INSTALLATION
The 8340 can be mounted indoors or outdoors. Find a location near a 120V wiring source
(230/240V for international models). Install the 8340. near eye level if possible.
CONNECTING THE TRANSFORMER
120 VAC in United States, Canada and Mexico; 230 VAC in Europe, and 240 VAC in UK,
Middle East, Australia and South Africa.
NOTE: Refer to and follow local codes if different from these instructions.
CAUTION: Disconnect 120V (230/240V) power source before wiring the transformer. Complete
all wiring and installation before connecting the transformer to power source. This will avoid
accidental shorting which could damage the controller.
Power supply cables and cords used for connections are to be of ordinary duty or greater. Low
voltage output cables should be enclosed in conduit affixed to the controller with a suitable
adapter. Remove the transformer cover by loosening the two screws. Attach AC wires to
transformer wires using wire nuts. Also, ensure earth ground wire is attached to green with
yellow stripe ground wire. Please check local codes for the grounding requirements in your area.
Bundle wire with cable tie loop and tighten cable tie to prevent loose wiring from touching
secondary circuits. The transformer is now wired. Replace the transformer cover and the two
screws.
DO NOT turn on power yet.
NOTE: Failure to ground unit properly may cause severe damage to the controller and/or
personal property and will void warranty
LOW VOLTAGE WIRING
Low voltage output cables should be enclosed in conduit affixed near the controller. (For field
connection, AC wires must have an insulation rated at 75° C minimum). Conduit should be
secured near the case (follow local codes). Field wiring is best accomplished with the AC
disconnected from the unit.
TERMINAL STRIP
All zone, pump and sensor wire connections made inside the 8340 utilize screw type connectors
that require a small screwdriver. The terminal strips in the controller accept 12 AWG (2.1mm)
wire or smaller.
(See Figure 1 on page 4)
CONNECTING MASTER VALVE OR PUMP-START RELAY
The 8340 is equipped with a shared circuit to operate either a pump-start relay or a master
valve. Connect one wire from the pump-start relay to COM (common) on the terminal strip, the
other to PMP/MV (pump/master valve) on the terminal strip. Refer to the pump-start relay
manufacturer’s instructions for specific installation details. (See Figure 1 on page 4)