Maxsys PC4204CX User manual

PC4204CX
Power Supply / Relay Output / Combus Repeater Module
v 3.0 • Installation Instructions
Please refer to the System Installation Manual for information on limitations regarding produ t use
and fun tion and information on the limitations as to liability of the manufa turer.
®
1.0 Introdu tion
The PC4204CX is a Power Supply/Relay utput/ Combus Repeater
Module. The PC4204CX provides a power output for system devices,
4 programmable relay outputs and an output to regenerate the
Combus data signal to allow for longer wire runs.
NOTE: Do not use any power supply other than the PC4204CX to repower
the Combus. If a power supply other than the PC4204CX is used, the
Combus repower function will not operate as intended. See the control
panel Installation Manual for details re ardin this feature.
2.0 Spe ifi ations
• Transformer 16VAC- 40VA to 80VA may be used to power the
PC4204CX
• Backup battery 4Ah to 38Ah (not provided)
• Connects to control panel via 4-wire Combus
• Current draw from Combus: 30mA
• Four programmable relay contacts rated 2A, 30VDC
• Selectable battery charging current (800mA or 1.2A)
• AUX current: 2.2A max., with 800mA battery charge current
and 80VA transformer
• Tamper connection
3.0 Installing the PC4204CX
The PC4204CX should be located inside a compatible cabinet,
mounted in a dry, secure location.
NOTE: The PC4204CX must be installed within a fire enclosure, as
defined in EN60950. The cabinet must comply with the battery
manufacturer’s installation instructions.
NOTE: The cabinet should be mounted in a safe and reliable manner. A
safety factor of 4 or hi her must be provided.
Perform the following steps to mount the unit:
1.1.
1.1.
1. Press the five plastic standoffs through the mounting holes
at the back of the cabinet.
2.2.
2.2.
2. Secure the cabinet to the wall in the desired location. Use
appropriate wall anchors when securing the cabinet to
drywall, plaster, concrete, brick or other surfaces.
3.3.
3.3.
3. Press the circuit board onto the plastic standoffs to secure
the module to the cabinet.
nce the unit is mounted, wiring may be completed.
3.3 Installation and Wiring
NOTE: The PC4204CX is intended to be PERMANENTLY CONNECTED
and should be installed by service personnel only.
Before beginning to wire the unit, ensure that all power (AC
transformer and battery) is disconnected from the control panel.
Perform the following steps to complete wiring:
1.1.
1.1.
1. Connect the four panel-originating Combus wires to the
PC4204CX. Connect the red, black, yellow and green
Combus wires to the RED, BLK, YEL and GRN Combus In
terminals, respectively.
If Relay 1 is being used for Combus power, connect the
Combus wires according to the diagram below. Note that
for this option, jumper Con3 must also be set for “Repower
Relay 1.”

