-6-
PART VI: SEQUENCE OF OPERATION
A. Introduction: The explanation of the sequence of operation will start with the assumption that the controller
has been properly installed, all external connections have been made and the isolation switch and circuit
breaker are closed. In other words, the controller is operational. The Power On pilot light should be on. All
wiring on the primary side of the Transformer 1CPT will be referred to as the primary circuit. All wiring on
the secondary side of the Transformer 1CPT will be referred to as the secondary circuit.
B. Manual Operation:
1. M100, M200 and M220 Manual Controllers: For manual operation there is a start button switch on
the controller and terminals for an optional remote start switch located elsewhere. These switches
have normally open contacts which close to energize 1CR. 1CR locks in on its own N.O. contact
and stays energized until the stop button is depressed. The N.O. contact of 1CR in the primary
circuit closes the circuit to the motor contactor to start the motor. On Models M200 and M220 a
time delay relay (2TR) is wired in parallel with 1CR. After a preset time delay N.O. contacts of 2TR
close to energize relay 3CR. A N.O. contact of 3CR then energizes the second or run contactor.
To stop the controller manually the stop pushbutton switch is depressed. This breaks the circuit to
the coil of 1CR and it is de-energized. At the same time the N.O. contacts of 1CR and 3CR in the
primary circuit open and de-energize the motor contactor(s) and stops the motor.
2. M300, M400 and M420 Combined Manual-Automatic Controllers: Manual operation of the
combined manual-automatic controllers is the same as for the manual controllers. The electrical
sequence is different in that the N.O. contact of 1CR does not energize the coil directly but
energizes the coil of 2CR, and a N.O. contact of 2CR in the primary circuit energizes the motor
contactor. On Models M400 and M420, 1CR also energizes a time delay relay 2TR. After a preset
time delay N.O. contacts of 2TR close to energize relay 3CR. A N.O. contact of 3CR then energizes
the second or run contactor.
C. Automatic Operation / (Pressure Switch): On drop of water pressure the N.O. contact in the pressure
switch closes energizing the coil of 2CR. 2CR locks in on its N.O. contact in the secondary circuit. At the
same time the N.O. contact in the primary circuit energizes the motor contactor to start the motor. In
controllers with sequential starting, 3TR is energized by the pressure switch starting its timing cycle and at
the end of the timer period a N.O. contact of 3TR closes energizing 2CR. A N.O. contact of 2CR in the
primary circuit closes and energizes the motor contactor as above. On Models M400 and M420 a time delay
relay 2TR is wired in parallel with 2CR. After a preset time delay N.O. contacts of 2TR close to energize
relay 3CR. A N.O. contact of 3CR then energizes the second or run contactor.
On controllers set for automatic stop, a running period timer is used to keep the motor running for a preset
time period regardless of whether the contact of the pressure switch has opened. This is accomplished by
keeping 2CR (or 3TR) locked in through the N.C. contacts of the timer (1TR) until the timer times out and
these contacts open.
On controllers set for manual stop only, a jumper is installed in parallel with the N.C. contact of 1TR, thus
2CR (or 3TR) is held in the energized state. The controller must be stopped with the manual stop
pushbutton switch which breaks the circuit to 2CR (or 3TR). The N.O. 2CR contact in the primary circuit
opens and stops the motor.
D. Automatic Operation / (Deluge Valve-Option D): The deluge valve switch is a N.C. switch. When it
opens 7CR is de-energized. The N.C. contacts of 7CR in the automatic circuit close and energize 2CR (or
3TR). The remaining sequence to start and stop the motor is the same as automatic operation with the
pressure switch closing.
E. Remote / Pump Running Signal: One (1) N.O. and one (1) N.C. contact is available for remote indication
that the pump is running.
F. Remote / Loss of Power, Loss of Phase, Low Voltage: One (1) SPDT contact is available for remote
indication of loss of line power, loss of phase, or low voltage.
G. Remote / Phase Reversal: One (1) SPDT contact is available for remote indication of phase reversal of the
incoming power to the controller.