Microsensor MFE600H Series User manual

MFE600H
Operation Manual
V2.1

I
Content
1 Introduction.......................................................................................................................................... 2
2 Specifications...................................................................................................................................... 2
3 Electrical Connection.......................................................................................................................... 3
3.1 Integrated wiring .......................................................................................................................... 3
3.2 Separated wiring.......................................................................................................................... 4
4 Start up................................................................................................................................................ 5
5 Operation............................................................................................................................................. 6
5.1 Key instruction ............................................................................................................................. 6
5.2 Key operation............................................................................................................................... 7
6 Parameter setting and method............................................................................................................ 7
6.1 Report query................................................................................................................................ 7
6.2 Parameters setting....................................................................................................................... 7
6.3 Password menu........................................................................................................................... 8
7 Introduction to some parameters of instrument energy meter.............................................................. 19
7.1 Flow parameter............................................................................................................................. 19
7.2 Output parameters........................................................................................................................ 20
7.3 Flow meter location....................................................................................................................... 21
7.4 Temperature parameter................................................................................................................. 21
7.5 Total amount setting parameters................................................................................................... 22
8 Installation requirements................................................................................................................... 22
9 Modbus RTU communication............................................................................................................ 26
10 Responsibility.................................................................................................................................... 28
Our company reserves the right to modify this manual due to product technology and process updates. If
there are changes, no further notice will be given.
Please note the latest version of this manual.
The company reserves the right of final interpretation of this manual.

2
Thank you very much for choosing our products. In order to better use the product, it is recommended
that you read the instructions carefully before using the product.
1Introduction
MFE600H Series Energy Electromagnetic Flowmeter is designed and manufactured with the most
advanced domestic and abroad technology, featuring high accuracy, reliability, good stability and long
service life. We pay our attention to every detail in the process of the product structure design, material
selection, manufacturing, assembly and factory testing etc. With a water tower up to 37m as pressure
stabilizer for actual flow calibration, we have a professional production line for electromagnetic
flowmeter, also we design and develop a series of software and hardware for energy electromagnetic
flowmeter for mass production to ensure high quality in long term use.
It can be widely used in heating, air-conditioning and other heat measurement in civil residential districts,
office buildings and enterprises and institutions.
2Specifications
Table 1
Diameter
Flange type DN25~DN400
level of accuracy
level 2
Electrode type
Standard fixed electrode, antifouling electrode
Structure type
Integrated type, separated type (cable length of separated type≤100m)
Electrode material
316L, Ti, HB/HC, Ta, WC, Pt
Lining material
Neoprene(CR)、 Polytetrafluoroethylene(PTFE)、F46
Measured pipe
Stainless steel
Nominal pressure
0.6MPa、1.0MPa、1.6MPa、2.5MPa、4.0MPa
flange/body flange
Carbon steel (standard), stainless steel (optional)
converter housing
Aluminum die-casting
Power supply
100 V AC~240V AC
12V DC、24V DC
Output signal
4mA~20mA DC (load resistance 0Ω~750Ω, active output)
Frequency, pulse output (Passive, active output optional)
Upper and lower limit alarm output (rated value 30V DC, 100mA)
RS485(Modbus protocol), RS232
Profibus-DP、Profibus-PA
Electrical connection
M20×1.5
IP protection
IP65
Display function
English
Display Data
Instantaneous heat, instantaneous flow, accumulated heat,
accumulated flow, flow rate
Maximum flow reading (m³)
99999999999
Maximum heat quantity reading (MWH)
99999999999
Heat flow unit
MJ/h、GJ/h、kWh/h、MW/h
Temperature Sensor
PT1000
Installation method
Plug-in installation
Temperature measurement range
-50℃~200℃

