Mect TP1070 Series User manual

ME7032_09
06/22
USER’S MANUAL for
TP1070 series
HMI - Operator panel

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
INDEX
1. Introduction.............................................................................................................. 1
1.1. Staff skill............................................................................................................ 1
1.2. Simbols............................................................................................................... 1
1.3. Terms ................................................................................................................. 1
1.4. Security .............................................................................................................. 2
1.5. REFERENCE MANUAL.................................................................................. 2
2. System description................................................................................................... 3
2.1. Specification....................................................................................................... 4
3. Hardware Installation............................................................................................... 5
3.1. Mechanical dimensions...................................................................................... 5
3.2. Panel mount........................................................................................................ 7
3.2.1. Distance........................................................................................................ 7
4. TP1070 wiring......................................................................................................... 8
4.1. Connections........................................................................................................ 8
4.2. Power supply...................................................................................................... 9
4.2.1. System power supply ................................................................................... 9
4.2.2. Fuse .............................................................................................................. 9
4.3. ModBus wiring (on all models)....................................................................... 10
4.4. CanOpen (TP10070_01_B model) .................................................................. 11
4.5. ModBus wiring (TP1070_01_C model)..........................................................12
5. Peripherals .............................................................................................................12
5.1. USB.................................................................................................................. 12
5.2. Ethernet............................................................................................................ 13
6. HMI........................................................................................................................ 13
6.1. System variables .............................................................................................. 13
7. How to order.......................................................................................................... 13

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
1
1. Introduction
To grant a fast setup of the device please follow carefully the information in this
manual.
1.1. Staff skill
Products described in this manual are devoted to PLC programmers or automation
experts only. MECT S.r.l. declines any responsibility about malfunctioning or
damage caused by incorrect use of MECT devices, due to noncompliance to this
manual information. MECT S.r.l has an help desk.
1.2. Simbols
Danger
Follow this advice to avoid people injury.
Warning
Follow this advice to protect the device.
Caution
Follow this advice to have a more effective performance.
ESD ( Electrostatic discharge)
Danger: possibly damage due to Electrostatic discharge.
Note
Step to follow for a correct installation.
Additional information
1.3. Terms
PLC: TP1070
Terminals: MPNC006; MPNC020; MPNC030; MPNC035
System: PLC (TP1070) with terminals

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
2
1.4. Security Attention
Switch off devices before connecting them.
ESD (Electrostatic discharge)
Modules have electronic components that can be damaged by.
electrostatic discharge. Be sure to be connected to ground when
handle the devices.
The instrument has no power switch and no internal fuse, but it powers on
immediately after connecting a correct power supply input (check the power supply
value on the instrument label). Keep the power supply line as short as possible and
keep it separate from other power lines.
For security reasons it is necessary to have a 2 section power switch with a fuse near
the instrument and easily replaceable.
Avoid the presence of other power actuators in the same control panel, high humidity,
excessive heat and corrosive gas.
Instruments must have a power supply from security transformers or SELV
transformers.
1.5. REFERENCE MANUAL
The Quick Start (downloadable from the web
site) and MectSuite Tutorial are the reference
manuals for MectSuite to develop HMI and PLC
applications.

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
3
2. System description
TP1070 is a device composed by a PLC and a HMI with touch-screen monitor 7”
width and 800 x 480 pixel resolution with 262.000 colors.
The TP1070 operator panel allows supervision of devices connected to the Modbus
TCP and Modbus RTU network. The networks are managed at the same time by the
TP1070, and data from one network can be sent to another, thus creating a bridge
between the two networks.
On the TP1070 operator panel there is also a USB host port. The USB allows the use
of a key for software update and data historicization.
On the TP1070 there are up to 1 kByte of retentive variables stored on flash memory.
The device can be applied in horizontal or in vertical design with the option "V" (see
following pictures).
Figure 1: Front view TP1070 (horizontal version)
Figure 2: Front view TP1070 (vertical version)

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
4
2.1. Specification
The TP1070 operator panel is based on a multiprocessor system. PLC and HMI are
based on a 454MHz ARM9.
Table 1
Hardware characteristics
Processor
ARM926JE 454MHz
RAM
128MB
FLASH
128MB
Non volatile variables
On FLASH memory
Real Time Clock
Yes with rechargeable battery
Screen 7”
TFT 800 x 480 pixel 262k colors
Touch screen
Resistive 4 wires
Ethernet
10Mbit/s - 100Mbit/s self recognition
USB
Host 2.0
CANOpen
1 channel
Max Bit rate: 1Mbit/sec
Cycle time: 10msec
Serial output
RS485 full duplex (hardware configuration)
Software characteristics
OS
LINUX 2.35
PLC
IEC61131-3
Graphics
Based onQT library
CAN Bus
CanOpen 2.0
ModBus
Modbus RTU master
Storage memory massa
Possibility of history storage
Field bus main features
RTU Modbus
Master 2 or 4 wies
TCP Modbus
Server
Electromagnetic compatibility
The electromagnetic compatibility tests have been carried out at accredited
laboratories, according to EN 61326-1, EN 61131-2 and EN 61000-6-2standards.

