NTU-1700 series Built-in UPS function()
Power ON-OFF remote control by front panel dry contact connector (by RELAY)
Remote controller sold separately, Order No.: IRC1,IRC2,IRC3
Open : Normal work ; Short : Remote off
ACCESSORY
CONNECTOR
MODEL
RATED POWER(Continuous)
OVER RATED POWER(3 Min.)
PEAK POWER(10 Sec.)
WAVEFORM
FRONT PANEL LED
AC REGULATION
SURGE POWER(30 Cycles)
AC VOLTAGE
FREQUENCY
1500W 1700W
NTU-1700-112 NTU-1700-124 NTU-1700-148 NTU-1700-212 NTU-1700-224 NTU-1700-248
1750W 2000W
2250W 2550W
True sine wave (THD<3%)
Please refer to section 3.4 of installation manual
±3.0% at rated input voltage
3000W 3400W
Default setting set at 110VAC Default setting set at 230VAC
Default setting set at 60 0.1Hz±Default setting set at 50Hz 0.1Hz±
100 / 110 / 115 / 120Vac selectable by DIP S.W 200 / 220 / 230 / 240Vac selectable by DIP S.W
50/60Hz selectable by DIP S.W 50/60Hz selectable by DIP S.W
OUTPUT
Note.1
= US, GFCI, UN = EU, CN, AU, UK, UN
INPUT
DC INPUT
BAT. VOLTAGE 12V 24V 48V 12V 24V 48V
Note.1
VOLTAGE RANGE (Typ.) 10 ~ 16.5Vdc 10 ~ 16.5Vdc20 ~ 33Vdc 20 ~ 33Vdc40 ~ 66Vdc 40 ~ 66Vdc
DC CURRENT (Typ.)
POWER SAVING MODE
150A 170A75A 85A37.5A 42.5A
OFF MODE CURRENT DRAW ≦1mA
EFFICIENCY (Typ.) 89% 90% 91% 90% 92% 93%
BATTERY TYPES Lead Acid or li-ion
FUSE (INTERNAL)
LOW
HIGH
BAT. POLARITY
OUTPUT SHORT
OVER TEMPERATURE
OVER LOAD (Typ.)
40A*5 40A*530A*3 30A*330A*2 30A*2
11 0.3Vdc±11 0.3Vdc±22 0.5Vdc±22 0.5Vdc±44 1Vdc±44 1Vdc±
10 0.3Vdc±10 0.3Vdc±20 0.5Vdc±20 0.5Vdc±40 1Vdc±40 1Vdc±
12.5 0.3Vdc±12.5 0.3Vdc±25 0.5Vdc±25 0.5Vdc±50 1Vdc±50 1Vdc±
15.5 0.3Vdc±15.5 0.3Vdc±31 0.5Vdc±31 0.5Vdc±62 1Vdc±62 1Vdc±
16.5 0.3Vdc±16.5 0.3Vdc±33 0.5Vdc±33 0.5Vdc±66 1Vdc±66 1Vdc±
15 0.3Vdc±15 0.3Vdc±30 0.5Vdc±30 0.5Vdc±60 1Vdc±60 1Vdc±
By internal fuse open
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recover
105 ~ 115% load for 180 sec., 115% ~ 150% load for 10 sec.
Protection type : Shut down o/p voltage, re-power on to recover
ALARM
ALARM
SHUTDOWN
SHUTDOWN
RESTART
RESTART
≦≦≧1.2W@standby saving, mode when AC output load 10W, auto wake up when AC output load 15W
PROTECTION
AC OUTPUT
GFCI PROCTECTION None
FUNCTION
UL458 (Only for “GFCI” AC socket)
REMOTE
CONTROL
200/220/230/240Vac 16%, recover 13%±±
AC UPS
MODE
AC INPUT RANGE
100/110/115/120Vac 16%, recover 13%±±
FREQUENCY RANGE 45 ~ 65Hz
TRASFER TIME (Typ.) 10ms inverter AC by pass
ENVIRON-
MENT
OTHER
WORK TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
VIBRATION
MTBF
DIMENSION
PACKING
-20 ~ +70 (Refer to “Derating curve”)℃
20 ~ 90% RH non-condensing
-30 ~ +70 / -22 ~ +158 F, 10 ~ 95% RH non-condensing℃o
10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X, Y, Z axes
TBD
400*184*70mm (L*W*H)
TBD
CIRCUIT BREAKER(GFCI) TBD
14
2
NTU-2200 series Built-in UPS function()
Power ON-OFF remote control by front panel dry contact connector (by RELAY)
Remote controller sold separately, Order No.: IRC1,IRC2,IRC3
Open : Normal work ; Short : Remote off
ACCESSORY
CONNECTOR
MODEL
RATED POWER(Continuous)
OVER RATED POWER(3 Min.)
