Hanbay MC A 8.09 Series User manual

Page 1 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
MCx-B-xxxAx-8.09
(12-24 VDC; Battery Backup; 4-20 mA Control)
USER MANUAL
Contents
INSTALLATION 2
Mounting 2
Wiring 2
Power Supply and Current Draw 3
Control Signal and Feedback 4
OPERATION 5
DIP switches 5
Controlling the Actuator 5
Changing the number of turns 6
Torque Settings 7
Speed and Torque Details 7
Signal Loss and Calibration 9
Troubleshooting 10
Battery Fail Safe Function 10
Testing Battery Functionality 10
ACTUATOR DIMENSIONS 11
PART NUMBER BREAKDOWN 12
LABEL BREAKDOWN 13

User Manual MCx-B-xxxAx-8.09
Page 2 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
INSTALLATION
Mounting
In most cases, the actuator must be mounted
and supported as shown in the image to the
right. The mounting bracket is not supplied by
Hanbay.
Exceptionally, the actuator may be suspended
on the tubing itself but ONLY if the application is
vibration free and the tubing is minimum ¼” dia.
stainless.
Wiring
The actuator comes standard with a Turck 5 position connector and a 20’ cable with plug. Cut the cable to
the length required and then connect according to the following wire color schematic:
Wire color schematic for “Turck 5” cable:
Pin
Colour
Function
6
White
+24 VDC
5
Black
Power Gnd.
4
Grey
Output Signal (4-20 mA)*
3
Not connected
2
Brown
Isolated** Input Signal Gnd.
1
Blue
Isolated** Input + Signal (4-20 mA)
* “feedback” available in MCx-Lx-xxxAFversion of actuator only.
** “isolated” available in MCx-Lx-xxxAIand xxxAFversions of actuator only.
Mounting
Bracket
Cable Entry

User Manual MCx-B-xxxAx-8.09
Page 3 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
If the Turck cable is not included in your actuator, connect the wires to the corresponding pins on the
terminal block as indicated in the table and schematic below:
Power Supply and Current Draw
The MCx-B-xxxAx can ONLY be connected to 24 VDC +/-10%.
The power consumption will range from minimum 100 mA to maximum 3 A while the actuator is active. When
not moving, the actuator draws approx. 50 mA.
Pin
Function
6
Already Connected to battery board
Connect +24 VDC wire to loose red cable with
crimp connector
5
Already Connected to battery board
Connect power ground wire to loose black cable
with crimp connector
4
Feedback signal (4-20 mA)*
3
Not connected
2
Isolated** input signal gnd.
1
Isolated** input signal (4-20 mA)
* “feedback” available in MCx-B-xxxAFversion only.
** “isolated” available in MCx-B-xxxAIand xxxAFversions only.
Terminal
1 2 3 4 5 6
Remove sensing resistor R66 to convert
from 4-20 mA to 1-5 V control signal
Note: if R66 is removed, we recommend
placing a 10K resistor between signal and
signal GND or simply using shielded cable
(for noise reduction).

User Manual MCx-B-xxxAx-8.09
Page 4 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
Control Signal and Feedback
Locate the correct connection terminals/wires as shown on the previous page, then connect your input signal
on positions 1 and 2 (blue and brown wires) as shown below. Feedback, if applicable is connected to
position 4 (grey wire).
1 2 3 4 5 6
P1
4-20 mA Signal source, user
powered
-
+
Actuator
MCx-B-xxxAx
Internal
RES
R66
NOTE 1: Usually, the actuators are
shipped for 4-20 mA signal input.
For 1-5 V signal input, remove 250 ohm
resistor R66.
The actuator 4-20 mA output is internally supplying the signal current and can drive sufficient voltage for any
sensing resistor of up to 250 ohms.
The potential of the external GND after the sensing resistor may not be more than +6 VDC / -2 VDC away from
the power GND of the actuator.
This feedback signal output is only available in MCx-B-xxxAF model actuators.
External
4-20 mA
Sensing
resistor
NC
NOTE 3: DO NOT CONNECT pin 4
directly or through a multimeter only to
ground.
A sensing resistor of 50 ohms or more
needs to be present.
Not observing this warning will damage
the equipment.
NOTE 2: Signal Gnd. is NOT
ISOLATED from Power Gnd. in all
MCx-B-xxxAB basic models.
If your signal Gnd. is different from
Power Gnd. use HANBAY
MCx-B-xxxAI or MCx-B-xxxAF model
actuators.
B B B B
4 3 2 1

