MG TR-EVO User manual

TR-EVO
220-240Vac
INSTRUCTIONS FOR USE
MG
MGINDUSTRY srl Via Casa Celeste 14 36014 Santorso (VI) Italy E-mail m @m online.it
Draft 2 13/02/2020
EN

General Index
Editor's notes..............................................................................................................................II
Introduction.................................................................................................................................1
Warnings.....................................................................................................................................1
Technical characteristics.............................................................................................................2
Description of parts.....................................................................................................................2
Control unit........................................................................................................................2
Po er unit..........................................................................................................................2
Transformer.......................................................................................................................3
DIN bar adapter.................................................................................................................3
Operation.....................................................................................................................................3
Principles...........................................................................................................................3
Operating modes................................................................................................................3
Installation...................................................................................................................................4
Assembly...........................................................................................................................4
Description of the connections on the po er unit.............................................................5
Signalling on po er module..............................................................................................8
Configuration of the s itches for selection of the current ranges.....................................8
Connections on the display unit.........................................................................................9
Selection of heating element..............................................................................................9
Alloys.......................................................................................................................9
Transformer dimensioning.................................................................................................9
"Hard are" configuration......................................................................................10
Start-up......................................................................................................................................11
Operating modes..............................................................................................................12
System and alarm monitoring..........................................................................................13
Errors table and possible solutions..................................................................................13
Configuration............................................................................................................................15
With serial bus connection...............................................................................................15
With numerical display....................................................................................................15
Basic parameters....................................................................................................15
Extended parameters..............................................................................................16
Maintenance..............................................................................................................................18
Warranty....................................................................................................................................19
Appendix...................................................................................................................................20
System dimensioning.......................................................................................................20
Editor's notes
This manual contains confidential information. All rights reserved.
The manufacturer reserves the right to make changes or improvements ithout prior arning to this documentation and
the devices they describe.
Utmost care as taken in the collection and verification of the documentation contained in this manual; ho ever, the
manufacturer cannot be held in any ay liable for its use. The same applies for each person or company involved in
the creation and production of this manual. Unless other ise specified, every reference to the company, names, data
and addresses used in the examples is purely casual and for the purpose of illustrating product use.
It is strictly forbidden to reproduce any part of this manual, in any format, ithout the manufacturer's explicit, ritten
permission.
Draft 1 10/18/2017
Draft 2 13/02/2020 Various corrections and improvements. Adapted to firm are 1.2
II

Introduction
The TR-EVO temperature controller is a valid tool to adjust temperature in heating elements,
ithout using external sensors.
By taking advantage of the voltage-current characteristic, the TR-EVO manages to maintain the
temperature set even in conditions of high heath loss, thereby obtaining considerable benefits
compared to traditional methods used.
To reach the temperature set in the least time possible (100 ÷ 350 ms) and keep it constant means
obtaining an increase in operating speed, but also an extended operating life of the heating part,
and enables less aiting times due to thermal inertia or dispersions of the various metal parts
supporting the heating element.
The TR-EVO as designed to be controlled or control, from the simplest electro-mechanical
packaging machines to the most complex packaging lines ith PLC or PC.
All the operating parameters can be entered using the display or the integrated serial port RS485.
Extremely easy to use, highly functional and compact, this system is the strength of heat sealing
processes, including ith hot air, temperature control, hot cutting, etc...
arnings
ATTENTION: for correct use of your temperature controller, it is essential to
comply with the instructions in this manual. You are advised to read each part of it
carefully before start up, to prevent possible damage due to improper actions.
Avoid installing the equipment in the immediate vicinity of high power units, relays,
motors, etc.
The equipment is NOT equipped with an ON/OFF switch, therefore it switches on as
soon as it is connected to the power supply.
The power supply should have adequate protection against any short circuits or
anomalies on the equipment.
Install connections using cable types with adequate sections for the voltage and
current limits specified in the manual.
Check the system has a good ground connection.
Do not use the equipment in environments with a dangerous atmosphere
(inflammable or explosive).
TR EVO operation implies use of specifics alloys for the heating elements. Use of
different alloys can cause the TR EVO to malfunction with possible temperature
instability and/or dangerous overheating.
1

