
7
PC4020 Design Notes
INSTALLATION AND WIRING
SECTION 2
2.0 Suggested Installation Procedure
The first step in designing a PC4020 installation is developing a System Layout on paper. Doing this
will allow you to work from a plan and help avoid making mistakes and make programming easier.
2.1 Step 1 - System Layout
[1] Layout
Draw a rough sketch of the building(s) in the installation including inside walls if necessary. This will
be the base from which to work. Indicate on the diagram the location of the PC4020 main panel.
[2] Zones and Expansion Modules
Mark all zones that will be required including all doors, PIRs, smoke detectors and glassbreak
detectors etc.
Locate any zone expansion modules (PC4108 and PC4116), if required, close to groups of
zones to provide easier wiring of the devices.
[3] Zone Assignment
Decide on the order to enroll the expansion module(s) so that each zone can be given a zone
number. The first 16 zones on the system are on the main panel. As each expansion module
is enrolled it will be assigned in sequence the next group of available zones. If an 8 zone
expansion module was enrolled first, it would be assigned zones 17-24. If then a 16 zone
expansion module was enrolled it would be assigned zones 25-40.
[4] Partitions
Indicate each partition by boxing the area of the partition on the diagram. This will allow you
to quickly determine which zones will have to be assigned to each partition.
[5] Keypads
Each keypad on the system must be assigned either as a Partition or a Global keypad. A keypad
assigned to a partition will only allow full operation of the partition. A Global keypad will allow full
operation of any partition on the system. Indicate on the diagram the location of all keypads
required. Also indicate if the keypad will be assigned to a partition or if it will be a Global keypad.
[6] Sirens
Siren outputs can be programmed to activate if one or more partitions go into alarm. The main
panel provides one output (the Main Bell Output) for this purpose. Additional siren outputs
can be obtained from PC4204 power supply/relay output module(s). Each PC4204 module
has 4 Form ‘C’ relays, 3 of which can be used as siren outputs.
The PC4204 module can supply up to 1.5 amps of current. If any PC4204 module is being
used to power siren outputs the total current draw when all outputs are active cannot
exceed 1.5 amps. Note: If the hardware revision of the PC4204 circuit board is Rev 08,
additional current (up to 5 Amps total) can be temporarily drawn. This additional current is
supplied by the battery and should not be drawn for an extended period of time.
Indicate on the diagram the location of all sirens and which partition(s) will activate them. If
more than one siren output is required also locate PC4204 module(s) where needed.
[7] COMBUS
The COMBUS is the four conductor cable which can be standard station wire (four 22 AWG
wires colour coded red, black, yellow and green) to which all system modules are connected
in parallel. The modules do not have to be home run to the control panel.
Draw the COMBUS on the diagram. Keep in mind the maximum distance in wire a module
can be from the main control is 1000 feet (305 m).