maxxess 3 Series User manual

eMAX-MR52
DUAL DOOR CONTROLLER – Series 3
Installation Guide and Specifications
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference
(2) This device must accept any interference received,
including interference that may cause undesired operation.
This device meets CE Specifications, and is RoHS Certified.
This device is UL 294 Recognized. FEBRUARY 2018

February, 2018 eMAX-MR52 Series 3 - Manual Page 2 of 13

February, 2018 eMAX-MR52 Series 3 - Manual Page 3 of 13
TABLE OF CONTENTS
Paragraph Title Page No.
1. General …………………………………………………………………………………………….. 3
2. Supplying Power to the eMAX-MR52 …….……………..…………….………….………...… 4
3. Communication Wiring (SIO Communication Port) ….……………………………………. 4
4. Reader Wiring ……………………………………..…………….……………………………….. 5
5. Alarm Contact Wiring …………………………………………………………………………… 7
6. Inputs for Cabinet Tamper/Power Fault ………………………………………….…………. 7
7. Control Output Wiring ………………..……………………….……………………………….. 8
8. Jumper & Dip Switch Usage …………….……………...…………….………….…………… 8
9. Status LEDs ………………………………………………………………..……………………. 10
10. Specifications …………………………………………………………………...………………. 11
Warranty and Liability ……………………………………………………………………………….. 12
Change History:
Original Original document creation February, 2018

February, 2018 eMAX-MR52 Series 3 - Manual Page 4 of 13
eMAX-MR52 DUAL DOOR CONTROLLER
Series 3
1. General:
The eMAX-MR52 Dual Door Controller (Series 3) provides a solution for interfacing to TTL (D1/D0, Clock/Data),
F/2F, or 2-wire RS-485 Reader-type devices and associated door hardware. It also provides tristate LED control
and buzzer control. The Boards includes six (6) form-C contact relay outputs which may be used for door lock
control or alarm signaling. Eight inputs are provided that may be used for monitoring the door contact, request
to exit devices, and other alarm contacts. Input circuits can be configured as unsupervised or supervised.
Communication to the eMAX-MR52-S3 is via a 2-wire RS-485 circuit. The eMAX-MR52-S3 requires 12 or 24
Vdc for power.
See the following figure for component location (some components shown are not present on the eMAX-MR52-
S3).
INPUTS
IN1 IN2 IN3 IN4
TB1
TB2
TB3
IN5 IN6
TB4
IN7 IN8
TB5
TMP
GND
PFL
GND
TR-
NC
NC
GND
TR+
TB6
RS-485
TB7
VIN
GND
VOUT
A B 1 2 3 4 5 6 7 8 PFL R1 R2TMP
STATUS LEDs
NC NO CNC
RLY 1
CNO
RLY 2
RLY 4 RLY 3
NO CNONCCNC
RLY 6 RLY 5
NO CNONCCNC
TB10
TB11
TB12
READER 2
VOLEDBZRCLKDATGND D1D0
VOLEDBZRCLKGND D1D0
DAT
READER 1
TB8
TB9
12V PT
J1
K1 K2 K3 K4 K5 K6
J4
14 3 2
^
|
ON
14 3 258 7 6
S1S2
MR52+
.25 [6.35]5.50 [139.70]
6.00 [152.40]
2.00 [50.80]
3.00 [76.20]
2.00 [50.80]
8.00 [203.20]
READER
INTERFACE
DIP SWITCHES
OUTPUT
RELAYS
Ø.156 [Ø4.0]
8 PLACES
.50 [12.70]
INPUTS
EARTH
GROUND
DC INPUT
POWER

February, 2018 eMAX-MR52 Series 3 - Manual Page 5 of 13
2. Supplying Power to the eMAX-MR52:
The eMAX-MR52-S3 accepts 12 to 24 Vdc for power on TB7
(VIN and GND). Locate the power source as close to the
eMAX-MR52-S3 as possible. Install the power connection
with minimum of 18 AWG wires.
Ensure that you observe POLARITY on VIN!
The VOUT terminal on TB7 is the same as VIN.
3. Communication Wiring (SIO Communication Port):
The eMAX-MR52-S3 communicates to a Maxxess EP
Series Intelligent Area Controller (EP2500 for example)
via a 2-wire RS-485 interface. The eMAX-MR52-S3
allows for multi-drop communication on a bus of up to
4,000 feet (1,200m). Use twisted pair (minimum 24
AWG) with drain wire and shield for communication. See
specifications section.
Install RS-485 termination jumper, J4, on the interface
boards at each end of the communication line only.
12 TO 24 Vdc
GND
VIN
+
-
TB7
VOUT
TR+
TR-
NC
NC
GND
2-WIRE RS-485
TB6
(ONLY 2-WIRE RS-485 IS SUPPORTED)
TO OTHER DEVICES
ON THE BUSS
TO OTHER DEVICES
ON THE BUSS

