This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2)
Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3)
Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
•
•
•
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Side
A
Side
B
JAPANESE
ENGLISH
JY997D14901G
Side
B
Note: This symbol mark is for China only.
含有有害6物质的名称,含有量,含有部品
本产品中所含有的有害6物质的名称,含有量,含有部品如下表
所示。
产品中有害物质的名称及含量
本表格依据SJ/T 11364的规定编制。
○
:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
规定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴
二苯醚
(PBDE)
可编程
控制器
外壳
印刷基板
○○
○○ ○ ○ ○
○○ ○ ○
×
「电器电子产品有害物质限制使用标识要求」的表示方式
基于中国标准法的参考规格:GB/T15969.2
Safety Precautions (Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and .
Depending on the circumstances, procedures indicated by may also
cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
How to obtain manuals
For product manuals or documents, consult with the Mitsubishi Electric dealer
from who you purchased your product.
Certification of UL, cUL standards
The following product has UL and cUL certification.
UL, cUL File Number:E95239
Models: MELSEC FX3UC series manufactured
FX3UC-4AD
Compliance with EC directive (CE Marking)
This note does not guarantee that an entire mechanical module produced in
accordance with the contents of this note will comply with the following standards.
Compliance to EMC directive and LVD directive for the entire mechanical module
should be checked by the user / manufacturer. For more details please contact the
local Mitsubishi Electric sales site.
Requirement for Compliance with EMC directive
The following products have shown compliance through direct testing (of the
identified standards below) and design analysis (through the creation of a
technical construction file) to the European Directive for Electromagnetic
Compatibility (2014/30/EU) when used as directed by the appropriate
documentation.
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury or
physical damage.
Manual name Manual No. Description
FX3S/FX3G/FX3GC/FX3U/
FX3UC Series
User's Manual
- Analog Control Edition
JY997D16701
MODEL CODE:
09R619
Describes specifications for
analog control and programming
method for FX3S/FX3G/FX3GC/
FX3U/FX3UC Series PLC.
FX3S/FX3G/FX3GC/FX3U/
FX3UC Series
Programming Manual
- Basic & Applied
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming for
basic/applied instructions and
devices.
FX3UC Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains the FX3UC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
Attention
This product is designed for use in industrial applications.
Type: Programmable Controller (Open Type Equipment)
Models: MELSEC FX3UC series manufactured
from October 1st, 2007 FX3UC-4AD
Caution for EC Directive
The FX3UC-4AD have been found to be compliant to the European standards in
the aforesaid manual and directive. However, for the very best performance
from what are in fact delicate measuring and controlled output device Mitsubishi
Electric would like to make the following points;
As analog devices are sensitive by nature, their use should be considered care-
fully. For users of proprietary cables (integral with sensors or actuators), these
users should follow those manufacturers installation requirements.
Mitsubishi Electric recommend that shielded cables should be used. If NO other
EMC protection is provided, then users may experience temporary loss or
accuracy between ±10% in very heavy industrial areas.
However, Mitsubishi Electric suggest that if adequate EMC precautions are fol-
lowed for the users complete control system, users should expect accuracy as
specified in this manual.
•Sensitive analog cable should not be laid in the same trunking or cable
conduit as high voltage cabling. Where possible users should run analog
cables separately.
•Good cable shielding should be used. Ground the shield of the twisted
shielded cable at one point on the PLC side.
•When reading analog values, EMC accuracy can be improved out by
averaging the readings. This can be achieved either through functions on the
special function block for analog input or through a users program in the
FX3UC Series PLC main unit.
•Please use FX3UC-4AD while installed in a shielded enclosure. For the
details, refer to the following manual.
→ Refer to the FX3UC Series User's Manual - Hardware Edition
Note for compliance with EN61131-2:2007
General note on the use of the power supply cable.
The FX3UC-4AD unit requires that the cable used for power supply is 30m or less.
1. Outline
The FX3UC-4AD special function block (hereinafter called 4AD) for analog input
converts four analog input values (voltage, current) to digital values and transfers those
digital values to the PLC main unit. For the purpose of this manual the FX3UC-4AD will
from here be referred to as the 4AD.
2. Incorporated Items
Verify that the following product and items are included in the package:
Standard Remark
EN61131-2:2007
Programmable controllers
- Equipment requirements and
tests
Compliance with all relevant aspects of the
standard.