Technical characteristics
Device supply: 230 Vac (+15% / -15%) 4W max. used by controller. 115Vac option available
Po er supply: 230Vac ith maximum distorsion of 10%. 115Vac option available
Mains frequency: 47 Hz to 65 Hz hit automatic adaption to the mains frequency in this range
Peak output po er: 3600 VA. Continuous output po er 1200 VA. 1800VA ith 115V supply
Load values: MAX 80Vac 100A. MIN 8Vac 12A
Device safety increased by the use of 2 breakers in series to po er the load.
Command inputs: 24Vac/30Vdc +20 -60% opto-isolated.
Signaling output: max 30Vdc 50mA opto-isolated, free of voltage, NPN or PNP configurable.
Alarm output: max 30V 0,5A free voltage contact.
Temperature adjustment range: 30 to 500 degree ith lockable limits.
Unit operational temperature: 0 to 50 degree
Adjustments and configuration through integrated keypad and numeric display, or through serial
bus EIA/TIA485, or through external voltage/potentiometer.
Description of parts
Control unit
Technical data:
-Dimensions mm. 96x48x118
-Weight gr. 200
-Fitted assembly on panel.
-Vertical or horizontal insertion.
-Self-extinguishing PVC material UL94 V-O
-Protection level IP42
-Numerical digits LED display.
-Po ered by po er unit.
-Maximun sensing voltage 80Vac.
-Maximum sensing current 100A.
Power unit
Technical data:
-Dimensions mm. 106x90x69
- eight gr. 500
-Assembly on bar DIN EN 50022- 50035
-Self-extinguishing PVC material UL94 V-O
-Protection level IP20
-Peak output po er 3600VA for t < 1sec.
-Maximum continuos po er 1200 for t > 1 min.
2

Transformer
Technical data:
-Single-phase, pulse transformer ith dual safety insulation according to
standards ISO/EN 61558
-Variable dimensions from mm. 122x95x108
-Variable eight starting from 4.3Kg
DIN bar adapter
Technical data:
-Standard reference DIN EN5002250035
-Front dimensions 112x55mm.
-Total depth ith mounted device 155mm.
-Metal an PVC made.
Operation
Principles
The temperature controller adjusts the temperature of a heating element ithout using probes, but
by basing itself on the variation characteristics of the resistance, on temperature variation, hich
is characteristic of each heating element. Measuring the voltage and current sent to the heating
element enables calculation of its resistance and by comparing it ith that of the cold detected
element during the "tuning" phase, the temperature can be found on measurement. Based on these
calculations, the po er necessary to bring or maintain the temperature set is calculated and a solid
state s itch is activated to provide the necessary po er to the heating element. Thanks to the high
speed ith hich this measurement is taken (50 times per seconds) very fast adjustment ith
good temperature stability of the heating element is possible. Heating times of 150ms. are normal
for this equipment and no particular measures are required to reach them. At the same time, the
temperature can be kept constant also in very lo po er request conditions, allo ing heating to
be kept continuously on.
Operating modes
The temperature controller can ork autonomously using the integrated display and keypad, or
can be connected to a PLC control device or PC using an EIA/TIA485 interface, or can be
adjusted by external analogue voltage or by a panel potentiometer.
3