User Manual MCx-B-xxxAx-8.09
Page 5 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
OPERATION
DIP switches
The DIP switches allow you to change the
settings on your actuator. To flip a switch,
gently use a small flat-head screwdriver.
See chart on next page for DIP switch functionality.
DIP
Function
1
2
Speed: Choose how quickly the actuator will turn the drive wheel. See p.7.
3
For external gear stage (MCH) –not an option for battery fail-safe model
4
5
6
7
8
Turns: The actuator usually ships from the factory with the recommended number of turns for the
valve. However, this number can be changed. Turning on a switch will add a specific number of
turns to the actuator’s movement.
See p.6 for relation between positions of the DIP switches and number of turns.
Example: Turning on DIP 6 adds four turns, turning on DIP 8 adds one turn. If both DIP 6 and 8 are
on, then the total turns of the actuator would be five.
9
Signal loss: See p.8.
10
11
Seating Torque: Set how much torque the actuator exerts on the valve lever during the calibration
(finding valve seat) procedure. See p.7.
12
Direction/Calibration: Toggle switch on and off while powered to re-calibrate actuator. Also sets
direction in which the actuator will open and close. See p.8.
Example: The MCM model actuator turns clockwise when the signal is decreased with DIP 12 in the
OFF position. Putting DIP 12 in the ON position will cause counterclockwise turning for a decrease
in signal. For changes in DIP 12 position to take effect, the power to the actuator must be cycled.
When cycling the power, the power must be off for at least 2 minutes to ensure the battery has
switched off.
Controlling the Actuator
The 4-20 mA (or 1-5 V / 1-10 V) input signal represents a total span of a number of turns.
I.e.: If you set the number of turns to 2, then a signal of 12 mA will set the actuator to exactly 1 turn from the
fully closed position. 15 mA will give: (15-4)/16=0.6875 ⇒68.75% of 2 turns ⇒1.375 turns from closed.
In this example DIPs 1, 2, 5 and 12 are on.

User Manual MCx-B-xxxAx-8.09
Page 6 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
Changing the number of turns
With the DIP switch settings, you can adjust anything between 1 and 31 turns to represent the full signal
range of 4-20 mA. Check in the table below. (1 = “On”, 0 = “Off”)
Total Turns
Dip4=0
DIP 5
DIP 6
DIP 7
DIP 8
reserved
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
5
0
1
0
1
6
0
1
1
0
7
0
1
1
1
8
1
0
0
0
9
1
0
0
1
10
1
0
1
0
11
1
0
1
1
12
1
1
0
0
13
1
1
0
1
14
1
1
1
0
15
1
1
1
1
WARNING: Be sure that the number of turns the actuator is set for is LESS than the number of
turns for the valve. The actuator should not stop itself on a fully opened valve. It can damage the
valve, and the actuator will lose its position.
For more turns, set DIP 4 to the ON position.
This will add 16 turns to the number set by DIPs 5
through 8, as shown in the table.
DIP 4=0
+0 turns
DIP 4=1
+16 turns

User Manual MCx-B-xxxAx-8.09
Page 7 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
Torque Settings
To accommodate different valves and other applications
with different torque requirements, the actuator can be set
to apply different torque on the valve stem when in the
seating mode.
During normal operation, the actuator will try to reach the
speed set by DIP 1 and DIP 2. It will use 100% torque to try
and reach the selected speed, regardless of the positions of
DIP 10 and DIP 11. Current draw is limited to 3 A
regardless of settings.
Please see the box to the right and the tables below to select the power setting that is right for your
application.
To deal with sticking valves, at the beginning of the first reversing movement after the seating (“zeroing”) of
the valve, the actuator will apply double the power set by DIP 10 and DIP 11 (up to 100% power.)
This “pull out” function is always enabled.
Speed and Torque Details
The maximum speed of the actuator can be set by using the first two positions of the DIP switch selector.
As a result of this setting, the actuator will limit the maximum speed. The tables below show the time required
to complete one turn.
The seating torque depends on the voltage provided in the power connection and on the
seating power settings on DIP 10, 11 as shown below.
MCL-B-xxxAx Actuators
Speed:
Torque:
DIP 1
DIP 2
Time for
1 turn (sec)
DIP 10
DIP 11
Seating Torque
(in-lbs)
Operating
torque is
100%
OFF
OFF
7
OFF
OFF
12
OFF
ON
3
OFF
ON
20
ON
OFF
2
ON
OFF
38
ON
ON
1
ON
ON
48
NOTE: If actuator is MCJ-B-xxxAx, divide torque values by 3.
To convert in-lbs to Nm, divide by 9.
WARNING: High power settings can supply enough torque to damage your valve.
Please be cautious, especially when using the 100% power setting.
Seating power settings:
DIP 10
DIP 11
Power
OFF
OFF
16%
OFF
ON
33%
ON
OFF
66%
ON
ON
100%
Note: 66% setting and 100% setting require voltage supply minimum values as follows:
-Supply voltage needs to be min 14 VDC for 66% setting
-Supply voltage needs to be 16 VDC for 100% setting
-When operating above 20VDC and 66% power, Duty cycle is reduced to 50% - 25%
maximum. At these levels, the electronics produce more heat which must be dissipated
(depending on environmental temperature)