3
3Electrical Connection
The MFE600H energy electromagnetic flowmeter converter can be divided into integrated converter and
separated converter, and the wiring diagram is shown in Figure 1 and Figure 2.
When wiring, please note:
a) RS485 communication cable needs to use two-core twisted pair shielded wire;
b) The same cable shall not be used for the power line and 4mA~20mA DC signal line. Two cables
shall be connected separately.
3.1 Integrated wiring
Figure 1 Integrated wiring diagram
When connecting the power cable, pay attention to select the appropriate voltage level wiring. For
different voltage levels, select 220V AC or 24V DC wiring to avoid power wiring faults.
When wiring, select the corresponding power terminal to connect to the power line according to the
product specifications, and then connect to the signal line according to the required output signal. See
Table 2 for the specific meaning of the integrated electromagnetic flowmeter wiring terminals.
Table 2
Terminal Symbol
Function
1
T-/B
RS485/RS232 communication output
2
RS232 GND
RS232 grounding wire
3
T+/A
RS485/RS232 communication input
4
IOUT
4mA~20mA DC output;
5
POUT
Pulse/frequency output
6
COM
Pulse/frequency output grounding wire
7
TRH1
Inlet thermal resistance
8
TRH2
9
TRH3
10
TRL1
Outlet thermal resistance
11
TRL2
12
TRL3
13
S1
Electrode wire
14
S0
Signal grounding wire
15
S2
Electrode wire
16
+24V
24V DC (12V DC) power supply access
17
-24V

4
18
PE
Power grounding wire
19
220V
220V AC power supply access
20
220V
21
EX1
Exciting current
22
EX2
3.2 Separated wiring
Figure 2 Separated wiring diagram
When connecting the power cable, pay attention to select the appropriate voltage level wiring. For
different voltage levels, select 220V AC or 24V DC wiring to avoid power wiring faults.
When wiring, select the corresponding power terminal to connect to the power line according to the
product specifications, and then connect to the signal line according to the required output form. See
Table 3 for the specific meaning of the integrated electromagnetic flowmeter wiring terminals.
Table 3 Terminal definition of separated type
Terminal Symbol
Function
1
T+/A
RS485/RS232 communication output
RS232 grounding wire
RS485/RS232 communication input
2
RS232 GND
3
T-/B
4
I mA
4mA~20mA DC output;
Active output If passive
output Then pull out the
shorting piece
5
ICOM
Current output grounding wire
6
P+
2-way flow pulse output/frequency output
7
PCOM
Pulse output grounding wire
8
TRH1
Inlet thermal resistance
9
TRH2
10
TRH3
11
TRL1
Outlet thermal resistance
12
TRL2
13
TRL3
14
EX1
Exciting current
15
EX2
Shielding network
DS1
16
SIG1
Electrode wire

5
17
SGND
Signal grounding wire
18
SIG2
Electrode wire
Shielding network
DS2
19
220V
220V AC power supply access
20
220V
21
PE
22
24V
24V DC power supply access
23
24V
4Start up
4.1 Switch on
Before turning on the power, please check that the system has been properly installed as required,
including:
a) The instrument shall be mechanically safe and shall be installed in accordance with regulations;
b) The power supply shall be connected according to regulations;
c) The electrical connection wire of the cavity shall be protected, and the cap shall be tightened;
d) Please check whether the running data of the power supply is correct.
4.2 Converter start-up
The measuring instrument is composed of a sensor and a converter and is ready for immediate use
when it is supplied. All operating data is factory set according to your order, please refer to the provided
inspection report for details.
After turning on the power, the flowmeter performs a self-check first. After the self-check, the flow meter
directly starts flow measurement and displays the current measured value.
Figure 3 Main interface of flow meter
The detailed information of the flowmeter interface status after startup is shown in Table 4.
Table 4
Display
Description
Reuse content
①
Real-time flow value and unit
Null
②
Inlet and outlet temperature
values
The display can be switched through the down key: flow
percentage, resistance value, temperature difference, flow rate
③
Alarm mark
System alarm, you can check the alarm content by up key
④
Accumulated of heat quantity
Accumulated heat, accumulated flow, and view specific alarm
content through the up key
④
③
①
②

