Milltronics pointek uls200 User manual

Instruction Manual January 2003
ULS 200
pointek

© Siemens MilltronicsProcessInstruments Inc. 2003
Safety Guidelines
Warning notices must be observed to ensure personal safety as well as that of others, and to
protect the product and the connected equipment. These warning notices are accompanied
by a clarification of the level of caution to be observed.
Qualified Personnel
This device/system may only be set up and operated in conjunction with this manual.
Qualified personnel are only authorized to install and operate this equipment in accordance
with established safety practices and standards.
Warning: This product can only function properly and safely if it is correctly transported,
stored, installed, set up, operated, and maintained.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Instruments Inc.2003.AllRights ReservedDisclaimer of Liability
This document is available in bound version and in
electronic version. We encourage users to
purchase authorized bound manuals, or to view
electronic versions as designed and authored by
Siemens Milltronics Process Instruments Inc.
Siemens Milltronics Process Instruments Inc. will
not be responsible for the contents of partial or
whole reproductions of either bound or electronic
versions.
While we have verified the contents of
this manual for agreement with the
instrumentation described, variations
remain possible. Thus we cannot
guarantee full agreement. The
contents of this manual are regularly
reviewed and corrections are included
in subsequent editions. We welcome
all suggestions for improvement.
Technical data subject to change.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI Technical Publications at the following address:
Technical Publications
Siemens Milltronics Process Instruments Inc.
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Canada, K9J 7B1
Email: techpubs@siemens-milltronics.com
For the libraryof SMPI instruction manuals, visitour Web site: www.siemens-milltronics.com

7ML19981AS01 ULS 200 – INSTRUCTION MANUAL Page 1
Table of Contents
Pointek ULS 200 ...................................................................................................................2
Specifications ......................................................................................................................3
Installation ...........................................................................................................................5
Location .....................................................................................................................................................5
Mounting and Dimensions ................................................................................................6
Threaded ....................................................................................................................................................6
Sanitary ......................................................................................................................................................7
Interface ...............................................................................................................................9
Interconnection .................................................................................................................10
Operation ............................................................................................................................11
Start Up ....................................................................................................................................................11
Quick Start ..............................................................................................................................................11
Display / Operation Status ..................................................................................................................13
Applications .......................................................................................................................14
Adjustments .......................................................................................................................20
Troubleshooting .................................................................................................................28
Maintenance ......................................................................................................................29
Certifications .....................................................................................................................30

Page 2 ULS 200 – INSTRUCTION MANUAL 7ML19981AS01
Pointek ULS 200
Pointek ULS 200 is an ultrasonic based process level switch providing high or low switch
action on liquids or solids. The process part (sensor) is Tefzel®or Kynar Flex®, allowing it
to be used in a wide variety of industries.
Pointek ULS 200 contains an ultrasonic transducer and temperature sensing element. The
transducer emits a series of ultrasonic pulses. Each pulse is reflected as an echo from
the material and sensed by the transducer. Pointek ULS 200 processes the echo using
Milltronic's proven Sonic Intelligence®techniques. Filtering is applied to help
discriminate between the true echo from the material and the false echoes from
acoustical and electrical noises and agitator blades in motion. The time for the pulse to
travel to the material and back is temperature compensated and then converted into
distance for display and relay actuation.
The Pointek ULS 200 is an excellent primary detection device, but should not be used as
a backup device. For backup devices use a contacting technology such as the Pointek
CLS 200. The optional sanitary version affords quick removal and ease of cleaning as
demanded by the food, beverage, and pharmaceutical industries.
Pointek ULS 200 Outputs
• switch outputs programmable for high-high, high, low, and low-low level actions
• fail-safe programmable
Pointek ULS 200 Features
• 2" NPT, 2" BSP or PF2 or 4" 3A approved Tri-clamp process connection
• 2 conduit connections, 1/2 “NPT or PG 13.5
• non-corrosive enclosure and wetted parts
• 2 button programming
• level run/program LCD display
Pointek ULS 200 Applications
• liquids, slurries, and fluid materials
• foods and pharmaceuticals
• chemicals
Note: Pointek ULS 200 is to be used only in the manner outlined in this instruction
manual.

