Milltronics Mercap MCP01 S series User manual

MERCAP MERCAP
MERCAP
Instruction Manual
June 2001
Siemens Automation

© Siemens Milltronics Process Instruments Inc. 2001
Safety Guidelines
Warning notices must be observed to ensure personal safety as well as that of others, and to
protect the product and the connected equipment. These warning notices are accompanied
by a clarification of the level of caution to be observed.
Qualified Personnel
This device/system may only be set up and operated in conjunction with this manual.
Qualified personnel are only authorized to install and operate this equipment in accordance
with established safety practices and standards.
Warning: This product can only functionproperly and safely if it is correctly transported,
stored, installed, set up, operated, and maintained.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Instruments Inc. 2000. All Rights Reserved Disclaimer of Liability
This document is available in bound version and in
electronic version. We encourage users to
purchase authorized bound manuals, or to view
electronic versions as designed and authored by
Siemens Milltronics Process Instruments Inc.
Siemens Milltronics Process Instruments Inc. will
not be responsible for the contents of partial or
whole reproductions of either bound or electronic
versions.
While we have verified the contents of
this manual for agreement with the
instrumentation described, variations
remain possible. Thus we cannot
guarantee full agreement. The
contents of this manual are regularly
reviewed and corrections are included
in subsequent editions. We welcome
all suggestions for improvement.
Technical data subject to change.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI TechnicalPublications atthe following address:
Technical Publications
Siemens Milltronics Process Instruments Inc.
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Canada, K9J 7B1
Email: techpubs@milltronics.com
For the library of SMPI instruction manuals, visit our Web site: www.milltronics.com

7ML19981CM01.1 MERCAP – INSTRUCTION MANUAL Page 1
Table of Contents
Introduction
IntroductionIntroduction
Introduction
................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
....................................
........
.... 3
33
3
Identifications and Abbreviations..............................................................................................3
Technical Specifications
Technical SpecificationsTechnical Specifications
Technical Specifications
................................
................................................................
................................................................
................................................................
................................................................
................................................................
..............................................
............................
.............. 5
55
5
Electrodes.........................................................................................................................................5
Wetted Parts....................................................................................................................................5
Transmitter.......................................................................................................................................5
Electrodes and Process Connections
Electrodes and Process ConnectionsElectrodes and Process Connections
Electrodes and Process Connections
................................
................................................................
................................................................
................................................................
........................................................
................................................
........................ 7
77
7
Handling of Electrodes..................................................................................................................7
Characteristics ................................................................................................................................7
General Design Principles ...........................................................................................................8
Mercap Configurations.................................................................................................................9
Examples of Mercap Level Instruments ................................................................................10
Interface and Level Version (Mercap MCP 02)....................................................................15
Flanges ............................................................................................................................................17
Flange Standards .........................................................................................................................17
Applications Examples................................................................................................................19
Flow-Through Electrode
Flow-Through ElectrodeFlow-Through Electrode
Flow-Through Electrode ................................
................................................................
................................................................
................................................................
................................................................
................................................................
..............................................
............................
.............. 21
2121
21
FTS Series ......................................................................................................................................21
FTF Series.......................................................................................................................................22
MST9500 Transmitter
MST9500 TransmitterMST9500 Transmitter
MST9500 Transmitter
................................
................................................................
................................................................
................................................................
................................................................
................................................................
..................................................
....................................
.................. 24
2424
24
Operating Principles ....................................................................................................................24
Installation
InstallationInstallation
Installation
and Interconnection
and Interconnectionand Interconnection
and Interconnection................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................ 25
2525
25
Interconnection.............................................................................................................................26
Connection Diagrams..................................................................................................................27
Factory settings ............................................................................................................................29
Applications
ApplicationsApplications
Applications
and Grounding
and Groundingand Grounding
and Grounding ................................
................................................................
................................................................
................................................................
................................................................
................................................................
.......................................
..............
....... 30
3030
30
Start-up
Start-upStart-up
Start-up
................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
.........................................
..................
......... 35
3535
35
Push-Button Adjustment............................................................................................................35
Adjustment using HARTTM ..........................................................................................................36
Maintenance
MaintenanceMaintenance
Maintenance
................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................ 39
3939
39
Test function ..................................................................................................................................39
Appendix A: HART
Appendix A: HARTAppendix A: HART
Appendix A: HARTTM
TMTM
TM Documentation
DocumentationDocumentation
Documentation
................................
................................................................
................................................................
................................................................
........................................................
................................................
........................ 41
4141
41
HARTTM info.....................................................................................................................................41
HARTTM Conformance and Command Class .........................................................................41
MST9500 DD Menu/Variable Organization ..........................................................................43
HARTTM Response Code information.......................................................................................44
General transmitter information...............................................................................................44
Siemens Automation

