Page 10
Optima 532 Series
• Local/On (up position) causes the PDU to ignore the On/Off/EPO commands of the remote panel. The local breakers
will then be in sole control of the outlets.
• Off (center position) causes an internal contactor to disengage power from all branches except for the CB1/J1 branch
which continues to be powered. The PDU will ignore the On/Off/EPO commands of the remote panel. Therefore, Off
disconnects power to almost all outlets even if the breakers are switched on.
If there will not be a remote On/Off/EPO panel connected to the PDU, switch the Outlet Control
Bus mode switch to the up position labeled Local/On. This is the normal operating position for any
unit with no remote panel. (The other positions will prevent power from getting to the outlets.)
Whether there is a remote control panel connected or not, toggling the Outlet Control Bus mode
switch to the center position labeled Off will disconnect power to almost all outlets even if the
breakers are switched on. The Off mode causes an internal contactor to disengage power from all
branches except for the CB1/J1 branch which continues to be powered.
3.3.2 Remote Bus Connectors
There are a total of four connectors, but note that there are two types of connectors. Based on the label of the top pin,
we call the two types the standard “enable” type, and the alternative “delay” type. There are three of the standard type (2
front, 1 back), and one of the delay type (on the back).
Multiple PDUs can be wired in a daisy-chain fashion to be operated by a single remote panel.
The standard enable connectors are J9, J10, J11. These are all wired in parallel.
The delay connector is J12. When used, the On signal from the remote panel is delayed by about 2 seconds.
J 2
J 3
J 4
J 10 J 11
Enable
Disable
Return
Delay
Disable
Return
J 7 J 6 J 5 J 1
J 2
J 3
J 4
J 10 J 11
Enable
Disable
Return
Delay
Disable
Return
J 7 J 6 J 5 J 1
J 2
J 3
J 4
J 10 J 11
Enable
Disable
Return
Delay
Disable
Return
Input
J 7 J 6 J 5 J 2
J 3
J 4
J 10 J 11
Enable
Disable
Return
Delay
Disable
Return
Input
J 7 J 6 J 5
Enable
Disable
Return
Enable
Return
Outlet Control Bus
J1 J2 J4 J5J3
Remote EPO Input Outlet Control Bus
Aux 2
Marway Commander UCP 5000 Remote EPO
Using the “Enable” connectors, each PDU receives the On signal at the same time. Using the “Delay” connector to connect to the second PDU, the second PDU will receive
the On signal approximately 2 seconds after the first PDU.
Enable
Disable
Return
Enable
Return
Outlet Control Bus
J1 J2 J4 J5J3
Remote EPO Input Outlet Control Bus
Aux 2
3.3.2.1 Remote Bus Connector Wiring
The 3-pin connectors use two low-voltage signals as follows:
• Shorting the Enable pin to the Return pin with a dry contact will trigger the remote bus Enable signal.
• Shorting the Disable pin to the Return pin with a dry contact will trigger the remote bus Disable signal.
• Note that the Disable signal has priority, so that if both signals are triggered at the same time, the net result will be
Disable.
For additional information about Marway’s Commander UCP remote panel, visit the web site at
http://www.marway.com/commander-epo-panels