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
5
3. Hardware Installation
In the following figures see the TP1070 operator panel dimensions.
3.1. Mechanical dimensions
Side view
Figure 3
Rear view
Figure 4
Side view
Figure 5

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
6
Technical specification
Table 2
Mechanical
Material
Polycarbonate, Polyamide 6.6
Dimensions W x L x H
195 mm x 145 mm x 60.5 mm
Mounting plate
138mm x 188mm
Installation
Panel installation
Environmental conditions
Operative temperature
0 °C ... 55 °C
Storage Temperature
-20 °C ... +85 °C
Relative Humidity
5 % a 95 % no condensation
Electric isolation
Air clearance
According to IEC 60664-1
Pollution
According to IEC 61131-2
2
Protection
Rear protection
IP 20
Front protection
IP65
Attention
Install the device in a panel with no more than 55 °C.

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
7
3.2. Panel mount
3.2.1. Distance
System must be installed with a space for heat dissipation and cabling. Avoid
cabling superimposing to avoid EMC problems.
Figure 6A: Horizontal mounting
Figure 6B: Vertical mounting

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
8
4. TP1070 wiring
4.1. Connections
In the following figure see the wiring diagram with the available I/O.
Figure 7
Table 3
TP1070
Power Supply
12÷36Vdc Vdc 400mA
USB A
2.0
Ethernet
Bit rate: 100Mbit/sec
Serial ouputs
RS485 full duplex (hardware configuration)

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
9
4.2. Power supply
4.2.1. System power supply
TPAC1070 operator panel has a 12÷36Vdc according to the scheme in the figure.
System is protected against reverse power supply.
4.2.2. Fuse
System has no internal fuse , so is suggested the use of an external 1A fuse for the
panel power supply.
Figure 8
Attention
A wrong value for the power supply can cause a damage to the
device

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
10
4.3. ModBus wiring (on all models)
ModBus on TP1070 operator panel is a 4 wire RS485 serial line, on the M2 terminal
(RTU3) board on pins:
Table 4
Pin
Segnale
Description
11
GND
12
TX +
Line + Tx
13
TX -
Line - Tx
14
RX +
Line + Rx
15
RX -
Line - Rx
Example of a wiring of a system composed by:
MPNC006
MPNC020
MPNC030
TP1070
Figure 9

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
11
4.4. CanOpen (TP10070_01_B model)
Can interface on TP1070_01_B operator panel is on M3 terminal board on pins.
Table 1
Pin
Signal
1
CAN H
2
CAN L
3
GNDiso
Example of a wiring of a system composed by:
MPNC010
MPNC020
MPNC030
TP1070
Figure 15
Cable type
Cable between TP1070_01_B and CANopen slave must be a shielded twisted pair,
and to avoid external disturbances the shield must be connected to both 0V of the
communicating systems. The cable length is a function of the baud rate as follows.

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
12
Table 2
Baud rate
Bus lenght
1
Mbit/s
10
m
800 kbit/s
50
m
500 kbit/s
100
m
250 kbit/s
250
m
125 kbit/s
500
m
50 kbit/s
1000 m
Terminal resistence
Inside the TP1070_01_B operator panel there is a resistance of 120to terminate
properly the bus on the master side.
To configure the CAN communication see the CAN Builder tutorial.
4.5. ModBus wiring (TP1070_01_C model)
ModBus on TP1070_01_C operator panel is a 4 wire RS485 serial line, on the M3
terminal (RTU0) board on pins.
Table 6
Pin
Signal
1
D+
2
D-
3
GNDiso
5. Peripherals
5.1. USB
TPAC1070 has an USB 2.0 host for:
software update.
data storage: datalogger.
Connect USB peripherals as printers, mouse, etc.
Specific connection of external peripherals are implemented on request.

HMI - Operator panel: TP1070 Mect srl
ME7032_09 06/22
13
5.2. Ethernet
TP1070 operator panel has a 10/100Mbit/s ethernet port with autoconfiguration, with
direct or inverse connection cable.
TP1070 operator panel, by ethernet, can be controlled by a personal computer, it is
possible to control the I/O of TP1070 by means of a program on a PC.
6. HMI
To set the TP1070 operator panel is necessary to develop a software in QT Creator
based on QT libraries, custom-tailored on MECT operator panel.
A specific tutorial is furnished with the device.
The QT Creator suite software is available in Windows environment.
6.1. System variables
The system can use 5472 interchange variables between HMI and automation (at
maximum) which include:
internal variables, interchange variables on Modbus network, retentive variables.
The variables are defined by a tool furnished from Mect.
7. How to order
Table of contents