
Page | 7
4.0 Location and other important considerations required for Inverell / I7000 installation
- Location
•Evaluate the location of your fireplace, ducting and venting options. It is important to
determine how the fireplace is going to be finished.
•Ensure that there is adequate air supply within the room/area where the fire is installed
in, to ensure proper operation of the fireplace. Install outside air intake kit, if in doubt.
•Ensure that there are no exhaust fans within the vicinity of the fireplace as this can cause the
fireplace to emit fumes back into the room. Also, heat transfer kit with fan should not be
used in any circumstances.
- Built-in cavity
•Consider minimum size and clearances to combustibles given on page XX, for the built-in
cavity required for this wood burner.
•For framing, use dressed framing timber with minimum 90x45 cross section.
•Refer schematic diagrams shown on pages 9 & 10.
•Inside dimensions of the built-in cavity are important. In case, framing timber with larger
dimensions is used, maintain minimum inside dimensions.
•If there is a ceiling in the cavity, cutout with minimum 25mm gap should be made around outer
flue casing to ventilate the cavity. i.e. 300mm dia hole around 250mm outer casing of flue
casing.
•If the cavity opens into the ceiling space, provide adequate rodent proofing at ceiling level.
•Fix cladding only after installing fire, ducting and all the vents in place.
- Elevation of fire
•Decide height of burner install from the ground.
•Considering the modern aesthetic of this model, it is recommended that Inverell / I7000 be
installed at an elevated height.
•floor protector requirement depends upon the elevation of fire above ground
•Support shelf can be maximum up to height of 670mm above the ground
- Floor protector
•For an elevated installation of 350mm and more above the ground, only ash floor protector up
to 300mm distance in the front of the door glass is required.
•Ash floor protector must be constructed of non-combustible material such as fibre cement
board (e.g. Hardies Tile & Slate underlay), steel sheet or equivalent. The minimum width of
floor protector should be 1000mm.
•Larger and thicker floor protector can be constructed for aesthetic purpose.
•For installation below 350mm height, the floor must be non-combustible extending from rear of
the burner to 650mm in the front of door glass.
•Refer schematic diagrams shown on page 16
- Fresh air intake
•Fresh air intake into built-in cavity is a requirement for this installation for proper and efficient
operation of Inverell/ I7000 burner.
•This fresh air needs to enter the built-in cavity at the lower part of the fire.
•It can enter from bottom, sides or rear of the built-in cavity.
•It can enter the built-in cavity through the same room, adjacent room or outside of the house.
•Appropriate configuration should be used to avoid condensation, particularly if the air is
coming from outside.
•The air intake must not draw air from the attic, from the basement or from garage.
•The outside wall termination must be installed where it is not likely to be blocked by snow or
exposed to extreme wind and away from automobile exhaust fumes, gas meter or other vents.
•The fresh air intake openings must be covered with an appropriate mesh or similar to prevent
vermin etc. entering the built-in cavity and meet the local building code requirements.