February, 2018 eMAX-MR52 Series 3 - Manual Page 6 of 13
4. Reader Wiring:
Each reader port of the eMAX-MR52-S3 supports a reader with TTL (D1/D0, Clock/Data), F/2F, or 2-wire RS-
485 signaling. Source Power to the reader is selectable: 12 Vdc created on the Board (VIN must be greater
than 20 Vdc), or power that is passed-through (PT) from the input voltage of the eMAX-MR52-S3 (TB7-VIN),
300 mA maximum per reader port. Readers that require different voltage or have high current requirements
must be powered separately. Refer to the reader manufacturer specifications for cabling requirements.
J1 –Reader Port Power Select
!! - If the input voltage to the eMAX-MR52-S3 is 12 Vdc, jumper J1 MUST be in the PT position.
In the 2-wire LED mode, the buzzer output is used to drive the second LED. Reader port configuration is set
via the host software.
To fully utilize each reader port:
➢TTL signaling requires a 6-conductor cable (18 AWG)
➢F/2F signaling requires a 4-conductor cable
➢RS-485 signaling requires two 2-conductor cables. Use one cable for power (18 AWG) and one cable
for communication (24 AWG, with drain wire and shield)
Typical D1/D0 or Clock/Data Reader
Typical RS-485 Device
1
VO
LED
BZR
D1/CLK/TR+
D0/DAT/TR-
GND
TB8 or TB9
1
VO
LED
BZR
D1/CLK/TR+
D0/DAT/TR-
GND
TB8 or TB9

February, 2018 eMAX-MR52 Series 3 - Manual Page 7 of 13
* Inputs on supervised F/2F readers may be unsupervised or supervised (supervised
shown).
Typical Unsupervised F/2F Reader
Typical Supervised F/2F Reader
Jumper D1 to LED on supervised
F/2F readers
1
VO
LED
BZR
D1/CLK/TR+
D0/DAT/TR-
GND
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
TB8 or TB9
VO
LED
BZR
D1/CLK/TR+
D0/DAT/TR-
GND
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
NORMALLY CLOSED CONTACT *
DOOR MONITOR SWITCH
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
1K,1%
1K,1%
1K,1%
1K,1%
1
TB8 or TB9

February, 2018 eMAX-MR52 Series 3 - Manual Page 8 of 13
5. Alarm Contact Wiring:
The eMAX-MR52-S3 includes 8 inputs that are typically used to monitor door position, request to exit devices,
or alarm contacts. Input circuits can be configured as:
•Unsupervised alarm (2 states); reporting as open or closed contact.
•Supervised alarm (6 states); reporting as open or closed contact, open circuit, shorted circuit, grounded
circuit *, or foreign voltage*.
A supervised input circuit requires adding two (2) EOL resistors with value of 1k ohm, 1% to the circuit to
facilitate proper monitoring and reporting. The Resistors should be located as close to the sensor as
possible. Custom end of line (EOL) resistances may be configured via the host software.
* Grounded and foreign voltage states are not a requirement of UL 294 and therefore not verified by UL.
The input circuit wiring configurations shown are supported but may not be typical.
6. Inputs for Cabinet Tamper/Power Fault:
Input CT and input BA are used for monitoring cabinet tamper and power failure with normally closed contacts.
These two inputs are for contact closure monitoring only, and do not use EOL resistor(s). If these inputs are
not used, install a short jumper wire across the input to indicate a safe condition.
1K,1%
1K,1%
1K,1%
1K,1%
IN1 IN2 IN3 IN4
Standard Supervised Circuit,
Normally Closed Contact
Standard Supervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Closed Contact
TMP
FLT
GND
CABINET
TAMPER
POWER
FAULT
TB5
GND

