Flow temp. controller
C-17
Electrical work (FTC2) Flow temp. controller
3
C-17
3.4. Connecting thermistor cable
Connect the thermistor 2for the FTC2 controller.
3.4.1. Connecting the actual flow water temp. thermistor (TH1)
Connect the thermistor for the actual flow water temp. to 1 and 2 on
the terminal block (TB61) on the FTC2 controller.
When the thermistor cables are too long, cut them at the
appropriate length.
Do not bind them in the FTC2 unit.
<Thermistor position>
Put TH1 on water piping (water outlet side) after booster heater.
Note: Be sure to attach the TH1 where it detects Flow
temp.(Water oulet side) correctly.
3.4.2. Connecting the pipe temp. thermistor (TH2)
Connect the thermistor for the refrigerant pipe temp. to 3 and 4 on
the terminal block (TB61) on the FTC2 controller.
For packaged Outdoor unit : It is NOT necessary to connect TH2.
For split Outdoor unit : Connect TH2.
When the thermistor cables supplied with FTC2 are too long, cut
them to the appropriate length.
Do not bind them in the FTC2 unit.
<Thermistor position>
Put the TH2 on refrigerant piping (Liquid side).
It is better to protect the thermistor with heat insulating materials not to be affected by the ambient temperature.
Note: Be sure to attach the TH2 where it detects Refrigerant piping temp. (Liquid side) correctly.
3.4.3. Connecting the actual DHW tank thermistor (TH5)
Connect the thermistor for the actual DHW tank temp. to 5 and 6 on the terminal block (TB61) on the FTC2 controller.
When the thermistor cables supplied with the FTC2 are too long, cut them to the appropriate length.
Do not bind them in the FTC2 unit.
<Thermistor position>
Put the TH5 on the DHW tank. It should be positioned directly onto the lower half of the external surface of the tank.
Caution:
Do not route the thermistor cables together with power cables.
The sensor part of the thermistor should be installed where user must not touch.
(It is separated by the supplementary insulation from where user may touch.)
3.4.4. Thermistor position and necessity
For packaged type Outdoor unit: It is NOT necessary to connect TH2.
For split type Outdoor unit: Connect TH2
<Thermistor position and necessity>
Outdoor Type DHW tank TH1 TH2 TH5
PACKAGED type Present ΟХΟ
Absent ΟХХ
SPLIT type Present O O O
Absent ΟΟХ
Ο: Necessary. Connect the thermistor. Х: Not necessary. The thermistor is not required, do not connect.
Photo.3-3
TB61
TH1
TH2
TB62
Wired remote controller cable
TH5
SPLIT type outdoor unit without DHW tank
Outdoor unit
*1 Water piping
TH1
Booster heater
Water OUTLET
side
TH2
TH5
TH5:
not necessary
SPLIT type
(without a refrigerant-water HEX inside)
Refrigerant LIQUID side
Refrigerant piping
FTC2
*1 Refrigerant-water HEX
PACKAGED type outdoor unit without DHW tank
Outdoor unit
*1 Water piping
TH1
Booster heater
Water OUTLETside
after Booster heater FTC2
TH2 TH5
TH2:
not necessary
TH5:
not necessary
PACKAGED type
(with a refrigerant-water HEX inside) *1 Refrigerant-water HEX
SPLIT type outdoor unit with DHW tank
Outdoor unit
*1 Water piping
TH1
Booster heater
Water OUTLET
side
TH2
SPLIT type
(without a refrigerant-water HEX inside)
Refrigerant LIQUID side
Refrigerant piping
FTC2
TH5
DHW tank
temperature
*1 Refrigerant-water HEX
PACKAGED type outdoor unit with DHW tank
Outdoor unit
*1 Water piping
TH1
Booster heater
Water OUTLETside
after Booster heater FTC2
TH2
TH5
TH2:
not necessary
PACKAGED type
(with a refrigerant-water HEX inside)
DHW tank
temperature
*1 Refrigerant-water HEX