7ML19981AS01 ULS 200 – INSTRUCTION MANUAL Page 3
Specifications
ac Version
Power
• 100 - 230 V ac, +15%, 50/60 Hz, 12 VA (5W) max.
Fuse
• Slow-Blow, 0.25 A, 250 V ac
Output:
• repeatability: 0.25 % of full range
• resolution: 3 mm (0.1")
•relay: 2form C (SPDT) contacts, rated 5A at 250 V ac, non-
inductive
dc Version
Power
• 18 to 30 V dc, 3 W
Output:
• repeatability: 0.25 % of full range
• resolution: 3mm (0.1")
• relay: 2 form C(SPDT) contacts, rated 5 A at 48 V DC
OR
• transistor: 2 transistor switches, rated 100 mA maximum at 48 V DC
Environmental
• location: indoor/outdoor
• altitude: 2000m max
• ambient temperature: - 40° to 60° C (- 40° to 140° F)
* - 20° C (-5° F) if metal mounting
• relative humidity: suitable for outdoor (Type 6 / NEMA 6 / IP67 enclosure)
• installation category: II
• pollution degree: 4
Process Pressure:
• vented to atmosphere

Page 4 ULS 200 – INSTRUCTION MANUAL 7ML19981AS01
Switching Range
• liquids: 0.25 to 5m (0.8 to16.4 ft)
• solids: 0.25 to 3m (0.8 to 9.8 ft)
Memory
• non-volatile EEPROM
Programming
•2keys
Temperature Compensation
• built-in to compensate over the operating range
Display
• liquid crystal
• three 9mm (0.35") digits for reading of distance between sensor face and material,
multi-segment graphic for operation status
Electronics/Enclosure
• termination: terminal block, 2.5mm2(14 ga) solid1.5 mm2(16 ga)
stranded, maximum
•material: plastic
OR
epoxy coated aluminum with gasket
• ingress protection: Type 6 / NEMA 6 / IP671
• conduit: aluminum, 2 connections 1/2” NPT
plastic, 2 connections PG 13.5
Sensor
• material: Tefzel2®or Kynar Flex3®
• mounting: threaded:
• 2" NPT, 2" BSP or PF2
• optional flange adapter, to 3" ANSI, DIN 65PN10,
and JIS 10K3B
sanitary:
• 4" 3A compliant Tri-clamp fitting
Approvals
• CE (EMC performance available upon request.), CSANRTL/C, FM, 3A
• CSA/FM Class 1, Division 1, Group A, B, C, D; Class II, Group E, F, G; Class III
• Europe: ATEX II 2G, EEx md IIC T5
(see product nameplate for approval details)
1. Use only approved, suitable size hubs for watertight applications.
2. Tefzel ® is a registered trademark of Dupont.
3. Kynar Flex® is a registered trademark of Elf Atochem North America.

7ML19981AS01 ULS 200 – INSTRUCTION MANUAL Page 5
Installation
The Pointek ULS 200 should be mounted in an area within the temperature range
specified and suitable to the housing rating and materials of construction. Make sure the
cover is accessible to allow programming, wiring, and access to the display.
Keep the Pointek ULS 200 away from high voltage or current runs, contactors, and SCR
control drives.
Location
Locate the Pointek ULS 200 so that it has a clear sound path perpendicular to the
material surface.
The Pointek ULS 200 sound path should not intersect the fill path, rough walls, seams,
rungs, or any other obstruction.
-40°C
60°C
Warning: Explosion Hazard. Substitution of components may impair
suitability for Class 1, Division 2 applications.
sanitary ferrule
pipe
rungs
seams
fill