Additional modules repowered by the PC4204CX should
have the black, yellow and green Combus wires connected
to the BLK, YEL and GRN Combus ut terminals
respectively.
2.2.
2.2.
2. Complete all output wiring.
3.3.
3.3.
3. Connect the external tamper switch, if used.
Consult the wiring diagrams for further information.
Current Ratings
In order for the system to operate properly, the power output of the
PC4204CX module cannot be exceeded. The maximum available AUX
supply current is dependent on the size of the transformer used as
well as the selected battery charge current. Use the following chart
to determine the maximum AUX supply current:
Maximum Maximum
Maximum Maximum
Maximum AUX Supply CurrAUX Supply Curr
AUX Supply CurrAUX Supply Curr
AUX Supply Currentent
entent
ent
BB
BB
BAA
AA
ATTERTTER
TTERTTER
TTERYY
YY
Y C C
C C
CHARGEHARGE
HARGEHARGE
HARGE 40V40V
40V40V
40V
AA
AA
A80V80V
80V80V
80V
AA
AA
A
CC
CC
CURRENTURRENT
URRENTURRENT
URRENT TT
TT
TRANSF RMERRANSF RMER
RANSF RMERRANSF RMER
RANSF RMER TT
TT
TRANSF RMERRANSF RMER
RANSF RMERRANSF RMER
RANSF RMER
HI-CHRG (800mA) 700mA 2.2A
OFF
HI-CHRG (1.2A) 300mA 1.8A
ON
NOTE: When usin the PC4204CX to repower additional Combus modules,
current calculations must be made to ensure that the maximum AUX supply
current is not exceeded.
Module Ratings
The current draw of compatible modules is listed below:
DeviceDevice
DeviceDevice
Device Current Draw (mA)Current Draw (mA)
Current Draw (mA)Current Draw (mA)
Current Draw (mA)
Keypad (LCD45XX) .......................................................................... 50
PC4108A Zone Expander ................................................................. 30
PC4116 Zone Expander .................................................................... 30
PC4164 Wireless Receiver .............................................................. 110
PC4701 Fire Module ......................................................................... 35
PC4702BP Dual Bell utput Module ............................................. 75
PC4204CX Relay utput Module ................................................... 30
PC4216 Low Current utput Module ............................................ 15
ESC RT4580 Audio Assistant ....................................................... 150
PC4400 Printer Module .................................................................... 30
PC4820 Access Control Module ...................................................... 35
PC4936 Audio Interface Module ..................................................... 65
PC4401 Serial Interface Module ...................................................... 35
PC4850 Telephone Entry Module ................................................. 135
Calculating Total Current Requirement
nce you have determined which modules will draw power from the
main panel, use the following chart to calculate the Combus current.
Combus Current Calculation Chart
Item Current (mA) x Quantity Total (mA)
Keypad 50 x
PC4108A* 30 x
Current required for connected devices =
PC4116* 30 x
Current required for connected devices =
PC4164 110 x
PC4701 35
PC4702BP 75 x
PC4204CX 30 x
PC4216* 15 x
Current required for connected devices =
Escort4580 150
PC4400/4401 30/35 x
PC4820 35 x
PC4850 135 x
PC4936* 65
Alt. Comm.
TT
TT
Total Combus Currotal Combus Curr
otal Combus Currotal Combus Curr
otal Combus Current =ent =
ent =ent =
ent =
NOTE: * These modules draw current from the Combus to power devices
external to the module. This current must be added to the total Combus
current. See manufacturer’s specifications for the current draw of each
device. Each LED assembly draws up to 20mA of current.
Combus Operation and Wiring
The Combus is used by the control panel and the modules to
communicate with each other. When the PC4204CX is used to repower
and extend the Combus, please refer to the wiring diagram for the
exact wiring procedure.
NOTE: Please follow the dia ram exactly.
Modules can be home-run, connected in a daisy chain or T-tapped
anywhere on the Combus.
The following rules MUST be followed when wiring the Combus:
1.1.
1.1.
1. The Combus must be run in minimum 22-gauge wire.
2.2.
2.2.
2. No module can be more than 1000' (305m) in cable length from
the PC4204CX.
3.3.
3.3.
3. Shielded wire should only be used in areas that present excessive
RF noise or electromagnetic interference. If shielded wire is used,
the maximum distance a module can be located from the
PC4204CX is significantly reduced. Check the capacitance rating
of the wire to calculate the maximum distance (see “Capacitance
Limits”). NOTE: Shielded wire is not recommended.
4.4.
4.4.
4. The total capacitance of the Combus wiring must not exceed 80nF
between the control panel and PC4204CX module or between two
PC4204CX modules (see “Capacitance Limits” below).