User Manual MCx-B-xxxAx-8.09
Page 8 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
MCM-B-xxxAx Actuators
Speed:
Torque:
DIP 1
DIP 2
Time for
1 turn (sec)
DIP 10
DIP 11
Seating Torque
(in-lbs)
Operating
torque is
100%
OFF
OFF
23
OFF
OFF
35
OFF
ON
11
OFF
ON
60
ON
OFF
7
ON
OFF
115
ON
ON
4
ON
ON
145
NOTE: If actuator is MCK-B-xxxAx, divide torque values by 3.
To convert in-lbs to Nm, divide by 9.
MCF-B-xxxAx Actuators
Speed:
Torque:
DIP 1
DIP 2
Time for
1 turn (sec)
DIP 10
DIP 11
Seating Torque
(in-lbs)
Operating
torque is
100%
OFF
OFF
161
OFF
OFF
230
OFF
ON
77
OFF
ON
380
ON
OFF
49
ON
OFF
720
ON
ON
28
ON
ON
915
To convert in-lbs to Nm, divide by 9.
The MCH model is not available with battery backup, please use the RDH model instead. Please see user
manual RDx-B-xxxDT for more details.
If the M-Series housing with MDH torque range (120-497 in-lbs) is essential, contact us about MDF-L.
For reference, the torque and speed values for the RDH are given below:
RCH-B-xxxAx Actuators
Speed:
Torque:
DIP 1
DIP 2
Time for
1 turn (sec)
DIP 10
DIP 11
Seating Torque
(in-lbs)
Operating
torque is
100%
OFF
OFF
90
OFF
OFF
120
OFF
ON
45
OFF
ON
205
ON
OFF
30
ON
OFF
400
ON
ON
18
ON
ON
497
To convert in-lbs to Nm, divide by 9.

User Manual MCx-B-xxxAx-8.09
Page 9 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
Signal Loss and Calibration
1. In the event of a power loss, the battery fail-safe model will move to its designated fail-position. This
position is programmed at the factory (based on user request) and cannot be changed in the field.
IF YOU HAVE TO turn the actuator manually when its power is turned off, it will lose its
position, and it will need to be re-zeroed (as described in sub-section 3).
2. The behavior on signal loss can be set as follows:
Normal position of DIP 9: OFF
With DIP 9 in the off position, the actuator will ignore the signal if it is lost (i.e.: if the signal falls below
0.700 V or 2.80 mA) and simply remain in its current position.
Predetermined signal loss position DIP 9: ON
With DIP 9 in the on position, the actuator will move to a predetermined position when the signal is
lost (i.e.: if the signal falls below 2.80 mA or 0.700 V).
Setting of the predetermined signal loss position:
a.- turn DIP 9 to the “off” position
b.- re-zero the actuator by sending and holding an input signal between
2.80 and 4.16 mA (0.700 and 1.04 V) wait until the device is re-zeroed, (i.e.: valve is closed)
c.- by varying the input signal, move the actuator to the position that is going to be the
predetermined signal loss position.
d.- switch DIP 9 to the “on” position. The current actuator position will be saved as the default
signal loss position. (The default signal position is an absolute actuator position. i.e.: not a
signal value.)
3. Re-zeroing the actuator and initiating calibration routine:
The actuator will re-zero when the input signal is between 2.80 and 4.16 mA (0.700 and 1.04 V). It
will turn clockwise until the actuator has reached the fully closed position of the valve.
If the valve is removed for any reason, the calibration routine must be initiated on the
actuator manually. This is done by toggling DIP 12 (switch position, then back to the original
position) while the actuator is powered. This will prevent damage to the valve.
If you need to re-zero in the opposite direction (i.e.: for pressure regulators, which typically go to
the “top” fully open position at 4 mA) change the setting of DIP 12 and cycle power.
Remember to wait 2 minutes before restoring the power, to allow the battery board to shut down
after moving to the fail-safe position.
4. Feedback calibration: [RCx-B-xxxAF model actuators only]
The current feedback will be calibrated from the factory.
To re-calibrate the feedback:
a.- Turn off the actuator and wait 2 minutes to allow the battery board to shut down after
moving to the fail-safe position. Then disconnect the feedback and input signals. If possible,
remove the actuator from the valve.
b.- Connect the feedback signal to the signal input. Also connect the power and signal grounds.
c.- Power up the actuator with this “signal loop-back” setup.
d.- Short SP1. It will automatically run a special routine to calibrate the feedback signal to the
signal input. The whole process takes about 1.5 seconds.
e.- turn off the power and reconnect the actuator as normal.