February, 2018 eMAX-MR52 Series 3 - Manual Page 9 of 13
7. Control Output Wiring:
The eMAX-MR52-S3 include six (6) Form-C contact relays used for controlling door strikes/locks or other such
devices. Load switching can cause abnormal contact wear and premature contact failure. Switching of
inductive loads (strike) also causes EMI (electromagnetic interference) which may interfere with normal
operation of other equipment. To minimize premature contact failure andto increase systemreliability, a contact
protection circuit must be used. The following circuit is recommended. Locate the protection circuit as close to
the load as possible (within 12 inches [30 cm]), as the effectiveness of the circuit will decrease if it is located
further away.
Use sufficiently large gauge of wires for the load current as to avoid voltage loss.
See documentation included with locking device regarding suppression device requirements.
DIODE SELECTION:
Diode current rating > 1x strike current
Diode break down voltage: 4x strike voltage
For 12 Vdc or 24 Vdc strike, diode 1N4002
(100V /1A) typical
8. Jumper and DIP Switch Usage:
JUMPER
DESCRIPTION
J1
Reader Power Select
12V = 12 Vdc at reader ports. *** See note below ***
PT = VIN “Passed Through" to reader ports
J4
RS-485 Termination, install in first and last units only
All other jumpers are for factory use only
NOTE: The input power (VIN) must be 20 Vdc minimum if the 12 Vdc selection is to be used.

February, 2018 eMAX-MR52 Series 3 - Manual Page 10 of 13
Switches 1 to 5 select the device address. Switch 6 and 7 select the communication baud rate. Switch 8
enables encrypted communication. All other configuration settings are set via host software. Defaults are
address 0 and baud rate 38,000.
S8
S7
S6
S5
S4
S3
S2
S1
SELECTION
OFF
OFF
OFF
OFF
OFF
Address 0
OFF
OFF
OFF
OFF
ON
Address 1
OFF
OFF
OFF
ON
OFF
Address 2
OFF
OFF
OFF
ON
ON
Address 3
OFF
OFF
ON
OFF
OFF
Address 4
OFF
OFF
ON
OFF
ON
Address 5
OFF
OFF
ON
ON
OFF
Address 6
OFF
OFF
ON
ON
ON
Address 7
OFF
ON
OFF
OFF
OFF
Address 8
OFF
ON
OFF
OFF
ON
Address 9
OFF
ON
OFF
ON
OFF
Address 10
OFF
ON
OFF
ON
ON
Address 11
OFF
ON
ON
OFF
OFF
Address 12
OFF
ON
ON
OFF
ON
Address 13
OFF
ON
ON
ON
OFF
Address 14
OFF
ON
ON
ON
ON
Address 15
ON
OFF
OFF
OFF
OFF
Address 16
ON
OFF
OFF
OFF
ON
Address 17
ON
OFF
OFF
ON
OFF
Address 18
ON
OFF
OFF
ON
ON
Address 19
ON
OFF
ON
OFF
OFF
Address 20
ON
OFF
ON
OFF
ON
Address 21
ON
OFF
ON
ON
OFF
Address 22
ON
OFF
ON
ON
ON
Address 23
ON
ON
OFF
OFF
OFF
Address 24
ON
ON
OFF
OFF
ON
Address 25
ON
ON
OFF
ON
OFF
Address 26
ON
ON
OFF
ON
ON
Address 27
ON
ON
ON
OFF
OFF
Address 28
ON
ON
ON
OFF
ON
Address 29
ON
ON
ON
ON
OFF
Address 30
ON
ON
ON
ON
ON
Address 31
OFF
OFF
115,200 BPS, See note 1 below.
OFF
ON
9,600 BPS
ON
OFF
19,200 BPS
ON
ON
38,400 BPS
OFF
Encrypted communication not required
See note 2 below.
ON
Encrypted communication required
See note 2 below.
Note 1: Firmware revisions prior to 1.38.1, this setting is 2,400 BPS
Note 2: Firmware revisions prior to 1.38.1, SW8 is not defined. Set to the OFF position

February, 2018 eMAX-MR52 Series 3 - Manual Page 11 of 13
9. Status LEDs:
Power-up: All LED’s OFF
Initialization: Once power is applied, initialization of the module begins
When initialization is completed, LEDs A through R2 are briefly sequenced ON then OFF
Run time: After the above sequence, the LEDs have the following meanings:
A LED: Heartbeat and On-Line Status:
Off-line: 1 sec rate, 20 % ON
On-line:
Non-encrypted communication: 1 sec rate, 80 % ON
Encrypted communication:
.1 sec ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .3 sec OFF
A LED Error Indication:
Waiting for application firmware to be downloaded: .1 sec ON, .1 sec OFF.
B LED: SIO Communication Port Status:
Indicates communication activity on the SIO communication port
1 LED: Input Status: IN1
2 LED: Input Status: IN2
3 LED: Input Status: IN3
4 LED: Input Status: IN4
5 LED: Input Status: IN5
6 LED: Input Status: IN6
7 LED: Input Status: IN7
8 LED: Input Status: IN8
TMP: Cabinet Tamper
PFL: Power Fault
Input in the inactive state: OFF (briefly flashes ON every 3 seconds)
Input in the active state: ON (briefly flashes OFF every 3 seconds)
Input in a trouble state: Rapid Flash
R1 LED:reader port 1:
Clock/Data Mode: Flashes when data is received, either input
D1/D0 Mode: Flashes when data is received, either input
RS-485 Mode: Flashes when transmitting data
F/2F Mode: Flashes when data/acknowledgment is received
R2 LED:reader port 2:
Clock/Data Mode: Flashes when data is received, either input
D1/D0 Mode: Flashes when data is received, either input
RS-485 Mode: Flashes when transmitting data
F/2F Mode: Flashes when data/acknowledgment is received
K1 through K6 LEDs:Illuminates when output relay RLY 1 (K1) through RLY 6 (K6) is energized.
Every three seconds, LEDs Athrough R2 are pulsed to their opposite state for 0.1 sec.