Page 2 MERCAP –INSTRUCTION MANUAL 7ML19981CM01.1
Additional universal command specifications .....................................................................45
Additional common-practice command specifications.....................................................45
Transmitter specific commands...............................................................................................47
Appendix B: Tables
Appendix B: TablesAppendix B: Tables
Appendix B: Tables
................................
................................................................
................................................................
................................................................
................................................................
................................................................
.....................................................
..........................................
..................... 54
5454
54
Table A Conversion......................................................................................................................54
Table B Total Loop ΩVersus Supply Volts..........................................................................55
Table C Voltage Drop Versus mA For Current Transmitter Operation....................................55
Appendix C: Approvals
Appendix C: ApprovalsAppendix C: Approvals
Appendix C: Approvals................................
................................................................
................................................................
................................................................
................................................................
................................................................
.................................................
..................................
................. 56
5656
56
CE Certificate .................................................................................................................................56
Certificates and Approvals ........................................................................................................57
Control Drawing FM/CSA Approval Mercap........................................................................58
Index
IndexIndex
Index
................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
..............................................
............................
.............. 59
5959
59

7ML19981CM01.1 MERCAP –INSTRUCTION MANUAL Page 3
Introduction
The Mercap system is a high performance, level measurement instrument consisting of a
sophisticated, easy-to-adjust, transmitter (MST9500) combined with measurement electrodes
and process seals designed to accommodate numerous configurations. The electrode,
comprised of a measurement section and an active shield section, is the primary sensor of
the system, and it indicates the electrical capacitance value of the measurement section
relative to the environment (tank wall, stilling well, or conductive material). This electrode
then connects to the capacitance detector portion of the two-wire loop powered electronic
transmitter. The measurement section can be set up to measure the level of solids, liquids
and slurries, as well as the interface between two immiscible liquids.
The manual is presented in three sections:
1. The electrode process connections and seals
2. The transmitter
3. Appendix sections providing supplementary information.
Identifications and Abbreviations
Various mnemonics and abbreviations are used in this manual. See below:
Short form Long Form Description Units
CE /FM /CSA ConformitèEuropèene/
Factory Mutual/Canadian
Standards Association
DAC Digital Analog Converter
DCS Distributed Control System Control Room apparatus
Ex Explosion Proof
Exd Flame Proof
FV Full Vacuum
ESD Electrostatic Discharge
HARTTM Highway Addressable
Remote Transducer
LRV Lower Range Value value for 0 % 4 mA
LSL Lower Sensor Limit below which PV is incorrect
pF pico Farads 0.000000000001 Farad
ppm parts per million
PV Primary Variable measured value
Stilling Well grounded metal tube with
openings
SV Secondary Variable equivalent value
SVLRV Sec. Var. Lower Range Value 0 % equivalent value
SVURV Sec. Var. Upper Range Value 100 % equivalent value
µFmicro Farads 0.000001 Farad
URV Upper Range Value value for 100% 20 mA
µSec micro Seconds 0.000001 Seconds
USL Upper Sensor Limit above which PV is incorrect
HARTTM Communication Foundation, Austin, Texas, USA
Siemens Automation