User Manual MCx-B-xxxAx-8.09
Page 10 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
Troubleshooting
Upon noticing a problem, your first step should almost always be to recalibrate the actuator by toggling DIP
12 while the actuator is powered. This alone can solve basic problems. See sub-section 3 above for more
details.
If the actuator does not move, try following these steps:
1) Re-calibrate the actuator. This will move the actuator regardless of what signal it is receiving.
2) A sticking valve may be the problem. Remove the valve from the actuator, and re-test the actuator.
3) Remove power. Re-check the wiring and the power/signal apparatus. Power actuator and re-calibrate.
If the problem persists, please call Hanbay for technical support.
Battery Fail Safe Function
1. In the event of a loss of power or signal, the battery will maintain power to the P1 processor and
trigger the actuator to move the valve to its designated fail-safe position, using power from the
battery. The digital potentiometer will monitor the position of the valve during this fail-safe operation.
2. Once the valve has reached its fail-safe position, and after about one minute, the P1 processor will
go into sleep mode to preserve the battery life.
3. The actuator will not respond to commands until the power supply is restored.
Note: The battery will maintain a charge for up to 2 months without power being applied.
The fail-safe actuation can be performed for 30 cycles on the charge available in the battery.
During normal operation, from totally discharged, the batteries will take 2 hours to re-charge.
If in a critical fail-safe application, the battery function should be tested monthly.
Testing Battery Functionality
- The batteries will be continuously on charge when power is available to the actuator.
- Regardless of application, the fail-safe function should be tested monthly by signaling the unit to the
position opposite the fail position, removing the power to the actuator and observing whether the
actuator reaches the desired fail position.
- The battery voltage can be measured with a multimeter set for DC volt measurement.
Measure battery
voltage between the
connector terminals.
Value should be:
7.9 ± 0.4 VDC

User Manual MCx-B-xxxAx-8.09
Page 13 of 13 www.hanbayinc.com | 1 800 315 4461
Rev.2021.7 hanbaysales@hanbayinc.com
LABEL BREAKDOWN
Actuator Series
M-Series or R-Series
Actuator Supply Voltage
12-24 VDC @ 3.0 A or
110-240 VAC @ 1.5 A
Circuit Board Version
Ax-8.09
Dx-10.31
Dx-4.10 (Obsolete since 2019)
Px-10.3
Actuator Part Number
Refer to part number breakdown
for available options.
QR Code
Scan this QR code for a
direct link to the user
manual for your unit!
Actuator Serial Number
This serial number is unique for
each individual unit and is directly
tied to your order/invoice number.
Firmware Version
AF-1.05 MM = Multiturn
AB-1.05 MML = Multiturn Low Torque
AS-1.05 MMUL = Multiturn Extra Low Torque
QM = Quarter turn
QM97 = Quarter turn 97°
DT-2.01
DC-2.01
DT-4.06 (Obsolete since 2019)
M-Dx V2.31
Table of contents
Other Hanbay Controllers manuals

Hanbay
Hanbay RD-AC Series User manual

Hanbay
Hanbay MD DT-10.31 Series User manual

Hanbay
Hanbay M Series User manual

Hanbay
Hanbay MC-B-A-8.09 Series User manual

Hanbay
Hanbay MC DC-2.00 Series User manual

Hanbay
Hanbay RD-DT-10.31 Series User manual

Hanbay
Hanbay RC Series User manual

Hanbay
Hanbay RC AS-1.05 Series User manual

Hanbay
Hanbay MC-AS-1.05 Series User manual
Popular Controllers manuals by other brands

Linear Technology
Linear Technology DC1936A Demo Manual

Grundfos
Grundfos Conex DIA-G Installation and operating instructions

Monoprice
Monoprice Speaker Volume Control with Infrared... user manual

Sentinel
Sentinel EVC-2 instruction manual

VelLight
VelLight LEDC09 user manual

AirCom
AirCom R110 operating manual