Long Distance Combus Extensions
The length of Combus from a PC4204CX Combus Regenerator can
be extended beyond 1000ft (305m), providing the following
conditions are met:
• Combus must be regenerated and repowered at both ends of
the wire run using the PC4204CX.
• No other modules are to be connected along the long distance
wire run.
• A maximum distance of 4000ft (1220m) can be achieved between
two PC4204CX devices. To extend further, additional PC4204CX
devices should be used.
NOTE: The wirin used to connect this equipment must be insulated with
PVC, TFE, PTFE, FEP, neoprene or polymide.
When extending Combus long distances, use the following chart to
determine what gauge of wire is necessary:
Maximum Length AWG
2000ft (600m) 22
3000ft (900m) 21
4000ft (1200m) 20
Line Loss
When current is drawn through a piece of wire, voltage will be lost
due to the wire’s resistance. This voltage loss must be considered
for all installations.
To ensure proper operation, at least 12.5VDC must be applied to all
modules on the system (when AC is applied and the battery is fully
charged). If less than 12.5VDC is applied, system operation will be
adversely affected.
To correct the problem, try any or all of the following:
1. Connect another PC4204CX power supply near the module to
provide power to the Combus.
2. Reduce the length of the Combus run to the module.
3. Increase the gauge of wire.
Capacitance Limits
An increase in capacitance on the Combus will affect data
transmission and will cause the system to slow down. Capacitance
will increase for every foot of wire added to the Combus. The
capacitance rating of the wire used will determine the maximum
length of the Combus, between two PC4204CX Combus Repower/
Regenerator modules.
For example, 22-gauge, non-shielded, 4-conductor wire has a typical
capacitance rating of 20 picofarads per foot (which is 20nF/1000’).
For every 1000' of wire added – regardless of where it is run – the
capacitance of the Combus will increase by 20nF.
The following chart indicates the total Combus wire allowed
depending on the capacitance rating of the wire used:
Wire Capacitance per
1000’( 00m)
TOTAL Combu s Wire
Length
15nF 5300’/1616m
20nF 4000’/1220m
25nF 32 00’/976m
30nF 26 66’/810m
35nF 22 80’/693m
40nF 20 00’/608m
Wires run in parallel also increase Combus capacitance. For example,
when using 20nF wire, the following would be some of the
combinations allowed:
• Four wire runs at 1000'/305m each
• Six wire runs at 666'/203m each
• Eight wire runs at 500'/152m each
• 10 wire runs at 400'/122m each etc…
Contact the wire manufacturer for the capacitance ratings of the
wire being used.
3.4 Regenerating Combus
This module will regenerate the Combus signal as it passes from
one side to the other. The LEDs on the module will illuminate
whenever there is activity on either side of the input or output of
the module.
LED 1 LED 1
LED 1 LED 1
LED 1 illuminates when the module transmits data on ‘Combus In’
LED 2 LED 2
LED 2 LED 2
LED 2 illuminates when the module transmits data on ‘Combus ut’
The PC4204CX module will isolate ‘Combus In’ from any short
circuit problems on ‘Combus ut’. In the event of a problem, the
PC4204CX module will generate a module fault along with the
modules on the disabled Combus. This information can be used
to determine which section of Combus is disabled on the system.
When connecting the PC4204CX to the Combus, care must be taken
to ensure that the ‘Combus In’ terminals are connected to the
wires originating from the control panel (or a module that may be
situated between the PC4204CX and the control panel).
3.5 Applying Power
NOTE: Do not connect power until all wirin is complete.
After all wiring is completed, apply power to the control panel.
Connect the battery leads to the battery, then connect the AC
transformer. Then, connect power to the PC4204CX: first connect
the battery leads, then the AC transformer.
For more information on control panel power specifications, see
the control panel
Installation Manual
.
NOTE: It is the installer’s responsibility to provide adequate protection
for the transformer used in the primary and secondary circuit accordin
to the rated current of the transformer. The transformer used must be Class2,
Fail Safe as defined within EN61558-1 and must meet the applicable
requirements of the EN60950 Standard. A readily accessible disconnect
device must be incorporated into the fixed wirin and must disconnect
both poles simultaneously. The wirin connected to the PC4204CX must
be mechanically protected, routed, supported, clamped or secured in a
manner that prevents excessive strain on wire and terminal connections,
loosenin of terminal connections and conducter insulation dama e.
NOTE: Do not connect fully dischar ed (less than 10V) or dama ed
batteries to the PC4204CX.
4. Enrolling the Module
nce connected, the module must be enrolled on the system. To
enroll the module, perform the following:
1. Enter installer’s programming by pressing [*] [8] [Installer’s Code].
2. Scroll to “Module Hardware” and press the [*] key.
3. Scroll to “Enroll Module” and press the [*] key.
4. Scroll through the different modules until “PC4204” is displayed.
Press the [*] key.
5. The message “Create Tamper on Desired Unit” will be displayed.
To create the required tamper, secure the tamper zone on the
module and then open it. The transition from secure to violated
enrolls the module. After this is done, the keypad will display
the module number and will confirm enrollment (e.g., “PC4204
Mod 01 Enrolled”).
For more information regarding module enrollment, see the control
panel
Installation Manual
.