EMI
• Radiated Emission
• Conducted Emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field
Product FX3UC-4AD special function block for analog input
Accessories
•Special unit/block No. label
•FX2NC-10BPCB1 (Power crossover cable)
•Installation manual (This manual)
3. External Dimensions, Part Names, and Terminal Layout
[1]
Status indicator LED
- PW (Green): Lit while 5 V power is normally supplied from PLC.
- 24V (Red): Lit while 24V power is normally supplied from power supply.
- A/D (Red): Flashes during A/D conversion.
[2]
Terminal block (European type)
Wiring of the voltage and current input
[3]
Connector (PLC side)
Used to fix extension block on right side.
[4] DIN rail mounting hook
[5]
Slide lock
Used to connect the FX
3UC
main unit extension block.
[6]
Connector (Extension side)
Used to connect extension block on right side of this special block.
Remove this cover for connecting.
[7]
Power connector (24V DC)
The connector for supplying 24V power supply to 4AD.
[8]
Power crossover connector
Used to supply power supply to the extension block.
4. Installation
The 4AD can be installed on a DIN46277 rail (35 mm (1.38") wide).
Up to 8 units
*1
can be connected to the FX
3UC
Series PLC.
*1 Up to 7 units can be connected to the FX3UC-32MT-LT(-2) PLC.
INSTALLATION
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before attempting
installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
INSTALLATION
PRECAUTIONS
•Use screwdrivers carefully when performing installation work, thus avoiding accident
or product damage.
•Use the product within the generic environment specifications described in PLC main
unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive dusts,
corrosive gas (salt air, Cl2, H2S, SO2or NO2), flammable gas, vibration or impacts, or
expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•When drilling screw holes or wiring, make sure that cutting and wiring debris do
not enter the ventilation slits of the PLC.
Failure to do so may cause fire, equipment failures or malfunctions.
•Connect FX3UC-4AD securely to their designated connectors.
Loose connections may cause malfunctions.
PW
24V
A/D
V1+
I1+
COM1
SLD
V2+
I2+
COM2
SLD
V3+
I3+
COM3
SLD
V4+
I4+
COM4
SLD
90(3.55")
20.2
(0.8")
74(2.92")
15
(0.6")
[2]
[1]
[3]
[4]
[5]
[6]
FX
3UC
-4AD
[7]
[8]
Mass (Weight) : Approx.130g (0.29lbs)
Unit: mm (inches)
SLD
V2+
I2+
V3+
V1+
I1+
COM2
SLD
COM3
SLD
V4+
I3+
COM1
I4+
COM4
SLD
Terminal layout
4.1 Connection to the PLC
1)
Turn off the power.
Disconnect all the cables connected to the PLC, and demount the PLC from
the DIN rail.
2) Remove the extension block connector cover on
the main unit / extension block.
3) Slide the special block slide lock of the main unit
/ extension block.
4) The 4AD connector (PLC side) is connected to
the main unit / extension block connector whose
cover was previously removed.
(see the following figure.)
5) Slide back the slide lock of the main unit / exten-
sion block to attach the 4AD.
4.2 Installation In Enclosure
1) Push out all DIN rail mounting hooks.
2) Fit the upper edge of the DIN
rail mounting groove onto the
DIN rail.
DIN46277 rail (35 mm (1.38")
wide)
3) Lock the DIN rail mounting
hooks while pressing the PLC
against the DIN rail.
For installation/uninstallation, Refer to the FX3UC Series User's Manual -
Hardware Edition.
5. Wiring (Power supply and analog input)
WIRING
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
hook
hook
Main unit
FX
3UC
-4AD
5.1 Wire and Terminal Tightening Torque
5.1.1 Cable
1) Applicable cable
2) Termination
Strip the coating of strand wire and twist the cable core before connecting it,
or strip the coating of single wire before connecting it. An alternative
connection is to use a ferrule with insulating sleeve.
*1 Old model name : CRIMPFOX ZA 3
*2 Old model name : CRIMPFOX UD 6
•Stranded wire/solid wire •Ferrule with insulation sleeve
When using a ferrule with insulation sleeve, choose a wire with proper cable
sheath referring to the above outside dimensions, otherwise the wire cannot
be inserted easily.
5.1.2 Tightening Torque
Tightening torque should be between 0.22 and 0.25 N•m.
