Charge Amps ............................................................56
Figure B-1, Series Battery Wiring...................................................................................60
Figure B-2, Parallel Battery Wiring .................................................................................60
Figure B-3, Series-Parallel Battery Wiring .......................................................................60
Figure B-4, Battery Bank Wiring Examples (12-volt).........................................................61
Figure B-5, Battery Bank Wiring Examples (24-volt).........................................................62

© 2012 Magnum Energy, Inc.Page viii
List of Tables
Table 1-1, Typical Appliance Power Consumption............................................................... 7
Table 2-1, Recommended DC Wire/Overcurrent Device for Rated Use .................................16
Table 2-2, DC Wire Size For Increased Distance ...............................................................17
Table 2-3, AC Input/Output Wiring Configurations (MS2012, MS2812, MS2024, MS4024)......24
Table 2-4, AC Input/Output Wiring Configurations (MS2000 models)...................................31
Table 2-5, AC Grounding Electrode Conductor Sizing ........................................................35
Table 2-6, Equipment Grounding Conductor Sizing ...........................................................37
Table 3-1, Inverter Battery Turn On/Off Levels.................................................................48
Table 3-2, Inverter/Charger Default Values .....................................................................50
Table 3-3, Inverter Compatibility Level ...........................................................................51
Table 4-1, Basic Troubleshooting....................................................................................53
Table A-1, Inverter/Charger Specifications ......................................................................55

© 2012 Magnum Energy, Inc.Page 1
Introduction
1.0 Introduction
Congratulations on your purchase of a MS Series inverter/charger from Magnum Energy. The MS
Series is a “pure” sine wave inverter designed especially for rugged mobile applications, home
backup power, and standalone applications. Powerful, yet simple to use, this inverter/charger will
provide you with years of trouble-free performance you have come to expect from Magnum Energy.
Installation is easy. Simply connect the inverter’s output to your distribution circuits or electrical
panel, connect your utility or AC generator power to the inverter’s easy-to-reach terminal block,
connect the batteries, and then switch it on for power.
Info: This is a sizable manual and much of it is fairly technical. Terms may be used
throughout the manual that are unfamiliar to you. Refer to the Inverter/Charger
Terminology glossary in Appendix C for clarification.
The MS Series inverter/charger includes the following:
• 2000, 2800, or 4000 watt model in a small footprint – less area needed for installation
• Pure sine wave output
• Automatic PFC (Power Factor Corrected) multi-stage battery charging
• RS485 standard communication protocol
• Remote and Network ports (easy connection for optional accessories)
• Inverter-mounted ON/OFF switch with LED indicator
• 30-amp per leg AC pass-thru capability
• Field serviceable for qualified personnel – tested repair kits available
• Automatic battery temperature compensation (when using the Battery Temperature Sensor)
for optimum charging even during extreme temperature changes
• Overcurrent, over-temperature, and high/low battery voltage protection
The following accessories are also available for use with the MS Series inverter/charger:
• ME-AGS-N (Automatic Generator Start Module – Network version) – automatically starts/
stops your generator.
• ME-ARC50 (Advanced Remote Control) – easy to read LCD display panel that allows advance
inverter set up, control, and troubleshooting.
• ME-BMK(Battery MonitorKit -with Shunt)– providesprecise DCvoltage/currentmeasurements
and information on your battery’s State of Charge (SOC) condition.
• ME-RC50 (Standard Remote Control) – easy to read LCD display panel that allows standard
inverter set up, control, and troubleshooting.
Regulatory Compliance
The MS Series inverter/charger is designated as a Standalone (non grid-interactive) power
inverter with an internal battery charger. It can be connected to the utility grid (or to a generator)
to allow the inverter batteries to be charged, and to power inverter loads while connected. The
MS series is not a grid-interactive (also known as utility-interactive) inverter and does not have
the capability to export (or sell) power back into the utility grid.
The MS Series has been tested and listed to UL 458, 5th Edition (Power Converters/Inverters
and Power Converter/Inverter Systems for Land Vehicles and Marine Crafts) and UL 1741, 2nd
Edition¹(Inverters, Converters and Controllers for Use in Independent Power Systems) for use
in the US; and is also certified to CSA C22.2 No. 107.1-01 (General Use Power Supplies) for use
in Canada. It has been tested and certified to these product safety standards by Intertek Testing
Services (known as ETL), which is a Nationally Recognized Testing Laboratory (NRTL). NRTL’s
are qualified organizations that meet Occupational Safety and Health Administration (OSHA)
regulations to perform independent safety testing and product certification.
The MS Series also meets the KKK-A-1822E standard for use in ambulances.
Note¹ – The MS2000 models are not listed to the UL 1741 standard.