PEAK POWER(10 Sec.)
WAVEFORM
FRONT PANEL LED
AC REGULATION
SURGE POWER(30 Cycles)
AC VOLTAGE
FREQUENCY
2200W
NTU-2200-112 NTU-2200-124 NTU-2200-148 NTU-2200-212 NTU-2200-224 NTU-2200-248
2530W
2750W
True sine wave (THD<3%)
Please refer to section 3.4 of installation manual
±3.0% at rated input voltage
4400W
Default setting set at 110VAC Default setting set at 230VAC
Default setting set at 60 0.1Hz±Default setting set at 50Hz 0.1Hz±
100 / 110 / 115 / 120Vac selectable by DIP S.W 200 / 220 / 230 / 240Vac selectable by DIP S.W
50/60Hz selectable by DIP S.W 50/60Hz selectable by DIP S.W
OUTPUT
Note.1
= US, GFCI, UN = EU, CN, AU, UK, UN
INPUT
DC INPUT
BAT. VOLTAGE 12V 24V 48V 12V 24V 48V
Note.1
VOLTAGE RANGE (Typ.) 10 ~ 16.5Vdc 10 ~ 16.5Vdc20 ~ 33Vdc 20 ~ 33Vdc40 ~ 66Vdc 40 ~ 66Vdc
DC CURRENT (Typ.)
POWER SAVING MODE
220A 220A110A 110A55A 55A
OFF MODE CURRENT DRAW ≦1mA
EFFICIENCY (Typ.) 89% 91% 92% 90% 92% 93%
BATTERY TYPES Lead Acid or li-ion
FUSE (INTERNAL)
LOW
HIGH
BAT. POLARITY
OUTPUT SHORT
OVER TEMPERATURE
OVER LOAD (Typ.)
40A*5 40A*530A*3 30A*330A*2 30A*2
11 0.3Vdc±11 0.3Vdc±22 0.5Vdc±22 0.5Vdc±44 1Vdc±44 1Vdc±
10 0.3Vdc±10 0.3Vdc±20 0.5Vdc±20 0.5Vdc±40 1Vdc±40 1Vdc±
12.5 0.3Vdc±12.5 0.3Vdc±25 0.5Vdc±25 0.5Vdc±50 1Vdc±50 1Vdc±
15.5 0.3Vdc±15.5 0.3Vdc±31 0.5Vdc±31 0.5Vdc±62 1Vdc±62 1Vdc±
16.5 0.3Vdc±16.5 0.3Vdc±33 0.5Vdc±33 0.5Vdc±66 1Vdc±66 1Vdc±
15 0.3Vdc±15 0.3Vdc±30 0.5Vdc±30 0.5Vdc±60 1Vdc±60 1Vdc±
By internal fuse open
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recover
105 ~ 115% load for 180 sec., 115% ~ 150% load for 10 sec.
Protection type : Shut down o/p voltage, re-power on to recover
ALARM
ALARM
SHUTDOWN
SHUTDOWN
RESTART
RESTART
≦≦≧1.2W@standby saving, mode when AC output load 10W, auto wake up when AC output load 15W
PROTECTION
AC OUTPUT
GFCI PROCTECTION None
FUNCTION
UL458 (Only for “GFCI” AC socket)
200/220/230/240Vac 25%, recover 12.5%±±
AC UPS
MODE
AC INPUT RANGE
100/110/115/120Vac 25%, recover 12.5%±±
FREQUENCY RANGE 45 ~ 65Hz
TRASFER TIME (Typ.) 10ms inverter AC by pass
ENVIRON-
MENT
OTHER
WORK TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
VIBRATION
MTBF
DIMENSION
PACKING
-20 ~ +70 (Refer to “Derating curve”)℃
20 ~ 90% RH non-condensing
-30 ~ +70 / -22 ~ +158 F, 10 ~ 95% RH non-condensing℃o
10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X, Y, Z axes
TBD
400*270*98mm (L*W*H)
TBD
REMOTE
CONTROL
CIRCUIT BREAKER(GFCI) TBD