6
The "bell" sign at the upper right of the meter is an alarm sign. You can view the alarm message by the
key. The possible causes for the alarm are shown in Table 5.
Table 5
Item
Alarm content
Possible causes
1
Excitation
impassability
The excitation part is not working normally. The excitation line may be
loose or misconnected
2
Empty pipe
The fluid is not filled with pipe; the media conductivity is less than 5us;
the electrode is misconnected
3
Electrode
The fluid is not filled with pipe; the media conductivity is less than 5us;
the electrode is misconnected
4
Upper flow limit
The real-time flow value is higher than the set upper limit of alarm
value
5
Lower flow limit
The real-time flow value is lower than the set lower limit of alarm value
5Operation
5.1 Key instruction
The electromagnetic flowmeter display and operation interface are shown in Figure 4. There is a key on
the left side of the screen and 4 keys on the bottom side of the display screen.
Figure 4 Operation interface
The meaning of the keys and operation methods are shown in Table 6. The composite key needs to
press two keys at the same time. If there is no key operation within 10 minutes, it will automatically
return to the main screen. This version does not provide touch keys or infrared remote-control keys. If
you need to set up, you must open the front cover.
Table 6

7
Key
Sign
Function
Shift
1. Use in combination with the confirm key to enter the
password interface;
2. Cursor movement during password input
Down
Number minus 1 or page down
Up
Number plus 1 or page up
Enter
Enter or exit
Function
Enter key for report, data reset and other functions
5.2 Key operation
The meter can enter the menu setting interface by simultaneously pressing the "shift" and "enter".
Customers can choose the corresponding password to enter the menu for operation according to
different needs. The meter password has two levels: level 1 password is 09454 and the level 2 password
is 19818. The authority of level 1 password is different from that of level 2 password. Level 2 password
has higher authority and more parameters can be changed. If customers need to modify level 1 or 2
password, it can be done in the secondary menu password modification item.
Note: If you modify level 1 or level 2 password, please remember the modified password!
6Parameter setting and method
6.1 Report query
In the main interface state (Figure 4), press (Function key) to enter the report query interface
(Figure 5), and then select the corresponding function to view the data according to actual needs.
Figure 5 Report query interface
Users can query 4 types of reports: daily, monthly, annual, and power outage reports. The meter can
save up to 90 daily reports, 36 monthly reports, 3 annual reports and 20 power outage reports.
6.2 Parameters setting
In the main interface state (Figure 4), press + ("shift" + "enter”) to enter the password input
interface (Figure 6). The user enters the corresponding password by entering passwords. The menu
sets the parameters related to the use of the flowmeter.
Special tips: Please operate carefully when setting, so as to avoid the failure of the flowmeter due to the
Day Report
Month Report
Year Report
Power Report

8
parameter setting!.
Figure 6 Password input interface
6.3 Password menu
Users enter the menu through password "19818” and can set the parameters in the menu. The specific
parameter information and data type are shown in Table 7.
Table 7
Items
Functions
Setting/Instructions
Parameter Range
1
Language
English
2
Communication
address
Range:0~255
3
Communication
rate
Rate:1200,2400,4800,9600,14400
Check: no check, odd parity Check, even parity
check
4
Pipe Diameter
3, 6, 8, 10, 15, 20, 25, 32, 40, 50...3000
5
Range setting
m³/h, L/s, L/m, L/h, Ukg/s, Ukg/m, Ukg/h, Usg/s,
Usg/m, Usg/h, T/s, T/m, T/h, kg/s, kg/m, kg/h, m³
/s, m³/m
Flow Range Max
200.0000 m3/h
Pipe Diameter
100
COM Baud Rate
9600 N
COM Address
001 k
Language
English
Pass Word Input
00000