Page 2
© 2012 Magnum Energy, Inc.
Introduction
1.1 Features and Benefits
The MS Series inverter/charger is designed to allow easy access to wiring, circuit breakers, and
controls. Its die cast baseplate with one-piece aluminum cover ensures maximum durability with
minimum weight, as well as a cooler, more efficient operation.
The front of the MS inverter is equipped with the following features (refer to Figures 1-1 and
1-2):
1Power ON/OFF Switch – a momentary pushbutton switch that alternately turns the
inverter on or off.
2Status LED Indicator – this green LED illuminates to provide information on inverter
or charger operation.
3Stack/Accessories Connection Port (red label) – a RJ11 port that allows series-
stacking, and accepts the optional RSAs (Remote Switch Adapters) for remote on/off
switch operation.
Info: The series-stacking capability—which allows two units to provide 120/240 VAC
output—is only available on the MS4024 inverter/charger. See the ME-SSI owner’s
manual (PN: 64-0009) for additional information on series stacking.
4Network Connection Port (green label) – a RJ11 port that accepts optional network
capable accessories (i.e., Auto Gen Start or Battery Monitor).
5Remote Connection Port (blue label) – a RJ11 port that allows an optional remote
control to be connected.
6Battery Temperature Sensor Connection Port (yellow label) – a RJ11 port that
accepts the remote Battery Temperature Sensor (BTS).
Figure 1-1, Power Switch, Status LED, and Accessory Connection Ports
1
2
3
4
5
6
Power ON/OFF Switch
Status LED
(charging/inverting)
Stack/Accessories Port
(red label – RJ11 connection)
Network Port
(green label – RJ11 connection)
Remote Port
(blue label – RJ11 connection)
Battery Temp Sensor Port
(yellow label – RJ11 connection)

© 2012 Magnum Energy, Inc.Page 3
Introduction
Figure 1-2, Electrical Connection Points
9
10
8
712
11
Positive (+)
DC Terminal
(under cover)
Negative (-)
DC Terminal
(under cover)
Mounting
Flange
DC
Equipment
Ground
Terminal
AC Entry/
Exit
Connections
Intake Air Vents
(and on right side)
7DC Equipment Ground Terminal – this connection is used to tie the exposed chassis
of the inverter to the DC grounding system. This terminal accepts CU/AL conductors from
#14 to #2 AWG (2.1 to 33.6 mm2).
8AC Entry/Exit Connections – two 3/4” knockouts provided with cable-clamp strain
reliefs to accommodate and secure the AC input and output field wiring.
9Intake Air Vents –ventilation openings to pull in air to help keep the inverter cool for
peak performance.
10 Positive DC Terminal – provides a 360 degree connection point for the positive (+) cable
from the battery bank; consists of a 5/16-18 bolt with a Kep or Flange nut that holds the
battery cable to the DC terminal.
11 Negative DC Terminal – provides a 360 degree connection point for the negative (-)
cable from the battery bank; consists of a 5/16-18 bolt with a Kep or Flange nut that
holds the battery cable to the DC terminal.
12 Mounting Flange – used to secure the inverter to a shelf or wall.