Page 4 MERCAP –INSTRUCTION MANUAL 7ML19981CM01.1

7ML19981CM01.1 MERCAP – INSTRUCTION MANUAL Page 5
Technical Specifications
Electrodes
Process connections
Screw mounting:
Flange mounting:
NPT, BSPT, JIS.
ANSI, DIN
Process material: C 22.8 N, AISI 316 L, Monel 400, Hastelloy C22
Probe diameter (mm/inch): 9/0.35 (cable), 16/0.63 (rod), or 24/0.95 (rod)
Probe length (mm/inch)
Rod version:
Cable version:
5500/216
35000/1378
Probe lining: PFA, Enamel, PTFE
Pressure rating (bar/psi): FV - 200/2920 up to 525/7665 as option
Temperature rating (°C/°F): -200°/-328°to 200°/392°up to 450°/842°as option
Wetted Parts
Liner: PFA/PTFE
Flange: stainless steel or teflon lined
Transmitter
Measurement range (pF): 0 – 3300
Span (pF): minimum 3.3
Supply voltage (Vdc): •maximum 33
•minimum 12 Vdc at 3.6 mA
•minimum 9.5 Vdc at 22 mA
Output current (mA): 3.6 – 22 / 22 - 3.6 (2-wire current loop)
Smart communication: Acc. the HART Communication Foundation (HCF)
Temperature range (°C/°F): -40°/-40°to 85°/185°(ATEX–Explosion Proof: -20°/-4°to
60º/140º)
Siemens Automation

Page 6 MERCAP –INSTRUCTION MANUAL 7ML19981CM01.1
Temperature stability: 0.15 pF (0pF) or <0.25% (typically <0.1%) of actual
measurement value, whichever is greater over the full
temperature range of the product.
Non linearity and
reproducibility:
< 0.1% full scale and actual measurement respectively
Accuracy: <0.1% of actual measurement value
Features: •polarity protection input circuit
•E.S.D. protected (Loop)
•galvanically isolated measurement circuit
•fully potted with epoxy resin
Diagnostics (Includes fault
alarm):
•primary variable (PV) out of limits
•system failure measurement circuit
•deviation between A/D and D/A converter values
•check sum
•watch dog
•measurement current out of range
Measurement current
signalling:
NAMUR NE 43
Function rotary switch1
Position 1:
Position 2:
Position 3:
Position 4:
4 mA measurement value (set)
20 mA measurement value (set)
3.8 up to 20.5 mA range by means of a field service
programmer
functionality test
Approvals: •Cenelec, FM/CSA (IS), FM (Ex-proof), CE, ATEX
1 HART communication in all switch positions

7ML19981CM01.1 MERCAP –INSTRUCTION MANUAL Page 7
Electrodes and Process Connections
This section of the manual is designed to assist in the determination of the best possible
probe configuration for your application. Therefore, we discuss the electrodes and process
connections before the instrumentation and the operation procedures. When configuring the
unit to your application, use the sample configurations below as your criteria.
Mercap electrodes come in a variety of formats to provide the necessary characteristics for
correct mounting, chemical compatibility, temperature and pressure requirements, and
dielectric constant. Most applications use the simple threaded connection, which is directly
mounted in the tank with the mating threaded nipple, or with a flange adapter that includes a
threaded hole.
For applications requiring higher temperature and pressure, or greater integrity, welded and
solid machined flange versions are available with single or double cone seals, and/or a
second seal on the flange plate to avoid any metallic wetted parts.
Handling of Electrodes
WARNING: Do not scratch or gouge the PFA electrode insulation since this could
reduce the integrity of the insulation and the useful life of the electrode.
WARNING: Be careful with an enamel insulated electrode. Normally an enamel lining
is protected by a stilling well, which is part of the design.
WARNING: Do not damage the insulation jacket on the electrode during shipping,
packing, and installation. Most electrodes use PFA insulation, a very dense and reliable
type of Teflonthat prevents leakage and corrosion of the metal electrode and acts as
an insulator when conductive materials are being measured. Any damage to the
electrode can prevent proper performance.
WARNING (ATEX 100): Precautions MUST be taken to avoid ignition due to
hazardous electrostatic charges when an isolated probe is used in a potentially
explosive atmosphere caused by gas, vapor, or a non-conductive liquid, requiring
apparatus group IIC equipment. Or when the probe is used in a potentially explosive
atmosphere caused by dust.
Siemens Automation