9
6
Damping time
0.5s, 0.8s, 1.0s, 2s, 3s, 4s, 5s, 6s, 8s, 10s, 20s,
30s, 50s, 100s
7
Zero velocity
correction
8
Small signal
excision
Data type: integer
Range:0~100%
9
Remove display
Yes, NO
10
Flow direction
Positive, reverse
11
Reverse
measurement
Yes, No
12
Flow integration
unit
1m³, 0.1m³, 0.01m³, 0.001m³, 1L, 0.1L, 0.01L,
0.001L, 1t, 0.1t, 0.01t, 0.001t, 1kg, 0.1kg, 0.01kg,
0.001kg, 1gal, 0.1gal, 0.01gal, 0.001gal, 1ig, 0.1ig,
0.01ig, 0.001ig
13
Pulse output
method
Frequency output, pulse output
Pulse Output Mode
Frequency
Unit Totalizer
0.001 m³
Flow Direction
Forward
Flow Direction
Forward
Low Cutoff Mode
Disable
Low Flow Cutoff
0.50 %
Zero Correct Set
V= +0.000m/s
Zero=+0.000m/s
Damp Time Set
1 S

10
14
Frequency
output range
1~5000
15
Sensor
coefficient value
Factory set, unchangeable
16
Calibration
coefficient
Factory set, unchangeable
17
Additional
coefficient
Factory set, unchangeable
18
Converter
coefficient
Factory set, unchangeable
19
Converter code
value
Factory set, unchangeable
20
Empty pipe
alarm
Yes, No
21
Empty pipe
alarm threshold
value
Factory set, unchangeable
Empty Threshold
100.0 KΩ
DetectEmpty Pipe
Enable
Converter SN.
000018120162
Converter Factor
1.0136
Additional Factor
1.0000
Calibrated Scale
1.0000
Sensor Factor
1.0000
Frequency Range
1000 HZ

11
22
Upper limit alarm
Enable, Disable
23
Upper limit alarm
value
Full scale percentage setting
24
Lower limit alarm
Yes, No
25
Lower limit alarm
Full scale percentage setting
26
Electrode alarm
threshold
0-999.9 adjustable
27
Resistance
coefficient
28
Current zero
point correction
Factory set, unchangeable
29
Current full-scale
correction
Factory set, unchangeable
Current Full Adj .
0.9960
Current Zero Adj .
0.9917
Res.Coefficient
20.000
Pole Threshold
100.0 KΩ
Lower Threshold
20.00 %
Lower Limit Alarm
Disable
Upper Threshold
80.00 %
UpperLimit Alarm
Disable

12
30
Excitation
method
4 types: 50 Hz,25 Hz,12.5 Hz,6.25 Hz
31
Positive total
preset
adjustable
32
Reverse total
preset
adjustable
33
Non-linear
correction
34
Non-linear
correction point
1
35
Non-linear
correction point
2
36
Non-linear
correction point
3
37
Non-linear
correction point
4
NonlineCorrenct4
V= 1.2000m/s
K= 1.0000
NonlineCorrenct3
V= 0.9000m/s
K= 1.0000
NonlineCorrenct2
V= 0.6000m/s
K= 1.0000
NonlineCorrenct1
V= 0.3000m/s
K= 1.0000
NolineCorrenction
Disable
Set Totalizer R.
000000000000007
698305.887683732
L
Set Totalizer F.
000000000000007
698305.887683732
L
Excite Mode
Mode 4

13
38
Non-linear
correction point
5
39
Acquisition
buffer depth
0~199 adjustable
40
Excitation
current test
Yes, No
41
Current output
0mA~10mA, 4mA~20mA
42
Output test
20mA/2000Hz, 10mA/1000Hz, 4.16mA/20Hz,
4mA/1Hz
43
Density of
measured fluid
As customers’ request
44
Change rate limit
value
0~100% adjustable
45
Insensitive time
0~99S adjustable
Slope Limit Time
10 s
Slope Limit
30.0 %
Liquid Density
1.000 t/m³
Output Test
Disable
Current Mode
4-20mA
Excite Test
Disable
Buffer Size
004
NonlineCorrenct5
V= 1.5000m/s
K= 1.0000