Page 6 ULS 200 – INSTRUCTION MANUAL 7ML19981AS01
Mounting and Dimensions
Mount the ULS 200 with sensor face at least 25cm above the highest anticipated level.
Threaded
The Pointek ULS 200 is available in three thread types: 2" NPT, 2" BSP, or PF2.
Before mounting the Pointek ULS 200, ensure that the mating threads are of the same
type, otherwise the threads can be damaged.
74 mm
(2.9”)
120 mm
(4.7”)
57 mm
(2.25”)
lid clip
#8-32x3/8”
machine screw
lid
conduit
connection
½” NPT
or
PG13.5
2” NPT
2” BSP
or
PF 2
74 mm
(2.9”)
180 mm
(7.1”)
electronics /
enclosure
sensor /
transducer
Notes:
• Dimensions are nominal and may vary with material types.
• Non-metallic enclosure does not provide grounding between connections.
• Use grounding type bushings and jumpers.

7ML19981AS01 ULS 200 – INSTRUCTION MANUAL Page 7
The Pointek ULS 200 can be fitted with the optional 75 mm (3") flange adapter for mating
to 3" ANSI, DIN 65PN10 and JIS 10K 3B flanges.
Sanitary
The Pointek ULS 200 also comes in a sanitary version for use in the food and
pharmaceutical industries.
Note: For CSA/FM approved Hazardous Location Models, see Siemens Milltronics
drawing 0-9440026Z-DI-A.
178 mm
(7.0”)
79 mm
(3.1”)
Notes:
• Dimensions are nominal and may vary with material types.
• Refer to threaded for other dimensions.

Page 8 ULS 200 – INSTRUCTION MANUAL 7ML19981AS01
Mount the Pointek ULS 200
onto the top of the tank's
sanitary ferrule.
Secure mating by surrounding
the joint with the optional clamp.
Tighten the adjusting nut
with your hand. Do not
use a wrench.
Sanitary Ferrule, 4" FDA Approved
(U.S. Food and Drug Administration)
Pointek
ULS 200
optional
clamp
adjusting
nut
ferrule
tank
*dimensions are approximate
119 mm
(4.68”)
97 mm
(3.83”)

7ML19981AS01 ULS 200 – INSTRUCTION MANUAL Page 9
Interface
ac Version
dc Version - Relay Output dc Version - Transistor Output
NL
100 - 230 V
213456789
12
2
2
1
1
Notes:
• A circuit breaker or switch in the building installation, marked as the
disconnect switch, shall be in close proximity to the equipment and within
easy reach of the operator.
• Relay contact terminals are for use with equipment having no accessible live
parts and wiring having insulation suitable for at least 250 V.
21 34567 89
12
2
2
1
1
24V
213456789
24V 12
2
2
1
1
Note:dc terminals shall be supplied from an SELV source in accordance with
IEC 1010-1 Annex H.

Page 10 ULS 200 – INSTRUCTION MANUAL 7ML19981AS01
Interconnection
Separate cables and conduits may be required to conform to standard instrumentation
wiring or electrical codes.
Relay Output
All relays are shown in their de-energized (unpowered) state.
Optional Transistor Output – dc Version only
Power
Notes:
• Installation shall only be performed by qualified personnel and in
accordance with local governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
n/o n/ocom comn/c n/c
456789
12
relay 1 relay 2
213
456789
24-30 V
12
relay 1 relay 2
18 to 30 V
21
2
N
1
L
3
dc Version
100 - 230 V 18 to 30 V
100 to 230 V ac supply 18 - 30 V dc supply
ac Version