Page 8 MERCAP – INSTRUCTION MANUAL 7ML19981CM01.1
Characteristics
The following characteristics apply to all general connection configurations:
•The standard Mercap insulated electrode is designed for use in both
conducting and non-conducting liquid applications.
•All electrodes consist of an active shield portion and a measurement portion,
which combine to form the complete electrode.
•The sum of the active shield length and the measurement length is the total
insertion length.
•The active shield design provides continuous immunity to the known changes
in conditions at the top of many vessels, where levels of vapours, dust, and
condensation are constantly changing.
•All changes in capacitance due to temperature and pressure changes that
could cause small changes in the seal geometry are also isolated from the
measurement signal because they are not included in the starting
capacitance of the electrode by virtue of the action of the active shield.
•Due to the well-controlled diameter of the electrodes and insulation, a linear
output is achieved over a wide range of capacitance values (3.3 to 3300 pF).
•The end seal is formed as an integral part of the electrode lining, giving
smooth and uniform insulation characteristics (tested to 55 kV).
•Standard single cone usage
•Secondary cone usage
General Design Principles
The Mercap capacitance level instrument combines an optimum combination of mechanical
and electrical/electronic principles in its design. Combining a single transmitter with as few
electrode configurations as possible maximizes the number of potential applications while it
minimizes the complexity of the instrument.
In principal, the standard threaded process connection (S-Series) with PFA insulated
electrode, including the active shield, provides good results in all measurement situations that
are within the temperature, pressure, and corrosive capabilities of the materials and seals.
This is true over a wide range of dielectric constants in both non-conducting and conducting
materials.
Applications outside of the standard capabilities of the S-Series would require a different
design configuration. These non-standard applications include:
Non-Standard Application Mercap Configuration
Non-metallic tanks with both conducting
and non-conducting liquids.
Use a stilling well to provide second
electrode reference.
Non-conducting liquids in spherical and
horizontal-cylindrical tanks.
Use a stilling well as linearizer.
Highly corrosive materials requiring no
metallic wetted parts.
Use flange mount with D, DD seal
version.
High pressure and temperature (greater
than 200 bar) with conductive liquid.
Use HP version.
Sanitary/food safe applications. Use Mercap MCP 03.

7ML19981CM01.1 MERCAP –INSTRUCTION MANUAL Page 9
Mercap Configurations
The Mercap is a versatile level measurement instrument that can be designed for your
specific application by taking the following conditions into consideration:
Process Connections
Any standard process connection is available with Mercap, and special versions can be
fabricated to match the mounting and application requirements. Various sizes of threaded
and flanged fittings are available.
Seal Types
The basic internal seal for the Mercap is of a conical-shaped, preloaded pressure/leak
resistant construction. Up to three levels of seal protection are implemented depending on
the integrity requirements of the application. A single or double cone internal seal forms 1 or 2
blocks against leaking, and a third flange face gasket is also available in the D and DD seal
construction. The flange face seal also provides a design with no metal wetted parts if
required.
Pressure and Temperature Considerations
The maximum temperature and pressure of operation for the standard Mercap level probe is
200°C (392°F) and 200 bar (2900 psi). There are, of course, qualifications that must be applied
to these maximums.
Enamel probes are suggested when process temperature exceeds 200 °C, and/or in
combination with very high pressure.
Note:
::
: Consult Milltronics for chemical applications other than water.
Process Connection and Seal Configuration of Mercap
Process Connection
Process ConnectionProcess Connection
Process Connection Seal Type
Seal TypeSeal Type
Seal Type Seal Description
Seal DescriptionSeal Description
Seal Description
Threaded S Single Cone
Welded Flange S Single Cone
S Single Cone
D Single Cone + Teflon flange seal
DD Double Cone + Teflon flange seal Consult factory*
SD Double Cone (used for stilling well applications)
Solid Machined
Flange
HP Consult factory*
Note: HP (high pressure) is only supplied with enamel insulation and a recommended
stilling well for protection of the enamel. A cone seal plus a secondary redundant seal
is provided between the electrode and the stilling well.
Siemens Automation

