ES-405-9800 Manual Rev A Page 13
3 SITE SELECTION and REMOTE POWER OPTIONS
Use the following criteria when deciding on a sampling location for the ES-405. Always consider
the safety and security of the unit, as well as the suitability of the sampling environment.
3.1 Site Selection Requirements
Selection of a proper site for the ES-405 is critical for accurate measurements.
The following is a summary of general ambient particulate monitoring site requirements that will be
appropriate for use with the ES-405 in many cases. Some of these criteria may not be appropriate
in some applications, due to the versatile nature of the ES-405:
Inlet Height:
•The inlet should be located in the “breathing zone”, between 2 and 15 meters above ground
level. When installed on the standard tripod, the ES-405 inlet is positioned two meters
above the ground or other mounting surface.
•If the ES-405 is to be collocated with other particulate instruments, such as FRM filter-type
samplers or BAM units, then the air inlet must be the same height as the inlet of the other
samplers, within one meter vertically. Within one foot is preferred.
•If the ES-405 inlet is the highest point on a building, then lightning rods must be installed to
prevent destruction of the unit during electrical storms.
Inlet Radius Clearance:
•The ES-405 inlet should have a one meter radius free of any objects that may influence
airflow characteristics, including the inlet of another instrument.
•If an ES-405 is to be collocated at a station along with BAM or FRM samplers, the inlets of
each sampler must be no less than one meter apart from each other, and no more than
four meters apart. Two meter inlet spacing is recommended where possible.
•If installed near a PM10 Hi-Volume sampler, then the distance between the inlet of the ES-
405 and the Hi-Vol must be no less than two meters.
•The ES-405 inlet should be located away from obstructions such as short walls, fences,
and penthouses, so that the inlet is unobstructed for two meters in all directions whenever
possible. In some ES-405 applications, this may not be entirely possible.
•If located beside a major obstruction (such as a building) then the distance between the
ES-405 and the building should be equal to twice the height of the building.
•The inlet should be at least 20 meters from the drip line of any overhanging trees.
•There should be at least a 270 degree arc of unrestricted airflow around the inlet. The
predominant direction of concentration movement should be included in the arc.
Artificial Particulate Sources:
To avoid possible errors in the concentration measurements, the inlet must be located as far as
possible from any artificial sources of particulate, such as blowers, vents, or air conditioners on a
rooftop. Especially if any of these types of devices blow air across the inlet of the ES-405. Even
sources of filtered air must not blow across the inlet.