Page 4
© 2012 Magnum Energy, Inc.
Introduction
Figure 1-3, Left Side Features (MS2012, MS2812, MS2024, MS4024)
The left side of the MS Series inverter is equipped with the following features (see Figures 1-3 & 1-4):
13 Exhaust Air Vents – ventilation openings that allow heated air to be removed by the
internal cooling fan.
14 Model/Serial Number Label –includes model/serial number information, date of
manufacture, and inverter and charger specifications. See the MS specifications in
Appendix A for more information and a list of available models.
15 AC Access Cover – provides access to the internal AC wiring terminal block (see Figure
2-8). This terminal block is used to hardwire all inverter AC input and output wiring
connections. Remove the two screws to access the AC wiring terminal block. The MS2000
models do not have the AC wiring terminal block.
16 AC Input Circuit Breaker (CB3) – this circuit breaker protects the unit’s internal
charger wiring and pass-thru relay while in Standby mode. The circuit breaker pops out
when it opens – press in to reset. The input circuit breaker is not branch-rated, therefore
branch-rated circuit breakers must be installed in the inverter’s input wiring.
17 AC Output Circuit Breakers (CB1 & CB2) – these circuit breakers are branch-rated
and are only available on models MS2000-15B, MS2000-20B, MS2012-15B, and MS2012-
20B. They allow the inverter AC loads to be connected directly to the inverter’s output
without requiring an inverter sub-panel. These circuit breakers pop out when they open
– press in to reset. They can also be manually pulled to disconnect the inverter’s loads.
CAUTION: Inverter models without the output circuit breakers (CB1 and CB2) must
have branch-rated circuit breakers installed in the inverter’s output wiring.
CAUTION: The inverter’s internal AC transfer relay is rated for 30 amps per leg. The
pass-thru current must be no greater than 30 amps per leg or damage to the relays
may occur.
14
15
13
17 16
AC Access Cover
Model/Serial
Number Label
AC Input Circuit
Breaker
AC Output Circuit Breakers
(only available on -15B,
-20B output breaker models)
Exhaust
Air Vents
(back side)

© 2012 Magnum Energy, Inc.Page 5
Installation
1.2 How an Inverter/Charger Works
There are two modes of operation associated with this inverter/charger:
• Inverter Mode:
When the inverter is properly connected to batteries and turned on, the direct current
(DC) from the batteries is transformed into a pure sine wave alternating current (AC).
This AC is similar to the voltage provided by your utility and is used to power any electrical
appliances (i.e., AC loads) connected to the inverter’s output.
• Standby Mode:
When an external source of AC power (i.e., utility power or generator) is connected and
qualified on the inverter’s AC input, it operates in Standby mode. In Standby mode,
the unit operates as a battery charger to convert the incoming AC power into DC power
to recharge the batteries; and at the same time, automatically closes an internal
AC transfer relay to pass the incoming AC power directly to the inverter’s output to continue
powering the connected electrical appliances.
1.2.1 Inverter Applications for Permanent Installations
An inverter can be used for backup power in a permanent location that normally uses utility power,
such as a home or office. When utility power is available, the inverter keeps the batteries charged.
When the utility power fails, the inverter comes on automatically to supply AC power to your home
or office during the power failure. For a home or business, reliable backup power is needed to
prevent lost computer data, or to maintain lights and keep food fresh in the refrigerator/freezer.
In some areas, where utility power is not available, this inverter can be used in a standalone
renewable power system. The inverter allows AC electrical appliances to be run from the storage
battery bank. When the battery bank becomes discharged, either renewable DC sources (solar,
wind, or hydro power) can be used to recharge the batteries, or a generator can be connected to
the inverter to power the system while the batteries recharge.
1.2.2 Inverter Applications for Mobile Installations
Inverters can also be used to provide power in mobile situations, such as in an RV, truck, or boat.
In these applications, the inverter provides power to the AC loads using the energy stored in the
batteries and recharges the batteries when shorepower or an onboard generator is available.
Figure 1-4, Left Side Features (MS2000 Series)
15
AC Access Cover
AC Input Circuit Breaker
AC Output Circuit Breakers
(on -15B, -20B output
breaker models only)
16
17
Note1: The model shown is not a -15B or -20B model, therefore it does not show any AC output breakers
Models without output breakers (CB1 & CB2) use carriage bolts to fill the breaker openings.