14
46
Level 1
password
modification
adjustable
47
Level2 password
modification
adjustable
48
Level3 password
modification
adjustable
49
Level4 password
modification
adjustable
50
Date-YY/MM/DD
adjustable
51
Time-HH/MM/SS
adjustable
52
System running
time
53
System time
adjustable
System Time
2021/03/08
11:57:54
System Run Time
1 Day 13 Hour
34 Min 43 Sec
Hour-Min.-Sec.
1 1 / 5 7 / 4 9
Year-Month-Day
2 1 / 0 3 / 0 8
Password Level4
00000
Password Level3
00000
Password Level2
00000
Password Level1
00000

15
54
LCD screen
brightness
1~5 adjustable
55
Measurement
mode
heat cool
56
Calibration mode
Enable, Disable
57
Emulate mode
Enable, Disable
58
Work pressure
0.6MPa 1.6MPa
59
Heat
accumulation
unit
0.0001MJ/0.001MJ/0.01MJ/0.1MJ/1MJ
0.0001GJ/0.001GJ/0.01GJ/0.1GJ/1GJ
0.0001KWh/0.001KWh/0.01KWh/0.1KWh/1KWh
0.0001MWh/0.001MWh/0.01MWh/0.1MWh/1MWh
60
Cool
accumulation
unit
0.0001MJ/0.001MJ/0.01MJ/0.1MJ/1MJ
0.0001GJ/0.001GJ/0.01GJ/0.1GJ/1GJ
0.0001KWh/0.001KWh/0.01KWh/0.1KWh/1KWh
0.0001MWh/0.001MWh/0.01MWh/0.1MWh/1MWh
61
Heat range
setting
Heat Range Max
100.0000 MJ/h
Unit Acc. Cool
1MJ
Unit Acc. Heat
1MJ
Press Mode
0.6 MPa
Emulate Mode
Disable
Calibration mode
Disable
Measure Mode
heat
LCD Brightness

16
62
Cool range
setting
63
Pulse output
type
adjustable
64
Current output
parameters
Cool, Heat, Flux
65
Pulse coefficient
66
Initial
measurement
temperature
difference
67
Cut off the
difference
between cold
and heat
Enable, Disable
68
Heat meter initial
measurement
temperature
69
Cold meter initial
measurement
temperature
Cold Start T.
0.0000℃
Heat Start T.
0.0000℃
Low H.C. Cutoff
Disable
Low H.C. Cutoff
0.0500℃
Pulse Factor
100.00
Current Type
Cool
Pulse output
Heat MJ
Cool Range Max
100.0000 MJ/h

17
70
Accumulated
heat total preset
71
Accumulated
cold total preset
72
Inlet temperature
Emulate
73
Outlet
temperature
Emulate
74
Flow Emulate
75
Temperature
input Emulate
PT1000, PT100
76
Input PT1000
calibration 1
Access standard resistance 1, automatic correction
77
Input PT1000
calibration 2
Access standard resistance 2, automatic correction
In Pt1000 Check 2
Input: R=1.5kΩ
Measure:1498.0Ω
In Pt1000 Check 1
Input: R=1kΩ
Measure:1000.6Ω
Temp. Input Mode
Pt1000
Flux Emu Set
100.00 m/s
Out Temp. Emu Set
18.000 ℃
In Temp. Emu Set
20.000 ℃
Set Totalizer C.
00000000000 J
Set Totalizer H.
00000000000 J