Installation
Assembly
Assembly and installation must only be carried out by qualified staff
Before you begin: -Ensure correct power supply voltage.
-Check an efficient ground system is present
Cable passage hole for heating element current detection.
Po er unit
Reserve in the electrical cabinet 110mm on a DIN rail EN
50022- 50035 and insert the unit in it.
Display unit
Cut out the panel based on the measurements given, insert
the module and tighten from behind using the scre
fastening clips supplied.
An adapter for DIN rail installation EN 50022-50035 can be
supplied on request, in this case reserve 60mm next to the
po er unit.
Po er transformer
Positioning of the transformer is constraint-free, but you are
advised to assess it based on the cable length. It is good practice
to optimise the length of the cable, especially the part connected
to the secondary.
If possible, avoid dividing the cable into sections using terminals.
The dimensions of the transformer are variable and depend on the
application. See chapter for calculation.
4
8.8.8
8.8
TD
TO
TR
≡
TR-EVO
48 mm
96 mm
45 mm
92 mm
DRILLING
92 X 45
1 2 3 4 5 6
15 14 13 12 11 10 9 8 7
106 mm
90 mm

DIN rail adapter
Reserve, next to the po er unit, 60mm on a DIN rail
EN50022- 50035
Connect the supplied cables to the display unit.
Insert the display unit into the slot and secure it ith the
standard panel mounting clips provided.
The cables are used for connection to the po er unit and
the RS485 communication module of the PLC.
Wire the system using the adequate iring diagrams for your configuration. For example, a
minimal diagram is provided belo .
Always check connections are correctly tightened. The current on the circuit is very high and
poor connections can cause problems.
Warning: remember that during heating, for example of a bar, elongation and shortening caused
by heating and cooling of the heating element must not affect the quality of the contacts.
Description of the connections on the power unit
Terminal 1
Connection for device grounding.
Terminal 2
Mains phase input for heating element command, protected by an external fuse.
Neutral mains is at terminal 5 shared ith device supply neutral.
Voltage must be bet een 220 and 240 Vac (+15% / -15%) ith maximum distortion of 10% and
frequency from 47 Hz to 65 Hz
On connection bet een the po er supply line and the equipment, cables ith a 2.5mm2 section
must be used.
5
1 2 3 4 5 6
15 14 13 12 11 10 9 8 7
8.8.8
8.8
TD
TO
TR
≡
TR-EVO
/
/
/
~
~
START
ALARM

A 16A fuse ith semi-rapid response should be used as the protective component.
Terminals 3, 4
Output to pulse transformer primary.
The transformer should be dimensioned starting ith the size of the element
to control, i.e. the type of alloy, idth, thickness and length. (see specific
section).
Unless legislative indications state other ise, cables ith a 2.5mm2 section
must be used on connection to the primary.
On the connection bet een the transformer secondary and the heating
element, the cross-section should be chosen according to the currents and
connection lengths involved, a cable ith section bet een 4mm2 and 8mm2 is
recommended.
Terminals 5,
Device po er supply input.
Here, connect the po er supply of the device
bet een 220 and 240 Vac (+15% / -15%). This
line is protected inside the device ith a 100mA
fuse.
Connect mains neutral to terminal 5 shared ith
the neutral of po er output.
Connect mains phase to terminal 6 to supply
device. This connection allo s to signal on the
display the possible intervention of the
protection circuit.
The mechanical dimensions and the type of filter
to install are based on the plate data of the pulse
transformer. Contact our technical office for the
relevant dimensioning.
Terminals 7, 8
"ALARM" output
Free contact to signal any faults: this contact is closed in the event of monitored malfunctions, for
example, breakage of the heating element, short circuit, etc. Apply a maximum voltage in
alternating current of 100V/0,5A and continuous current 24V/0,5A.
6
LINE 230V
6 5 4 3 2 1
LINE
FILTER
POWER
LOAD
F
6
N
PE
POWER
SUPPLY
FUSE
4 3
V2
SEC
V1
PRIM