Page 6
© 2012 Magnum Energy, Inc.
Introduction
1.3 Advantages of a Pure Sine Wave vs a Modified Sine Wave Inverter
Today’s inverters come in three basic output waveforms: square wave, modified sine wave (which
is actually a modified square wave) and pure sine wave (see Figure 1-5). Modified sine wave
inverters approximate a pure sine wave form and will run most appliances and electronics without
any problems. These inverters are less expensive, and therefore, offer a viable alternative to more
expensive pure sine inverters.
The output of the MS Series inverter—which is pure sine wave—is equal to, or in many cases,
better than the utility power used in your home. Virtually any electronic device will operate from a
pure sine wave inverter. Motors run cooler, microwaves usually cook faster, and clocks keep better
time just to name a few examples. Without compromising quality or performance, the MagnaSine
provides you with all the advantages of a pure sine wave inverter at a much lower cost than many
on the market.
The MS Series is built on the same platform as our popular ME and RD Series modified sine
wave inverters—allowing for an easy upgrade to a pure sine wave inverter from the original ME
or RD Series installation. This standard platform also helps reduce cost by using standard parts/
accessories across many models. Magnum accessories such as the Advanced Remote Control (ME-
ARC), Standard Remote Control (ME-RC), Automatic Generator Start - Networked (ME-AGS-N),
and Battery Monitor Kit (ME-BMK) can be used.
TIME
VOLTAGE
40
80
0
120
40
160
200
80
120
160
200
Modified
Sine Wave
Sine Wave
Square Wave
1.3.1 Output Waveform
The inverter’s output waveform is the shape of the wave that alternating current makes as its
voltage rises and falls with time (see Figure 1-5 below). The three basic output waveforms are:
• Modified Sine Wave – Also referred to as a “quasi sine wave” or a “modified square wave”.
This output looks like a one-step staircase and the waveform changes its width to continually
provide the correct RMS output voltage regardless of the battery voltage. Most loads that run
from a sine wave will also run from a modified sine wave. However, things such as clocks and
furnace controllers may have trouble.
• Sine Wave – An AC waveform that looks like rolling waves on water. It rises and falls smoothly
with time. The grid puts out a sine waveform. Any plug-in AC equipment will operate from a
sine wave output inverter.
• Square Wave – The simplest AC waveform. Some types of equipment behave strangely
when powered from a square wave inverter.
Figure 1-5, AC Waveforms

© 2012 Magnum Energy, Inc.Page 7
Introduction
1.4 Appliances and Run Time
The MS Series inverter/charger can power a wide range of household appliances including small
motors, hair dryers, clocks, and other electrical devices. As with any appliance using batteries for
power, there is a certain length of time that it can run – this is called “run time.” Actual run time
depends on several variables including the size and the type of appliance, the type of batteries
installed in your application, as well as the battery’s capacity and age. Other factors such as the
battery’s state of charge and temperature can also affect the length of time your appliances can run.
Appliances (TVs, VCRs, stereos, computers, coffee pots, incandescent lights, and toasters) can all
be successfully powered by your inverter. Larger electrical appliances, however, such as stoves,
water heaters, etc., can quickly drain your batteries and are not recommended for this application.
All electrical appliances are rated by the amount of power they consume (see Table 1-1). The rating
is printed on the product’s nameplate label, usually located on its chassis near the AC power cord.
Even though it is difficult to calculate exactly how long an inverter will run a particular appliance,
the best advice is trial and error. Your MS Series inverter has a built-in safeguard that automatically
protects your batteries from over-discharge.
Info: For optimum performance, a minimum battery bank of 200 AH is recommended
for moderate loads (<1000W) and greater than 400 AH for heavy loads (≥1000W).
Table 1-1, Typical Appliance Power Consumption
Device Load Device Load
Blender 400W Coffee Maker 1200W
Computer 300W Color TV 150W
Drill 500W Hair Dryer 1000W
Hot Plate 1800W Iron 1000W
Light (Flo) 10W Light (Inc) 100W
Microwave 1000W Refrigerator 500W

Page 8
© 2012 Magnum Energy, Inc.
Installation
2.0 Installation
Info: Installations should be performed by qualified personnel, such as a licensed
or certified electrician. It is the installer’s responsibility to determine which safety
codes apply and to ensure that all applicable installation requirements are followed.
Applicable installation codes vary depending on the specific location and application of
the installation.
CAUTION: Review the “Important Product Safety Information” on pages ii-v before
any installation.
CAUTION: The inverter is heavy. Use proper lifting techniques during installation to
prevent personal injury.
The simplified system diagram shown in Figure 2-1 should be reviewed to assist you in planning
and designing your installation. This drawing is not intended to override or restrict any national
or local electrical codes. This drawing should not be the determining factor as to whether the
installation is compliant, that is the responsibility of the electrician and the on-site inspector.
2.1 Pre-Installation
Before proceeding, read the entire Installation section to determine how best to install your MS
inverter/charger. The more thorough you plan in the beginning, the better your inverter needs
will be met.
2.1.1 Unpacking and Inspection
Carefully remove the MS Series inverter/charger from its shipping container and inspect all contents.
Verify the following items are included:
• The MS inverter/charger
• Red and black DC terminal covers with Phillips screws
• AC access cover with two Phillips screws
• Two 5/16” Kep or Flange nuts (installed on the DC terminals)
• Battery Temperature Sensor
• Warning label
• MS Series Owner’s Manual
If items appear to be missing or damaged, contact your authorized Magnum Energy dealer or
Magnum Energy. If at all possible, keep your shipping box to help protect your inverter from
damage if it ever needs to be returned for service. Save your proof-of-purchase as a record of
your ownership; it will also be needed if the unit should require in-warranty service.
Record the unit’s model and serial number in the front of this manual in case you need to provide
this information in the future. It is much easier to record this information now, instead of trying
to gather it after the unit has been installed.
2.1.2 Required Tools and Materials
Hardware/Materials
• Conduit, strain-reliefs and appropriate fittings • 1/4” mounting bolts and lock washers
• Electrical tape • Wire ties
Tools
• Miscellaneous screwdrivers • Pliers • Wire strippers
• Drill and drill bits • Pencil or marker • Multimeter
• Level • 1/2” wrench

