The light level is adjusted on the centre ring, le and right for minimum and maximum, up and down for fine
adjustment.
a. Ensure power to all luminaires in all groups
b. Point the remote programmer at a convenient fixture
c. Adjust the light to the level required for the target Group
Note: Dimming level can be set using the Sun Icon
Maximum or minimum seng can be achieved by pressing Min / Max
d. Move onto the next change or go straight to Sync / Save * see page 7
The moon sensor is a key part of the automaon process. Different circumstances require sensor range
adjustment. The actual distances will always be approximate. In every installaon there are many variable
environmental factors governing the effecve range.
a. Ensure power to all luminaires in all groups
b. Point the remote programmer at a convenient fixture
(the same fixture if you are following on from other seng changes)
c. Select: Near (~ 1- 3 metre radius)
d. Medium (~3 - 5 metre radius)
e. Far (~ 5 - 8 metre radius)
f. Move onto the next change or go straight to Sync / Save * see page 7
Note: The Moon Sensor can be DISABLED for certain applicaons (Please see page 7)
The ambient light sensor ensures AutoFLEX only operates in the correct light condions for the circumstances.
a. Ensure power to all luminaires in all groups
b. Point the remote programmer at a convenient fixture
(the same fixture if you are following on from other seng changes)
c. Select: Off (lights on regardless of the ambient light level)
Dusk (lights off unless light level drops below ~200lux)
Night (lights off unless light level drops below ~100lux)
d. Move onto the next change or go straight to Sync / Save * see page 7
The Hold me is the me the system remains at the set light level aer acvity in the group area ceases.
At the end of this me the light level drops to 50% for 30s warning prior to entering Standby mode.
a. Ensure power to all luminaires in all groups
b. Point the remote programmer at a convenient fixture
(the same fixture if you are following on from other seng changes)
c. Select: 30 seconds
3 minutes
10 minutes
d. Move onto the next change or go straight to Sync / Save* see page 7
Standby is the AutoFLEX sleep mode. It will stay in this mode unl acvity is again detected. The light level
selected for Standby will depend on factors relevant to the locaon and circumstances.
a. Ensure power to all luminaires in all groups
b. Point the remote programmer at a convenient fixture
(the same fixture if you are following on from other seng changes)
c. Select Off (luminaire will turn off)
10% of full brightness
30% of full brightness
d. Move onto the next change or go straight to Sync and Save* see page 7
This is where selecons are sent to the target groups or fixtures and saved as the operaonal sengs.
They can be saved to all groups, to individual groups, or somemes to an individual fixture only.
(a) To send a command to all Groups:
Press SELECT
Press ALL
Press and Hold SYNC unl the fixtures blink
(b) To send a command to a parcular Group:
Press SELECT
Press target GROUP NUMBER
Press and Hold SYNC unl fixtures blink
Note: To send to more than one Group repeat (b)
(c) To send to individual fixture only
Point the remote programmer at the fixture
Press and Hold SYNC unl fixture blinks
Note: To change sengs on mulple individual fixtures repeat (c)
The normal state is to have the sensor enabled. There may be occasions where the sensor may need
to be disabled during set up or on fixtures near doorways and thoroughfares where passing traffic is
causing unnecessary triggering of the group.
Ensure power to all luminaires in all groups
Point the remote programmer at the targeted fixture
(a) To Sync and Save to all Groups:
Press SELECT
Press ALL
Press ENABLE or DISABLE
(b) To Sync and Save to a parcular Group:
Press SELECT
Press target GROUP NUMBER
Press ENABLE or DISABLE
Note:To send to more than one Group repeat (b)
(c) To Sync and Save to individual fixture only
Point the remote programmer at the fixture
Press ENABLE or DISABLE
Note: To change sengs on mulple individual fixtures repeat (c)
The process to clear a Group seng or to return to factory default sengs on individual fixtures, individual
Groups, or the whole system is similar to Sync and Save.
Ensure power to all luminaires in all groups
Point the remote programmer at a convenient fixture
(a) To Reset all Groups:
Press SELECT
Press ALL
Press and Hold RESET
(b) To Reset a parcular Group:
Press SELECT
Press target GROUP NUMBER
Press and Hold RESET
Note: To Reset more than one Group repeat (b)
(c) To Reset an individual fixture only Point the remote programmer at the fixture
Press RESET
Note: To Reset mulple individual fixtures repeat (c)
1. Operaonal Light Level
2. Acvity Sensing Range
3. Ambient light acvaon
4. Time unl Standby
5. Standby Brightness
Sync/ Save
Enabling and disabling the moon sensor
Factory Reset