7ML19981AS01 ULS 200 – INSTRUCTION MANUAL Page 11
Operation
Start Up
With the Pointek ULS 200 correctly installed (or aimed at a wall 0.25 to 5 m away), apply
power and observe the Pointek ULS 200 start up sequence. The unit will cycle through the
following screens:
1. Lighting of all possible LED values
2. Product revision number
3. Product model number
4. Run mode
The display and operation sequence arrives within a few seconds at the run mode, which
is the measurement of the distance from the transducer face to the material level in the
units indicated. Full instructions on setting up the unit are found at Applications on page
13 and Adjustments on page 19.
Quick Start
Use this setup method if you have a basic high/low application and you are setting up the
unit in a place where you can easily adjust the measured distance.
The Pointek ULS 200 relays are preset as: relay 1 = alarm 1, high alarm at 0.25 m
relay 2 = alarm 2, low alarm at 5.00 m
To change the setpoints by reference method, set the material or target to the distance as
displayed. Press the ` 1 / ↑‘or ` 2 / ↓' key. The display responds by displaying the current
setpoint function and value. By pressing the alarm key a second time, the Pointek ULS
200 changes the setpoint to the value currently being measured.
After viewing or changing the setpoint, the Pointek ULS 200 reverts to the run mode.

Page 12 ULS 200 – INSTRUCTION MANUAL 7ML19981AS01
relay 1
1. Position the unit so that it reads 0.75 m.
2.
3.
relay 2
1. Position the unit so that it reads 3.50 m.
2.
3.
0.75 m
m
1/↑
function display:
high alarm
current setpoint,
0.5 m
function display:
high alarm
m
4. Once installed, the unit
will register a high alarm
at 0.75 m from the
sensor face.
1/↑
if
Loss of Echo
retry
3.5 m
m
2/↓
function display:
pump up control
m
4. Once installed, the
unit will register a low
alarm at 3.50 m from the
sensor face.
2/↓
if
Loss of Echo
retry

7ML19981AS01 ULS 200 – INSTRUCTION MANUAL Page 13
Display / Operation Status
Operation Status - Run Mode
- echoes are valid and within range.
-echoes are lost due to poor conditions or out of range.
This may be typical in applications where there are deep
vessels and the material level is normally out of range.
Refer to Troubleshooting.
-extended loss of echo period. Operation has gone into fail-safe.
Refer to Troubleshooting.
m
ft
reading
output 1
output 2
operation
status
units
↓key
↑key
program
mode adjustment
value
units
m
ft

Page 14 ULS 200 – INSTRUCTION MANUAL 7ML19981AS01
Applications
Pointek ULS 200 is designed for use as a process level switch. The local display is used
only as an aid during start up. The instrumentation interface is comprised solely of the
two relay outputs. Switching applications are based on the relay functions adjustment.
The outputs can be set to function in the desired mode.
* Factory setting
Alarm: the relay de-energizes to set the alarm ‘ON’
Control or Pump: the relay energizes to set the device ‘ON’
Application Function Relay 1 Relay 2
High / Low level switch *1 High Alarm Low Alarm
High level switch with two height alarms 2 High Alarm High Alarm
Low level switch with two height alarms 3 Low Alarm Low Alarm
High level switch with loss of echo alarm 4 High Alarm LOE Alarm
Low level switch with loss of echo alarm 5 Low Alarm LOE Alarm
Pump down control with low level alarm 6 Pump Down Low Alarm
Pump down control with high level alarm 7 Pump Down High Alarm
Pump up control with low level alarm 8 Pump Up Low Alarm
Pump up control with high level alarm 9 Pump Up High Alarm
Pump down control with loss of echo alarm 10 Pump Down LOE Alarm
Pump up control with loss of echo alarm 11 Pump Up LOE Alarm
Pump up control and Pump down control 12 Pump Down Pump Up
Dual pump down control 13 Pump Down Pump Down
Dual pump up control 14 Pump Up Pump Up