© 2012 Magnum Energy, Inc.Page 9
Installation
Figure 2-1, Simplified Installation Diagram for Permanent Installations
Battery Bank
120/240VAC
power to
inverter
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
240
VAC 120
VAC
120
VAC
DC
Overcurrent
Protection
(breaker or
fuse/switch)
MS Series
Inverter/
Charger
Main Panel Sub-Panel
120VAC inverter power
(or 120/240VAC pass-thru power)
to sub-panel
ME-BMK
Battery Monitor
with shunt
(Magnum
Accessory)
DC
Shunt
AC
Transfer
Switch
Generator Power
120/240VAC Output
Utility Power
120/240VAC Output
FluxCapacitorGenerator
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
BTS
ON
OFF
ON
OFF
30A
30A
ME-SBC
Smart Battery
Combiner
(Magnum
Accessory)
ME-AGS-N
Auto Gen Start
Controller
(Magnum
Accessory)
SELECT
TECH
AGS METER SETUPSHOREINVERTER
CHARGER
INV
CHG
FAULT
PWR
ON/OFF
ON/OFF
Remote Controls (Magnum Accessories)
ME-RC50 ME-ARC50

Page 10
© 2012 Magnum Energy, Inc.
Installation
2.1.3 Locating the Inverter
Only install the inverter in a location that meets the following requirements:
Clean and Dry – The inverter should not be installed in an area that allows dust, fumes, insects,
or rodents to enter or block the inverter’s ventilation openings. This area also must be free from
any risk of condensation, water, or any other liquid that can enter or fall on the inverter. The
inverter uses stainless steel fasteners, plated copper busbars, a powder-coated aluminum base
and the internal circuit boards are conformal coated – to help fight the harmful effects of corrosive
environments. However, the inverter’s life is uncertain if used in these type of environments, and
inverter failure under these conditions is not covered under warranty.
Info: If the inverter is installed in an area where moisture may occur, we recommend
putting silicone dielectric grease compound into the electrical ports (Items 3-6 as
shown in Figure 1-1). Before installing the cables, or if leaving any ports open, squirt a
liberal amount into each port. Silicone dielectric compound makes an effective moisture
and corrosive barrier to help protect and prevent corrosion to the RJ11 connections.
Cool – The inverter should be protected from direct sun exposure or equipment that produces
extreme heat. The ambient temperature around the inverter must not exceed 77°F (25°C) to
meet power specifications.
Ventilation – In order for the inverter to provide full output power and to avoid over-temperature
fault conditions, do not cover or block the inverter’s ventilation openings or install this inverter in
an area with limited airflow. The inverter uses two fans to provide forced air cooling, these fans
pull in air through the intake vents (see Item 9, Figure 1-2) and blow out air through the exhaust
vents (see Item 13, Figure 1-3). Allow at the minimum an airspace clearance of 6” (15.2 cm) at
the intake and exhaust vents, and 3” (7.6 cm) everywhere else to provide adequate ventilation.
If installed in an enclosure, a fresh air intake opening must be provided directly to the front side
(intake vents) of the inverter and an exhaust opening on the back side (exhaust vents) of the
inverter. This allows cool air from the outside to flow into the inverter and heated air to exit the
inverter and the enclosure. When mounted in an enclosed compartment, airflow must be ≥100
cfm in order to maintain no more than a 68°F (20°C) rise in compartment temperature.
CAUTION: Do not mount this inverter in a zero clearance compartment, nor cover or
obstruct the ventilation openings – overheating may result.
Safe – Keep any flammable/combustible material (i.e., paper, cloth, plastic, etc.) that may be
ignited by heat, sparks, or flames at a minimum distance of 2 feet (61 cm) away from the inverter.
WARNING: The MS Series inverter/charger is not ignition-protected. Do not install this
inverter in any area that contains extremely flammable liquids like gasoline or propane.
Close to the battery bank – The inverter should be located as close to the batteries as possible.
Long DC wires tend to lose efficiency and reduce the overall performance of an inverter. However,
the unit should not be installed in the same compartment as the batteries or mounted where it will
be exposed to gases produced by the batteries. These gases are corrosive and will damage the
inverter; also, if these gases are not ventilated and allowed to collect, they could ignite and cause
an explosion.
Accessible –Do not block access to the inverter’s remote control and accessory ports, as well
as the inverter’s controls and status indicator. Allow enough room to access the AC and DC wiring
terminals and connections, as they will need to be checked and tightened periodically. See Figure
2-3 for the MS Series inverter/charger’s dimensions.
Away from sensitive electronic equipment – High powered inverters can generate levels of RFI
(Radio Frequency Interference). Locate any electronic equipment susceptible to radio frequency
and electromagnetic interference as far away from the inverter as possible.