Terminals 9, 10
"IN WORK" output
Opto-isolated output of sealing circuit signaling: this optical coupler is
closed during the sealing cycle, and return open at the end of the cycle; see
the "operating modes" section for further operating details.
It can be externally configured NPN or PNP, ith a maximum current
hich must not exceed 50mA at 24 Volts continuously.
Pay attention on connection to polarity: terminal 9 has the positive
(collector) and terminal 10 has the negative (emitter).
Terminals 11, 12, 13
Heating and/or pre-heating start inputs
Wire to these inputs the signals for sealing cycle control: these
signals must have a voltage bet een 12 Vac and 24Vac or from
12Vdc to 30Vdc by applying the positive to terminal 11 and 13
and the negative to terminal 12.
In the presence of the START signal( terminal 11), the heating
element reaches the orking temperature.
In the presence of the pre-heating signal( terminal 13), the
temperature is adjusted to pre-heating level.
Further details are found in the "operating modes" section.
Terminals 14, 15
Heating element voltage measurement input.
Use is preferred of the flexible, t isted cable ( ith strand conductors) ith a 2x0.5 mm² section
ith at least 15 t ists per meter.
If there are multiple heating elements connected in series or parallel, the voltage is taken from
the ends of the heating elements based on the diagram outlined above.
7
10 9
-
NPN
+
10 9
-
PNP
+
12 1311
+
-
10-30Vdc
12-24Vac
1 5
1 4
1 5
1 4
1 4
1 5

Caution: To obtain correct measurements, this cable must be connected to the ends of the heating
element, connecting at other points introduces measurement errors and reduces the efficiency of
temperature control.
Current measurement input
To sense the heating element current, TR-EVO has a dedicated
passage here to pass one of the connecting cables bet een
transformer and heating element. Normally the cable only makes one
passage through the hole. In particular cases and depending on the
characteristics of the heating element and/or the transformer, the
number of passages to be made could be more than one. See in the
figure on the side of this paragraph ho to make t o passages. Do
reference to the section "Transformer sizing" for more information.
User interface connector
The po er unit should be connected to the display/user
interface unit using the cable supplied. 1-3-5 meters
cable lengths are available as option and must be
specified hen ordering.
Under the semi-transparent cover are available
s itches for the selection of the ork current and t o
signalling LEDs are visible.
Signalling on power module
Green LED L1: Po er supply signal. It stays on as long as the po er supply is on.
Yellow LED L2: Po er signal. It s itches on hen the temperature controller commands the
pulse transformer.
Configuration of the switches for selection of the current ranges
Both open, 12-25A range
DIP 1 closed , DIP 2open, 25-50A range
Both closed, (ON) 50-100A range
8
CONNECTION

Connections on the display unit
CONNECTOR FOR REMOTE CONTROL
PIN DESCRIPTION
1 NU
2 Potentiometer + output
3 Control voltage input (0-10V) or potentiometer
4 Control voltage 0V reference or potentiometer
5 NU
6 Serial data terminal A EIA/TIA-485 D0-
7 Serial interface 0V reference
8 Serial data terminal B EiA/TIA-485 D1+
The "po er unit" connector is reserved for the connection cable ith the relevant unit.
Selection of heating element
Alloys
The heating element alloys currently supported by the temperature controller are:
Type Name
0 Nickrome40®
1 Alloy20®
2 Steel AISI316
3 MS500 (it is not an alloy, but is used to adapt the air heater to the temperature
controller)
Nickrome40 and Alloy20 are registered trademarks of the relevant manufacturer.
Transformer dimensioning
Considering the voltage of the primary should be the same as the po er supply voltage of the
temperature controller and then 230Vac or 115Vac, another t o parameters must be defined:
voltage to the secondary and transformer po er. To calculate these parameters, start ith the
quantity of energy necessary for the operation, ho ever for simplicity purposes it is considered
that to heat a bar to approx. 200°C in approx. 200mS a specific po er of 30W per cm2 is needed
on the outer surface of the heating element.
9
45 mm
92 mm
CONNESSIONE A
UNITA’ DI POTENZA
CONNETTORE
CONTROLLO
REMOTO