18
78
Output PT1000
calibration 1
Access standard resistance 1, automatic correction
79
Output PT1000
calibration 2
Access standard resistance 2, automatic correction
80
Flowmeter
location
Entrance / Exit
Partial electromagnetic energy meter menu
Items
Measurement parameters
Setting
Parameter Range
Passwor
d level
1
Instrument working
Choose
Heat working mode,
Cooling working mode,
Heat cool working mode
2
Heat flow unit
Choose
GJ/h, MJ/h, KWh/h, MWh/h
3
Cooling flow unit
Choose
GJ/h, MJ/h, KWh/h,
MWh/h
4
Temperature difference
signal removal
Setting
5
Total heat unit
Choose
0.0001MJ, 0.001M, 0.010MJ,
0.100MJ,1.000MJ, .0001GJ,
0.001GJ, 0.010GJ, 0.100GJ,
1.000GJ,0.0001KWh,
0.001KWh,0.010KWh,
0.100KWh,1.000KWh,
0.0001MWh,0.001MWh,
0.010MWh,0.100MWh, 1.000MWh
6
Total cooling unit
Choose
0.0001MJ, 0.001MJ, 0.010MJ,
0.100MJ, 1.000MJ, 0.0001GJ,
0.001GJ, 0.010GJ, 0.100GJ,
1.000GJ,0.0001KWh,
0.001KWh,0.010KWh,
0.100KWh,1.000KWh,
0.0001MWh,0.001MWh,
0.010MWh,0.100MWh, 1.000MWh
Out Pt1000 Check 2
Input: R=1.5kΩ
Measure:1467.3Ω
Out Pt1000 Check 1
Input: R=1kΩ
Measure:989.92Ω
EMF Position
Entrance

19
7
Current output
Choose
Flow output、Heat output
Cooling output、Cold and heat output
8
Heat range setting
Setting
9
Cooling range setting
Setting
10
Pulse output method
Choose
Flow frequency output Hz, Flow pulse
L, Flow pulse m³Heat pulse MJ, Heat
pulse GJ, Heat pulse KWh, Cooling
output MWh, Cooling pulse MJ,
Cooling pulse GJ, Cooling pulse KWh,
Cold and heat output MWh, Heat and
cooling pulse MJ, Heat and cooling
pulse GJ, Heat and cooling pulse
KWh, Cooling and heat output MWh
11
Output pulse coefficient
Setting
12
Flow meter location
Choose
Flow inlet、Flow outlet
13
Heat meter to measure
water temperature
Setting
0~199.9
14
Cooling meter to measure
water temperature
Setting
0~199.9
15
Working pressure selection
Choose
0.6MP/1.6MP
16
Inlet PT check 1
Access standard
resistance 1
Automatic correction
17
Inlet PT check 2
Access standard
resistance 2
Automatic correction
18
Outlet PT check 1
Access standard
resistance 1
Automatic correction
19
Outlet PT check 2
Access standard
resistance 2
Automatic correction
20
Thermal resistance type
Choose
Pt1000 Pt100
21
Simulation mode
Choose
Enable/Disable
22
Entry temperature setting
Setting
0~199.9
23
Export temperature setting
Setting
0~199.9
24
Test flow rate setting
Setting
0~19.999
25
Total heat preset
Choose
26
Total cooling capacity preset
Setting
27
Calibration mode
Choose
Enable/Disable
The meter needs to set the operating parameters correctly to make the meter run in the best state and
obtain higher measurement display accuracy and measurement output accuracy。
7 Introduction to some parameters of instrument energy meter
7.1 Flow parameter
7.1.1 Instrument working mode
The electromagnetic flowmeter heat meter has three working modes: Heat working mode, Cooling
working mode, heat and cooling working mode.
Table of contents
Other Microsensor Measuring Instrument manuals

Microsensor
Microsensor MPM486 User manual

Microsensor
Microsensor MPM430 User manual

Microsensor
Microsensor MPM480 User manual

Microsensor
Microsensor MPM User manual

Microsensor
Microsensor MPM426WS User manual

Microsensor
Microsensor MDM7000 User manual

Microsensor
Microsensor MPM380 User manual

Microsensor
Microsensor MFE600C User manual