© 2012 Magnum Energy, Inc.Page 11
Installation
2.2 Mounting the Inverter
The inverter base can reach a temperature up to 90°C (194°F) and should be mounted on a
noncombustible surface*. This surface and the mounting hardware must also be capable of
supporting at least twice the weight of the inverter. To meet regulatory requirements, the MS
Series must be mounted in one of the following positions as shown in Figure 2-2:
• above or under a horizontal surface (shelf or table),
• on a vertical surface (wall) with the DC terminals to the right,
• on a vertical surface (wall) with the DC terminals toward the bottom, the MP-HOOD (inverter
hood) installed on the top, and either the ME-CB (Conduit box), MMP series (single inverter
enclosure), or MP Series (multiple inverter enclosure) installed on the inverter’s bottom.
Info: The ME-CB, MMP and MP Series enclosures prevent material from falling out the
bottom in the event of an internal fire, and also allow sufficient ventilation to prevent the
inverter from overheating under normal operating conditions. The MP-HOOD inverter
hood helps prevent items from falling inside causing damage to the inverter.
Info: Magnum provides a backplate for mounting the inverter. These backplates also
provide the ability to mount either the MMP Series enclosure (PN: BP-MMP) or the MP
Series Enclosure (PN: BP-S single plate, or BP-D dual plate).
After determining the mounting position, refer to the physical dimensions as shown in Figure
2-3, or use the base of the inverter as a template to mark your mounting screw locations. After
marking the mounting screw locations, mount the unit with appropriate mounting hardware.
* Noncombustible surface – A surface made of material that will not ignite, burn, support combustion, or
release flammable vapors when subjected to fire or heat as per the ASTM E136 standard. For the most part,
these are materials that are largely comprised of inorganic materials such as stone, steel, iron, brick, tile,
concrete, slate, and glass. Avoid common building materials such as gypsum board as well as any paint, wall
coverings, and all types of wood.
Figure 2-2, Approved Mounting Positions
30
30
SHELF OR TABLE
MOUNTED
(RIGHT SIDE UP)
SHELF OR TABLE MOUNTED
(UP SIDE DOWN)
WALL MOUNTED
(DC TERMINALS TO THE RIGHT)
WALL MOUNTED
(DC TERMINALS
FACING DOWN*)
*WHEN THE INVERTER
IS MOUNTED IN THIS
POSITION, THE MP-HOOD
(INVERTER HOOD ON
TOP), AND THE ME-CB
(CONDUIT BOX ON BOTTOM)
OR MP/MMP SERIES
ENCLOSURES MUST BE
USED.
Other manuals for MS2000
1
This manual suits for next models
4
Table of contents
Other Magnum Inverter manuals
Popular Inverter manuals by other brands

Generac Power Systems
Generac Power Systems Guardian 005261-1 owner's manual

Robin America
Robin America RGX3600 parts manual

Simphoenix
Simphoenix DL100 Series user manual

Autarco
Autarco LH Series Installation and operation manual

Sharp
Sharp JH-3500U Installation & operator's manual

IMEON
IMEON 3.6 installation manual