ABOUT THIS MANUAL
This manual is included as a quick reference for installation. For further
information on the use of this device with a FACP, please refer to the
panel’s manual.
Note: This manual should be left with the owner/operator of this
equipment.
DETECTOR BASE DESCRIPTION
The MIX-4001and MIX-4002 bases are used to interface MIX-4000 series
detectors to the SLC line and remote devices. The base can be wired and
secured to a back-box during building construction, allowing the detector
to be installed later, when premises become free of dust and other
contaminants. The MIX-4001 and MIX-4002 both have a set of mounting
holes covered by the detector head. On the MIX-4001, these are used to
mount the base to single gang boxes, 3.5" octagonal boxes, and 4"
octagonal boxes. On the MIX-4002, the holes are used to mount the base
to 3.5" octagonal boxes. The MIX-4001 has an extra set of outer holes,
covered by a removable ring, for 4" square boxes (see figure 2). When the
base is secured to the box, the ring is placed back to cover the mounting
screws heads. A breakable flat tab in the center of the base can be cut
and inserted in the base outer edge then pen marking or a label can then
be used to identify the device.
Before installing this device please thoroughly read this manual and refer
to the applicable codes for guidance on location, spacing and acceptable
use. Also seek guidance from the compatible control panel instructions for
the device operation modes and the configuration requirements.
Note: If the detector is used with the remote indicator, then the voltage
value of the detector must be at least 18V as the indicators do not operate
below 18V.
SPECIFICATIONS
MIX-4001 Dimensions: 6” Diameter, 5/8” Height
MIX-4002 Dimensions: 4” Diameter, 5/8” Height
Wiring range on all terminals: 22 to 12 AWG
FIGURE 1 BASE WIRING
INSTALLATION
The MIX-4001 may be installed over a 4" square, 4" octagonal, 3.5"
octagonal, or single gang box. The MIX-4002 may be installed over a 3.5"
octagonal box. The mounting may be performed on either the ceiling or
the wall. SLC line and remote output connections for the MIX-4001/4002
base are show in figure 1. A twisted pair cable should be used for the SLC
line. If a shielded cabled is used, connect the shields to the proper
terminal on the base. Do not connect shields to earth ground. If a ground
continuity wire is required by the local code, it should be a separate
conductor. Please note that shielded cables may reduce the SLC loop
length that can be achieved due to their high capacitance.
A breakaway tab inside the base can be inserted in the outer rim of the
base to visibly identify each detector with their address. See figures 1, 3,
and 5. The detector can then be placed on the base using the following
steps:
1. Position the detector centrally on its adapter base ensuring it is level.
2. Rotate clockwise applying gentle pressure. The detector will drop
into its keyed location.
3. Continue to rotate clockwise a few degrees until the detector has fully
engaged in the adapter base.
4. When the detector is firmly engaged, check the alignment of the
raised reference marks on the detector and on the base (figure 4).
See page 2 for instructions on using the anti-tamper feature.
IMPORTANT NOTE ON BASE INSTALLATION
Disconnect loop power before installing the base.
When duplicate terminals are not provided to facilitate monitoring of the
installation wiring connections, and there is no provision to prevent looping
an unbroken wire around or under a terminal, the word "CAUTION" and
the following or equivalent text in letters not less than 2.38 mm (3/32 inch)
high shall be included on the installation drawing: "FOR SYSTEM
MONITORING - FOR TERMINALS "Loop out (+)" AND "Remote Device
(+)", DO NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE
RUN TO PROVIDE MONITORING OF CONNECTIONS.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
MIX-4001 / 4002 DETECTOR BASE