Do not tighten terminal screws with a torque outside the abovementioned range.
Failure to do so may cause equipment failures or malfunctions.
5.2 Tool
To tighten terminals, use a purchased small-
sized screwdriver whose head is straight and
is not widened as shown in the right figure.
Note:
If the diameter of screwdriver grip is too
small, tightening torque will not be able to
be achieved. To achieve the appropriate
tightening torque shown in the table above, use the following screwdriver or an
appropriate replacement (grip diameter: approximately 25mm (0.98")).
<Reference>
5.3 Power supply wiring
Supply the 24V DC power to 4AD via the power supply connector.
WIRING
PRECAUTIONS
•Make sure to observe the following precautions in order to prevent
malfunctions under the influence of noise:
1) Do not bundle the power line or twisted shielded cable together with or lay
it close to the main circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line 100mm (3.94") or more away
from the main circuit, high-voltage lines, or load line.
2) Ground the twisted shield cable at one point on the PLC. However, do not
use common grounding with heavy electrical systems.
•Make sure to properly wire to the European terminal board in accordance
with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described
in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
Wire size
Single wire 0.3 to 0.5mm2 (AWG22 to 20)
Double wire 0.3mm2 (AWG22)*2
Ferrule with
insulation sleeve
0.3 to 0.5 mm2(AWG22 to 20)
(Refer to the external view of ferrule shown in the
following figure.)
Manufacturer Model Pressure bonding tool
PHOENIX CONTACT
GmbH & Co. KG AI 0.5-8WH CRIMPFOX 6*1
(or CRIMPFOX 6T-F*2)
Manufacturer Model
PHOENIX CONTACT GmbH & Co. KG SZS 0.4×2.5
Model Application
FX2NC-10BPCB1 Power crossover cable(offered as an accessory for the
FX3UC-4AD)
FX2NC-100BPCB Power cable(offered as an accessory for the FX3UC Series
main unit)
9mm
(0.36")
Termination of
cable end
8mm
(0.32")
Contact area
(Crimp area)
14mm(0.56")
2.6mm
(0.11")
Insulation sleeve
0.4mm
(0.02")
2.5mm
(0.1")
With
straight tip
1) Connection example with the power supply through crossover wiring to the
FX2NC input extension block
2) Connection example to the external power supply.
•Ground the " " terminal to the Class-D grounding line (100 Ωor less) together
with the ground terminal of the main unit.
•Remove the resin cover from the power crossover connector and perform crossover
wiring to connect the power line from 4AD to a succeeding extension block.
5.4 Wiring of Analog Input
For the terminal layout, refer to Chapter 3
*1 Use the 2-core shielded twisted pair cable for the analog input lines, and
separate the analog input lines from the other motive power lines or inductive
lines.
*2 To use the current input, be sure to short circuit the line between the V+
terminal and the I+ terminal (: channel number).
*3 The SLD and " " terminals are connected to each other inside.
*4 Do not connect any lines to the "•" terminal.
6. Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
•Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
•Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
24V
DC Class-D grounding
Terminal
block
FX
3UC
-4AD
GreenRed
Black
FX
3UC Series PLC
[Main unit]
Power connector
24+24- 24+24-
Power
connector
Power
crossover
connector
Red
Black
FX
2NC
Series PLC
(Input extension block)
+15V
24+24- 24+24-
-15V
Black Red
Power
connector
FX
2NC
-10BPCB1
Power crossover cable
FX
2NC
-100BPCB
Power cable
Terminal
block
FX
3UC
-4AD
+15V
24+24-
-15V
Black Red
Power
connector
24V
DC Class-D grounding
GreenRed
Black
FX
3UC
Series PLC
[Main unit]
Power connector
24+24-
FX
2NC
-100BPCB
Power cable
250Ω
6.8kΩch
FX
3UC
-4AD
200kΩ
250Ω
6.8kΩ
200kΩ
V+
COM
I+
V+
COM
I+
*2
*1 shield
If current input is
selected
If voltage input is
selected
Terminal
block
SLD
SLD
·
*4
*3
ch
V+, I+, ch: represents
the channel number.
6.1 Applicable PLC
6.2 General Specifications
The general specifications are equivalent to the PLC main unit.
(For general specifications, refer to the manual of the PLC main unit.)