February, 2018 eMAX-MR52 Series 3 - Manual Page 12 of 13
10.Specifications:
Revision D assembly:
The eMAX-MR52-S3 Interface is for use in low voltage, class 2 circuits only.
The installation of this device must comply with all local fire and electrical codes.
Primary power: 12 to 24 Vdc ± 10 %, 550 mA maximum (reader current not included)
Outputs: Six Form-C relays:
Normally open contact (NO) contact: 5 A @ 30 Vdc resistive
Normally closed contact (NC) contact: 3 A @ 30 Vdc resistive
Inputs: Eight unsupervised/supervised, standard EOL: 1k/1k ohm, 1%, ¼ watt
Two unsupervised, dedicated for cabinet tamper and UPS fault monitoring
Reader Interface:
Power: 12 Vdc ± 10 % regulated, 300 mA maximum each reader
(jumper selectable) (input voltage (VIN) must be greater than 20 Vdc)
or
12 to 24 Vdc ± 10 % (input voltage passed through), 300 mA maximum each
reader
Data Inputs: TTL compatible, F/2F or 2-wire RS-485
LED Output: TTL compatible, high > 3 V, low < 0.5 V, 5 mA source/sink maximum
Buzzer Output: Open collector, 12 Vdc open circuit maximum, 40 mA sink maximum
Communication: 2-wire RS-485: 9600, 19200, 38400 or 115200 bps
Cable requirements:
Power: 1 twisted pair, 18 AWG
RS-485 I/O devices: 1 twisted pair with drain wire and shield, 24 AWG, 120 ohm impedance,
4,000 feet (1,200 meters) maximum
Alarm inputs: One twisted pair per input, 30 ohms maximum
Outputs: As required for the load
Reader data (TTL): 6-conductor, 18 AWG, 500 feet (150 meters) maximum
Reader data (F/2F): 4-conductor, 18 AWG, 500 feet (150 meters) maximum
Reader data (RS-485): 1 twisted pair with drain wire and shield, 24 AWG, 120 ohm impedance,
2,000 feet (610 meters) maximum
Mechanical:
Dimension: 6 in. (15 2mm) W x 8 in. (203 mm) L x 1 in. (25 mm) H
Weight: 11 oz. (312 g) nominal
Environment:
Temperature: -55 to +85 °C, storage
0 to +70 °C, operating
Humidity: 5 to 95 % RHNC
UL294, 6th edition Performance Levels:
Feature
Level
Standby Power
I
Endurance
IV
Line Security
I
Destructive Attack
I

February, 2018 eMAX-MR52 Series 3 - Manual Page 13 of 13
Warranty
Maxxess Systems, Inc. warrants the product is free from defects in material and workmanship under normal
use and service with proper maintenance for one year from the date of factory shipment. Maxxess Systems,
Inc. assumes no responsibility for products damaged by improper handling or installation. This warranty is
limited to the repair or replacement of the defective unit.
There are no expressed warranties other than set forth herein. Maxxess Systems, Inc does not make, nor
intends, nor does it authorize any agent or representative to make any other warranties, or implied warranties,
and expressly excludes and disclaims all implied warranties of merchantability or fitness for aparticular purpose.
Returns must be accompanied by a Return Material Authorization (RMA) number obtained from customer
service, and prepaid postage and insurance.
Liability
The Interface should only be used to control exits from areas where an alternative method for exit is available.
This product is not intended for, nor is rated for operation in life-critical control applications. Maxxess Systems,
Inc. is not liable under any circumstances for loss or damage caused by or partially caused bythe misapplication
or malfunction of the product. Maxxess System, Inc. liability does not extend beyond the purchase price of the
product.
Other manuals for 3 Series
1
This manual suits for next models
1
Table of contents
Other maxxess Controllers manuals