Page 10 MERCAP –INSTRUCTION MANUAL 7ML19981CM01.1
Examples of Mercap Level Instruments
The following graphics illustrate the variation in configurations available for the Standard
series, Level and Interface series, and Sanitary series Mercap level instrument.
Note: All measurements are given in millimeters/inches.
Standard Level Version (Mercap MCP01)
This is the most common version of Mercap and is available with the following features:
•Threaded flanges, welded flanges, and solid flanges
•S series, D series, SD series, DD series, and HP series process seals.
•Selections of standard ANSI and DIN flanges are available
•The most common electrode is insulated with PFA, but Enamel (HP seal) is also
available as standard (Enamel is only available on rigid design).
•Various process connection materials are also available
•Rigid and Flexible Cable versions available
MCP01 (Standard) S-Series: Threaded Versions
S-Series: Threaded
Active Shield
Insertion
Length+175
(6.9”)
Insertion
Length
Active
Length
∅16 (0.63”)
or ∅24 (0.94")
∅160
(6.3”)
40 (1.57")
Inactive Tip

7ML19981CM01.1 MERCAP –INSTRUCTION MANUAL Page 11
S-Series Cable Version S-Series Cable Version
(with anchor)
MCP01 S-Series Threaded Features
•single process seal
•suitable for most level, interface, or detection applications
•high temperature and pressure resistance
∅160 (6.3”)
Transmitter
Enclosure
120 (4.72")
Insertion Length
Dimension
Varies
Insertion
Length
Seal Gland
Threaded Process
Connector
See Order
Instructions
PTFE Insulation
∅9 (0.35")
Tensile Weight+/-Varies
Insertion
Length
+175 (6.9")
Inactive
Part
125 (4.9")
55 (2.17")
Siemens Automation

Page 12 MERCAP –INSTRUCTION MANUAL 7ML19981CM01.1
MCP01 (Standard) S-Series: Welded and Machined Flanged
Versions
S-Series Welded Flange S-Series Machined Flange
MCP01 S-Series Flange Features
•single process seal
•suitable for most level, interface, or detection applications
•high temperature and pressure resistant
Active
Length
Active
Length
Insertion
Length
Insertion
Length
Insertion
Length
+185 (7.28")
Insertion
Length
+185 (7.28")
Active Shield
Active Shield
TIG Weld
Inactive Tip
Inactive Tip
∅16 (0.63”)
or ∅24 (0.94")
40 (1.57")
40 (1.57")
∅16 (0.63”)
or ∅24 (0.94")

7ML19981CM01.1 MERCAP –INSTRUCTION MANUAL Page 13
MCP01 Standard D-Series: Machined Flanged Versions
D-Series DD-Series
MCP01 Standard D-Series Features
•single process seal
•all wetted parts made of PFA (probe
lining) or PTFE (flange face)
•according to NACE requirements
MCP01 Standard DD-Series Features
•double process seal
•redundant safety (e.g. Phenol,
Phosgene applications, etc.)
•all wetted parts made of PFA (probe
lining) or PTFE (flange face)
•according to NACE requirements
•suitable for turbulent and toxic
chemical applications
∅16 (0.63”) or
∅24 (0.94")
∅16 (0.63”) or
∅24 (0.94")
Inactive Tip Inactive Tip
Probe Probe
Insertion
Length
Insertion
Length
Active
Length
Active
Length
Active
Shield
Active
Shield
65 (2.56")
120 (4.72")
120 (4.72")120 (4.72")
∅160 (6.3") ∅160 (6.3")
Transmitter
Enclosure
Transmitter
Enclosure
Seal GlandSeal Gland
Flange
Process
Connection
Flange
Process
Connection
PTFE Lining
∅
k
∅D
∅
k
∅D
n
holes
n
holes
40 (1.57") 40 (1.57")
PTFE Lining
Siemens Automation

Page 14 MERCAP –INSTRUCTION MANUAL 7ML19981CM01.1
SD-Series Probe/Thermal Isolator
MCP01 Standard SD-Series Features
•double process seal
•redundant safety (e.g. Phenol,
Phosgene applications, etc.)
•all wetted parts made of PFA/PTFE
•according to NACE requirements
•suitable for turbulent and toxic
chemical applications
MCP01 Probe/Thermal Isolator
Features
•thermal isolator
∅160 (6.3") ∅160 (6.3")
Insertion
Length
Insertion
Length
Active
Length
Active
Length
40 (1.57") 40 (1.57")
∅16 (0.63”) or
∅24 (0.94")
∅16 (0.63”) or
∅24 (0.94")
Transmitter
Enclosure Transmitter
Enclosure
120 (4.72") 120 (4.72")
Flange
Process
Connection
Flange
Process
Connection
120 (4.72")
Seal
Gland
Seal
Gland
Thermal
Isolator
Probe
Probe
85 (3.35")
∅
k
∅
k
∅D∅D
n
holes
n
holes
Inactive Tip Inactive Tip
Active Shield Active Shield
Dependent on
extension length