7ML19981AS01 ULS 200 – INSTRUCTION MANUAL Page 15
High Level Alarm Switch
This application uses Pointek ULS 200 to provide an alarm output, high and/or high-high
alarm, when the process material rises to a high level. The device range applies to its
switching capability, and not the process range of the material.
It is therefore common to apply the switch on vessels where the material is normally
below the unit's range. Under such a condition the Pointek ULS 200 loses echo, and if
prolonged, defaults to fail-safe operation. As this would be a normal occurrence, it is not
advisable to select the fail-safe high option.
If the high level switch is being applied to a vessel within the 3 / 5 m range, a loss of echo
and ensuing fail-safe condition would not be a common occurrence. The fail-safe default
would then be at the user's discretion.
Application Adjustments
alarm function 2 - high / high-high alarm
4 - high / Loss of Echo (LOE)
alarm setpoint set the high and / or high– high alarms to the desired values
fail-safe mode 1 - high, except if the process range is beyond the Pointek ULS 200
operating range (3 / 5 metres)
2 - low
3 - hold
fail-safe = 1, 2 or 3 fail-safe = 2 or 3
high-high,
eg. 0.75 m
high,
eg. 1 m
blanking
e.g. 0.5 m
rangelimit
e.g. 5.5 m
high,
eg. 1 m
high-high,
eg. 0.75 m
blanking
e.g. 0.5 m
range limit
e.g. 5.5 m

Page 16 ULS 200 – INSTRUCTION MANUAL 7ML19981AS01
High / Low Level Alarm Switch
This application uses Pointek ULS 200 to provide high and low level alarms. The device
range applies to its switching capability, and not the process range of the material. As
such the low and/or low-low level setpoints must be within the device's range (3 / 5
metres).
If the material can fall below the unit's range, the Pointek ULS 200 loses the echo, and if
prolonged, defaults to fail-safe operation. The fail-safe default should be set to suit the
application.
Application Adjustments
alarm function 1 - high / low alarm
alarm setpoint set the high and/or low alarms to the desired values
fail-safe mode 1 - high
2 - low
3 - hold
fail-safe = 1, 2 or 3
high,
eg. 1 m
low,
e.g. 4.5 m
blanking
e.g. 0.5 m
range limit
e.g. 5.5 m
fail-safe = 2 or 3
low,
e.g. 4.5 m
range limit
e.g. 5.5 m
low,
e.g. 4.5 m
high,
eg. 1 m
blanking
e.g. 0.5 m

7ML19981AS01 ULS 200 – INSTRUCTION MANUAL Page 17
Low Level Alarm Switch
This application uses the Pointek ULS 200 to provide one or two low level alarms. The
device range applies to its switching capability, and not the process range of the material.
As such the low and / or low-low level setpoints must be within the device's range (3 / 5
metres).
If the material can fall below the unit's range, the Pointek ULS 200 loses the echo,
and if prolonged, defaults to fail-safe operation. The fail-safe default should be set to
suit the application.
Application Adjustments
alarm function 3 - low / low-low alarm
5 - low / LOE alarm
alarm setpoint set the low and / or low-low alarms to the desired values
fail-safe mode 1 - high
2 - low
3 - hold
fail-safe = 1, 2 or 3
low,
eg. 3.5 m
blanking
e.g. 0.5 m
range limit
e.g. 5.5 m
fail-safe = 2 or 3
low, low,
e.g. 4.5 m range limit
e.g. 5.5 m
blanking
e.g. 0.5 m
low,
eg. 3.5 m
low, low,
e.g. 4.5 m

Page 18 ULS 200 – INSTRUCTION MANUAL 7ML19981AS01
Dual Pump Control
This application uses Pointek ULS 200 to provide a control output when the process
material rises to a high level. The device range applies to its switching capabilities, and
not to the process range of the material. As such, the level setpoints must be within the
device’s range (3 / 5metres).
Typically, wet wells are used to temporarily hold storm and/or waste water. When the
water surface reaches a high level setpoint, the wet well is pumped down. The process
material will be pumped down by the deadband value to another setpoint where the
control will turn off.
Application Adjustments
relay function 6 - high control / low alarm
7 - high control / high alarm
10 - high control / LOE alarm
13 - high control / high control
relay setpoints: set to desired values
deadband values: referenced from relay setpoints
(distance from Pump Start setpoint to Pump Stop setpoint)
Relay Function 13: Dual Pump Down
4 m
relay 1
e.g. 1 m
relay 2
e.g. 0.75 m
blanking
e.g. 0.5 m
pump 2 start
pump 1 start
deadband 1
e.g. 3 m
both pumps stop
deadband2
e.g. 3.25 m