The formula:
r
=
Cs
×
Lu
×
La
Sp
×
2
enables calculation of the maximum po er Pr required by the heating element, here:
Cs = surface load in Watts per cm2. This value determines the speed the bar heats and assumes,
as seen above, a reference value of 30. Naturally, this value can be changed if higher speed
is required, or less po er supply is available, or po er that exceeds the maximum that can
be supplied by the controller.
Lu = heating element length in centimeters.
La = heating element idth in centimeters.
Sp = heating element thickness in centimeters.
And its resistance R in ohm is:
ℜ=
Rs
×
Lu
/
100
here:
Rs = Specific resistance of the band in ohm/meter
These values are used to calculate the secondary voltage Vs of the transformer in volts according
to the formula:
Vs
=
r
×ℜ
The po er of the transformer Pt must be calculated in Watts using the formula:
t =r×1,1
here 1.1 is a constant to compensate transformer losses.
In addition, e can calculate the peak current I in Amperes requested by the load hich is orth:
I=r
Vs
"Hardware" configuration
Based on the current calculated, the s itches must be configured on the temperature controller
and in particular: if the current is over 50A both s itches should be closed, if the current is
bet een 25 and 50A s itch 1 should be closed, if the current is bet een 11 and 25A the s itches
should be left open.
For more detailed information, please compile and send the questionnaire in the
appendix. We will reply with a personalised application note for your application.
10

Start-up
On first start up, the equipment will probably give an error signal.
This signal is normal and depends on the fact the parameters of the
heating element have not been registered yet. For the temperature
controller to acquire these parameters, the Tuning procedure must
be activated which should always be executed after replacing the
heating element.
The tuning procedure enables the temperature controller to acquire the cold resistance value of
the heating element and starts ith the specific sequence indicated in the programming chapter or
from remote via interface 485. At the end of the procedure, the temperature controller ill start
orking properly again or blocks, displaying an error that indicates the reason the procedure did
not conclude properly.
Always execute the tuning procedure with the heating element at
room temperature.
On s itch on, the temperature controller prepares for operation by synchronising ith the mains
frequency and displaying it on the numerical display, (F 50 for 50Hz) .
Once synchronised, the temperature controller goes to "standby" mode and displays
the temperature read on the heating element. To read the temperature, the po er
output is briefly activated at a fixed rate, allo ing the device to continuously control
the load status and promptly signal any anomalies. If the device detects anomalies in
its operation, it blocks and signals the type of anomaly on the display and activates a
signal output.
In standby mode, the equipment does not adjust the temperature and displays the
temperature read on the heating element. Heating starts if the pre-heating and/or
START input are activated. These commands can also be serially activated, ho ever
the response time is not guaranteed therefore you are not advised to use them in
situations here the response time is important.
The operating status of the temperature controller is indicated on the leds on the left of the second
ro of the display. The first led on top indicates heating has started by applying voltage to the
START input, ho ever the temperature has not yet reached the value set or start of heating cicle
delay timer(td) is still active. When the temperature reaches the orking value, the central led
s itches on as long as the START input is active or until the pulse timer(to) expires. Lastly, the
bottom led s itches on hen heating has concluded, ho ever the heating element has not yet
cooled do n or cooling timer has not yet expired.
The orking temperature can be set using external voltage controlled by a
potentiometer or an analogue output, using the serial interface, or directly from the
keypad on the display. To set the orking temperature, press the
≡
key to display
the temperature, indicated by the abbreviation ht on the lo er display, and press the
and keys to edit the value.
11
030
173
173
ht