7ML19981CM01.1 MERCAP –INSTRUCTION MANUAL Page 15
Interface and Level Version (Mercap MCP 02)
This version is designed specifically for interface level where a long distance active shield
portion of the electrode is required (up to 35 meters) before the measurement portion of the
electrode begins. This type of application is common in large storage tanks for oil where the
bottom of the tank invariably has a layer of water below the oil. Often, when measurement
spans as much as 5.5 meters (for the water), up to 35 meters of flexible bellows cable are
used.
MCP02: Interface Version
Process Connection Size
•threaded version: ¾", 1", 1½", 2"
NPT, BSPT, or JIS
•sanitary version: on customer
request
•flange version: on customer
request
Options
•thermal isolator
•stilling well
Aluminum Enclosure
•Nema 4/Type 4/IP65
Conduit Entry:
•½" NPT (2x)
Flexible
Tube
Insertion Length
35m (115ft) max.
100 (3.9")
Inactive Tip
∅16 (0.63”) or
∅24 (0.94")
Active Shield
Active Length
∅16 mm=2m
∅24mm=5.5m
∅160 (6.3")
185 (7.28")
Process
Connection:
flange or
threaded
mounting
Seal
Gland
Probe
Dependent on
extension length
Adjustable
extension
part
Transmitter
Enclosure
Siemens Automation

Page 16 MERCAP –INSTRUCTION MANUAL 7ML19981CM01.1
Sanitary Level Version (Mercap MCP 03)
The hygienic design includes threaded and tri-clamp versions for use in the food and
pharmaceutical industry.
MCP03: Sanitary Versions
Sanitary Thread Coupling Sanitary Tri-Clamp
MCP03 Sanitary Tri-Clamp Features
•maximum active length 5.5m
•minimum active length 50mm
∅16 (0.63”) or
∅24 (0.94")
∅16 (0.63”) or
∅24 (0.94")
40 (1.57") 40 (1.57")
Probe
Active
Length
Active
Length
Inactive Tip
Inactive Tip
118 (4.65")
Seal Gland
Transmitter
Enclosure
∅160 (6.3")
Active
Shield
Insertion
Length
Insertion
Length +
175 (6.9")
Active
Shield
Tri-clamp
Connection
Seal Gland
Insertion
Length
IDF Nut

7ML19981CM01.1 MERCAP –INSTRUCTION MANUAL Page 17
Flanges
Flange Standards
Note:
•All Sizes: MM
•One (1) inch: ^ 25.4mm
•Details: See drawings, technical data, and measuring probe details
øL
b
øK (n holes)
øD
Siemens Automation

Page 18 MERCAP –INSTRUCTION MANUAL 7ML19981CM01.1
Temperature Versus Pressure Curve Mercap Level Probe
In this situation, as the temperature reaches 75°C (167°F) the maximum pressure must be
derated. As the temperature reaches 200°C (392°F) the maximum pressure is limited to 50 bar
(725 psi). This curve is typical for water only, for other, more aggressive chemicals the
derating curve will be more severe.
Note: For high temperature and pressure ratings for the Enamel probe, please
contact your Siemens Milltronics representative.
Reference Product: Water
This manual suits for next models
5
Table of contents
Other Milltronics Measuring Instrument manuals

Milltronics
Milltronics AIRANGER DPL PLUS User manual

Milltronics
Milltronics miniranger plus User manual

Milltronics
Milltronics COMPUFLO III User manual

Milltronics
Milltronics ILE-37 User manual

Milltronics
Milltronics HydroRanger I User manual

Milltronics
Milltronics airanger XPL plus User manual

Milltronics
Milltronics MultiRanger Plus User manual

Milltronics
Milltronics HydroRanger Plus User manual

Milltronics
Milltronics IQ Radar 160 User manual

Milltronics
Milltronics MultiRanger Plus PL-513 User manual