6.3 Power Supply Specifications
6.4 Performance Specifications
*1 Change the offset and gain values to change the input characteristics. However,
the resolution doesn’t change even when the offset and gain values change.
In the direct indication mode, however, the offset/gain cannot be adjusted.
*2 The offset and the gain should satisfy the following condition:
1V ≤(Gain - Offset) ≤7.5V
*3 The offset and the gain should satisfy the following condition:
3mA ≤(Gain - Offset) ≤30mA
*4 The resolution depend on the input mode.
6.5 Input characteristics
For the 4AD, the nine kinds of input characteristics are provided for each input mode.
For the details of the input character, refer to the following.
TRANSPORTATION AND
STORAGE PRECAUTIONS
•The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product.
After transportation, verify operation of the product and check for damage of the
mounting part, etc.
Applicable PLC
FX3UC Series PLC (Ver.1.30 or later)
From the production manufactured in August, 2004 with SER
No.48****
Item Specifications
A/D conversion
circuit driving
power
24V DC ±10%, 80mA
(24V DC power is supplied from the power connector.)
Interface driving
power
5V DC, 100mA
(5V DC power is supplied from the internal power supply of main
unit, it is not necessary to prepare power supply)
Item Specifications
Voltage input Current input
Analog input
range
-10 to +10V DC
(Input resistance: 200 kΩ)
-20 to +20mA, 4 to 20mA DC
(Input resistance: 250 Ω)
Offset*1 -10 to +9V*2 -20 to +17mA*3
Gain*1 -9 to +10V*2 -17 to +30mA*3
Maximum
absolute input ±15V ±30mA
Digital output Effective numeric value
15bits + Sign 1bit
Effective numeric value
14bits + Sign 1bit
Resolution*4 0.32mV (20V×1/64000)
2.50mV (20V×1/8000)
1.25mA (40mA×1/32000)
5.00µA (40mA×1/8000)
Total accuracy
•±0.3% (±60mV) for full scale
of 20V (when ambient
temperature is 25°C±5°C)
•±0.5% (±100mV) for full
scale of 20V (when ambient
temperature is 0°C to 55°C)
•±0.5% (±200µA) for full scale
of 40mA (when ambient
temperature is 25°C±5°C
and a current of -20mA to
+20mA is input)
Same when input is 4mA to
20mA
•±1.0% (±400µA) for full scale
of 40mA (when ambient
temperature is 25°C±5°C
and a current of -20mA to
+20mA is input)
Same when input is 4mA to
20mA
A/D conversion
time
500µs × number of selected channels
(If channels use the digital filter(s): 5ms × number of selected
channels)
Insulation
method
•The photo-coupler insulates the analog input area from the
PLC.
•The DC-DC converter insulates the analog input area from the
power supply unit.
•Channels are not insulated from each other.
Occupied points 8 point (Count either the input or output points of the PLC.)
Input mode
Set value Input mode Analog
input range
Digital output
range Resolution
0 Voltage input mode -10 to +10V -32000 to
+32000 0.32mV
1 Voltage input mode -10 to +10V -4000 to +4000 2.50mV
Input
mode
Set value
Input mode Analog
input range
Digital output
range
Resolu-
tion
2
Voltage input mode
Analog value direct
indication
-10 to +10V -10000 to
+10000 1.00mV
3 Current input mode 4 to 20mA 0 to 16000 1.25µA
4 Current input mode 4 to 20mA 0 to 4000 5.00µA
5
Current input mode
Analog value direct
indication
4 to 20mA 4000 to 20000 1.25µA
6 Current input mode -20 to
+20mA
-16000 to
+16000 1.25µA
7 Current input mode -20 to
+20mA -4000 to +4000 5.00µA
8
Current input mode
Analog value direct
indication
-20 to
+20mA
-20000 to
+20000 1.25µA
9 to E Not used.
F No channels used
FX3UC-4AD
INSTALLATION MANUAL
This manual describes the part names, dimensions, mounting, and specifications
of the product. Before use, read this manual and the manuals of all relevant
products fully to acquire proficiency in handling and operating the product. Make
sure to learn all the product information, safety information, and precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
The company and product names described in this manual are registered
trademarks or the trademarks of their respective companies.
Effective March 2018
Specifications are subject to change without notice.
©2004 MITSUBISHI ELECTRIC CORPORATION
Manual Number JY997D14901
Revision G
Date March 2018