Pressing the
≡
key again cfg is displayed on greater display line and 00 on lo er display and
access the equipment configuration is enabled (for information on the configuration, refer to the
relevant chapter).
Press the
≡
key again to display the temperature read on the heating element again.
For test purposes, you can press the key to force activation of the heating cycle.
Operating modes
The temperature controller can be configured ith various operating modes.
In brief, the available modes are:
interactive:
by doing so, the pre-heating input allo s you to activate
temperature control at the pre-heating temperature (2) and the
start input allo s you to activate the temperature control at the
heating temperature (4). The start input has priority over the
pre-heating input.
On reaching the orking temperature (3), the active cycle
output activates.
On deactivating the heating input temperature goes lo and
active cycle output deactivates.
Always on:
in this mode, temperature control is al ays on and
continuously adjusts the pre-heating temperature. Activating
the start input, the adjusted temperature changes to the heating
temperature.
On deactivating the heating input temperature goes lo and
active cycle output deactivates.
12
PREHEATH
START
CICLE
temperature
1
24
5
time
1
3
temperature
1
24
5
time
1
3
START
temperature
time
2
3
4
5
CICLE

Timed:
in this mode, hen the pre-heating input is on, it activates
temperature adjustment to the pre-heating temperature. Start
input activates the timed heating cycle hich is composed of 2
phases. The first phase (indicated ith the TD led on the display)
delays heating starting for the time set on the relevant timer. The
second phase (indicated ith the TO led on the display) adjusts
the heating temperature for the time set on the relevant timer. At
the end of the cycle, the equipment aits for start input disabling
to re-start a ne cycle. The cycle can be stopped at any time by
disabling the START signal.
Pulse:
in this mode, the start input is used to start the timed cycle
hich ill only end on conclusion of the 3 phases composing it
The phases are: (4) delay, adjustment activates at the pre-
heating temperature, ho ever heating is delayed for the time set
on the relevant timer. This time is used hen it is not possible to
have the START signal activated at the right moment. (5)
Heating, the temperature is brought to the ork value for the
time selected on the relevant timer. (6) Cooling, the heating
element is no longer po ered and hen the temperature is
belo the value set on the relevant parameter or on expiry of
the relevant timer, the cycle concludes by disabling the cycle
output.
System and alarm monitoring
When on, the temperature controller continuously controls operations are proceeding correctly
and if errors are found that prevent proper operation, blocks and signals the cause of the error.
Signalling is implemented via contact of a relay that signals the tool condition to the operating
machine, using an error number displayed on the numerical display, and transmitted instead of the
temperature on the serial interface.
Errors table and possible solutions
Error code Description
1 Load po er supply frequency outside limits;
this error highlights the protective fuse has blo n or the po er supply
frequency is outside the values permitted. Restore the fuse or check the
po er supply line.
13
CICLE
time
START
1
24
6
time
4
5
3
temperature
time
START
time
CICLE
temperature
3
1
24
6
4
5

2 Rapid temperature change
This error occurs in the tuning procedure and highlights the operation
started ith the heating element hot. Wait for it to cool and repeat the
operation.
3 Insufficient voltage reading;
this error occurs in the tuning procedure and highlights an error in
transformer connection or in its dimensioning. During the first tuning
operation after installation, it may also indicate improper connections.
4 Insufficient current reading;
this error highlights breakage of a heating element hen using elements in
parallel, if it occurs during the tuning procedure it highlights a
dimensioning error of the pulse transformer or in jumper configuration on
the temperature controller. During the first tuning operation after
installation, it may also indicate improper connections.
5 Too high voltage reading;
this error highlights voltage is too high in the equipment feedback and
requires a tuning procedure. During the tuning procedure, an error
highlights in the transformer connection. During the first tuning operation
after installation, it may also indicate improper connections.
6 Too high current reading;
this error highlights the short circuit of one of the heating elements hen
using elements in series, if it occurs during the tuning procedure it
highlights a dimensioning error of the pulse transformer or in jumper
configuration on the temperature controller. During the first tuning
operation after installation, it may also indicate improper connections.
7 Voltage not reaching the heating element
Possible causes:
- Po er adjustment element (TRIAC) faulty.
- Connections bet een the temperature controller and the heating element
interrupted.
- pulse transformer faulty.
8 Current not passing through the heating element
Possible causes:
- heating element damaged.
- loose heating element fastening.
9 Voltage reaching the heating element not read.
Possible causes:
- the feedback cable to the temperature controller is interrupted.
- loose connections on the temperature controller terminals.
- distortion on the po er supply line too high.
14