PC4204CX Outputs Module Number: PC4204CX # Module Number: PC4204CX #
Module Number: PC4204CX # Module Number: PC4204CX #
Module Number: PC4204CX # I
______I
______I (1-16 = XX)
Partition
utput 1 2 3 4 5 6 7 8 Zone Schedule # Pulse Timer
[000702XX01] PC4204CX Relay 1 I
______I
______II
______I
______I
______I
______I
______I
______I
______I
______II
______I
______I
______II
______I
______II
______I
______I
______I
[000702XX02] PC4204CX Relay 2 I
______I
______II
______I
______I
______I
______I
______I
______I
______I
______II
______I
______I
______II
______I
______II
______I
______I
______I
[000702XX03] PC4204CX Relay 3 I
______I
______II
______I
______I
______I
______I
______I
______I
______I
______II
______I
______I
______II
______I
______II
______I
______I
______I
[000702XX04] PC4204CX Relay 4 I
______I
______II
______I
______I
______I
______I
______I
______I
______I
______II
______I
______I
______II
______I
______II
______I
______I
______I
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved by Digital Security Controls Ltd. could void your authority to use this equipment.
This equipment generates and uses radio frequency energy and if not installed and used properly, in strict accordance with the manufacturer s instructions, may cause
interference to radio and television reception. It has been type tested and found to comply with the limits for Class B device in accordance with the specifications in
Subpart “B” of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in any residential installation. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to television or radio reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
•Re-orient the receiving antenna
•Relocate the alarm control with respect to the receiver
•Move the alarm control away from the receiver
•Connect the alarm control into a different outlet so that alarm control and receiver are on different circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional suggestions. The user may find the following
booklet prepared by the FCC helpful: “How to Identify and Resolve Radio/Television Interference Problems”. This booklet is available from the U.S.
Government Printing Office, Washington, D.C. 20402, Stock # 004-000-00345-4.
©2001 Digital Security Controls Ltd.
Toronto, Canada • wwwwww
wwwwww
www.dsc.com.dsc.com
.dsc.com.dsc.com
.dsc.com
Technical Support: 1-800-387-3630
Printed in Canada 29005814 R003
5. Programming the Module
To access PC4010/4020 programming, enter [*][8] followed by the
Installer’s Code. Each relay output must be programmed. Please see
the control panel
Installation Manual
and
Programming Worksheets
for
a detailed list of output options.
NOTE: Relay 1 must not be pro rammed if used for Combus power. Ensure
that jumper CON3 is set to “Repower Relay1.”
Other Maxsys Control Unit manuals
Popular Control Unit manuals by other brands

ACO
ACO PRO I/O installation manual

AlfaRadio
AlfaRadio AlfaSpid Rotator and Controller instruction manual

Argo-Hytos
Argo-Hytos SR1A-A2/L L CE1017 Series INSTRUCTIONS FOR PRODUCT USE

Huawei
Huawei ME909u-521 Hardware guide

DOLD
DOLD SAFEMASTER BG 5925 Series Translation of the original instructions

Move
Move MAMWLE Series manual