10 Short circuit:
- on the secondary circuit of the pulse transformer.
- on the heating element.
- on the t isted cable.
11 Heating activated in error;
this error indicates a likely fault in the po er adjustment element. It can
activate in the event of high inductive pulses on the po er supply.
14 Memory not valid on the temperature controller;
load a basic configuration on the temperature controller and proceed ith a
ne configuration.
15 Memory not valid on the temperature controller;
repair the temperature controller.
16 Internal fault;
repair the temperature controller.
Configuration
Configuration of the parameters can be executed via:
•Remote mode RS485: the configurations can be executed through commands sent via
interface EIA/TIA485.
•Internal mode via the numerical display: the configurations are executed directly using the
associated keys.
ith serial bus connection
In this mode, configuration is executed using the commands sent via the EIA/TIA485 interface by
a PLC or PC remote device. The communication protocol manual is separate and available on
request.
ith numerical display
Once the equipment starts, it orks in operating mode displaying the temperature read on the
heating element.
Press the
≡
key t ice to display CFG. The lo er display sho s 00. Press the
key on the keypad to display the first basic parameter or
≡
again if you ant to
return to the temperature display.
Basic parameters
The value is displayed that is currently set of the pre-heating temperature on the top
display and PH on the bottom display. If you do not ant to edit the value, press the
≡
key to go to the next parameter or press the and keys to edit the value
bet een the minimum of 50° and the maximum hich is set in configuration 13. The
key activates the value or saves it in the temperature controller memory.
15
cfg
0 0
050
p h

On releasing the key, a ne value is displayed hich, if timed operation was
enabled, indicates the delay timer setting bet een the start of the cycle and the
actual start of the heating phase and is indicated on the lo er display ith td. If you
do not ant to edit the value, press the
≡
key to go to the next parameter, other ise
the and keys edit the value and the
key saves the timer in the temperature controller
memory.
Identical configuration procedures are used for the subsequent TO and TR parameters that
respectively set the time in hich the heating element stays at the heating temperature selected
and the time to allo cooling of the heating element before indicating the operating cycle has
concluded.
The next configuration sets the temperature differential compared to the heating
temperature hich defines hen the heating element can be considered arrived to the
orking temperature and is indicated on the bottom display ith dr. If you do not
ant to edit the value, press the
≡
key to go to the next parameter, other ise the
and keys edit the value and the
key saves the timer in the temperature controller memory.
The top display sho s tun and the bottom display sho s 10 to indicate the
procedure for parameter acquisition of the heating element. The
≡
key is used to
return to temperature display. To start the procedure, press and keep pressed the
key until the counter on the second line reaches zero.
Warning: The counter may continue to restart even if you press and hold the button signalling
that the conditions are not right to start the procedure. Probably the heating element is not yet at
room temperature, temperature required for success of the "tuning" phase, or the device is active
in heating mode. Release the button, disable heating, and ait a fe minutes before trying again.
At this point, the first top led s itches on to indicate the procedure, divided in 3 parts, has started.
After approx. 1-2 minutes, the procedure ill end displaying, if everything as successfully
completed, the three flashing leds and t o numbers on the display. The
≡
key allo s you to
return to normal operation ith temperature display. (for further information on the procedure,
refer to the relevant section of the manual)
Extended parameters
The TR-evo operation is configured by adjusting another set of parameters, called extended
parameters hich can be accessed ith the follo ing procedure:
To access the extended configuration parameters, bring the bottom display to value
10 using the key hen the top display sho s CFG and then press
.
The display then sho s the first extended parameter indicated by the parameter code
on the bottom display. If you do not ant to edit the value, press the
≡
key to go to
the next parameter, other ise the and keys edit the value and the
key saves
the parameter in the temperature controller non-volatile memory.
16
000
t D
000
D r
tun
1 0
cfg
1 0
100
1 1

The configuration parameters available are in sequence:
code 11 Max settable temperature for pre-heating. Configure the adjustment limit of the hP
parameter. The absolute maximum that can be set is 100°.
code 12 Max settable temperature for heating. Configure the adjustment limit of the parameter
ht. When the adjustment ith potentiometer is used, this ill adjust bet een a minimum set
ith the parameter ht and this maximum value. The absolute maximum settable is 500°.
code 13 Operating mode. See operating modes section of the manual
0 = adjustment only activates hen inputs activate at the relevant temperatures set
1 = adjustment activates at the input pre-heating temperature for heating.
2 = timed heating cycle aborts if input removed.
3 = timed heating cycle after impulse on heating input.
code 14 Timers unit of measurement selection. It allo s to operate ith times up to 99.9 sec.
CEn (timing in hundredths of a second)
dEC (timing in tenths of a second)
code 15 Select temperature unit of measurement.
C (degrees Centigrade)
F (degrees Fahrenheit)
code 1 Analogue input voltage selection. Allo s you to adjust the temperature ith a
potentiometer connected to the device or ith an external 0-10V voltage connected instead of
the potentiometer.
POt input 0-5V ith potentiometer
U01 input 0-10V
code 17 Alloy used in heater. Indicates to the TR-evo hich material the heating element is made
of, to allo the correct temperature indication.
1 = Nichrome40
2 = AISI 316
3 = Alloy20
4 = MS500
5-9 = Others
code 18 Increment at minimum firing TRIAC This parameter allo s you to change ho the
heating element is po ered to improve performance in certain specific cases. The parameter
can take values bet een 0 and 20. Normally it should be left at 0.
code 19 Loop gain setting. It allo s to adapt the temperature control according to the specific
po er used in particular situations. The parameter can assume values bet een 0 (very lo
gain, hen specific po er is very high) and 30 (high gain to try to compensate very lo
specific po er). The default value is 5 valid for most configurations.
code 20 Serial bus mode. Select communication format depending on the other connected
devices.
72 = (7 + 2stop)
17

73 = (7 + EVEN )
74 = (7 + ODD )
1 = (8 + NONE )
2 = (8 + 2stop )
3 = (8 + EVEN )
4 = (8 + ODD )
code 21 Serial bus speed. As the previous parameter adapts communication to others connected
devices.
19 = 19200b/s
24 = 2400b/s
4 = 4800b/s
96 = 9600b/s
code 22 Device bus addres. Selects the number of peripheral devices that the TR-evo assumes in
the communications bus, its function is to allo multiple devices to connect to the same
communications port ithout interfering ith each other. Device address 58 is reserved and
must not be used on the bus that contains TR-evo devices.
On code 23, the display sho s rEt and allo s you to exit parameter programming
status by pressing the
key.
The
≡
key returns you to the beginning parameter 11 display.
Maintenance
ATTENTION: before carrying out any maintenance operation, ensure you have
disconnected power.
The temperature controller does not require particular maintenance, ho ever you are advised to
every no and then check all the connections are tight, especially those going from the
transformer to the heating element that carry very high current peaks.
The front of the keypad and the numerical display should be cleaned ith a clean, et cloth and
neutral detergent. The dirt on all the other parts should be removed ith compressed air.
18
ret
2 3
Table of contents
Popular Controllers manuals by other brands

Samson
Samson TROVIS 6495-2 Mounting and operating instructions

Warner Instruments
Warner Instruments TC-324C manual

Reer
Reer MOSAIC Master M1 Installation and use manual

Samson
Samson 3374 Mounting and operating instructions

Shihlin electric
Shihlin electric SA3 Series instruction manual

JBL
JBL SYNTHESIS SDP-40HD user guide