-2- -3-
30 mm
Make sure to install Air conducting fan securely and on the level in any case.
Note
- At least, 100 mm must be
provided for the air inlet
opening. Otherwise, the
unit will not provide
sufficient blowing
performance.
- When multiple units are
installed side by side, at
least 100 mm clearance is
necessary between the
neighboring mounting
plates.
- For ceiling-suspension, be
sure to reinforce the
anchor bolts with vibration-
isolation parts.
External Dimensions
Installation
Table of dimension changes Unit (mm)
Model A B C D
AH-1006S1-E 552 668 624 3
AH-1509S1-E 900 1016 972 5
AH-2009S1-E 900 1016 972 5
AH-3012S1-E 1194 1310 1266 6
Mounting examples
Electrical Work
Mounting the Unit
1. According to the “External dimensions”, select
firm foundation and install commercially available
anchor bolts (M8 or M10). (Refer to the figures.)
2. When adjusting the mounting angle, first, remove
the angle adjustment bolts to unclamp the unit
from the mounting plate, and then, loosen the
self-locking nuts.
After adjustment is completed, fasten nuts and
bolts securely again.
3. To clamp the mounting plate, get the installed
anchor bolts (hook bolts) through the holes in the
mounting plate and firmly secure them using
commercially available washers and nuts.
-
Electrical work shall be performed by qualified
persons accordance with national wiring regulations.
-
The cable size must be at least 0.75 mm2for power
cable. When operating multiple units, connect the
power using a cable with a capacity corresponding
to the total current value of the units installed.
-
When selecting a motor circuit isolator, use a value of
1.2 to 1.5 as the safety factor for the maximum load
current listed in the specifications as a rule of thumb.
- Make sure to ground and install an all-pole electric
leakage isolator.
1. Remove the three screws securing the terminal
cover and installed bushing.
2. Set a cable gland on the hole of terminal cover.
Opening dia. is 21 mm.
3. After pass the power supply cable though the
cable gland, connect to the terminal block and
grounding terminal securely. Peel 10 mm of the
cable end for the connection.
4. Reinstall the terminal cover as it has been before
and securely fasten the cable gland.
CAUTION
Do not pinch the cable between the cover and
the body.
Wire Connection
Thick and dotted lines are eld work.
When “High-Low” operation is selected:
When “High” or “Low” operation is xed:
Cable gland
(commercially
available)
CHi Lo
98A
Terminal block
N
L
FANS
COM
Low
High
FANS
COM
Low
High
FANS
COM
Low
High
ON/OFF
ON/OFF
Terminal
block
Terminal
block
Terminal
block
Second
unit
HIGH/LOWON/OFF
Control Switch
(commercially
available)
Switch
(commercially available)
Switch
(commercially available)
“High”
operation
“Low”
operation
Power supply
220-240 V~ 50 Hz
220 V~ 60 Hz
A
66
B
C
115
77
130
256
197
153
190
222
58
136
12
100
7
Angle
adjustment bolt
φ21 for cable gland
D (No. of fans)
CAUTION
Incorrect handling could cause injury or
damage to property or household effects.
Do not hang from the unit.
Otherwise it may result in injury or malfunction.
When adjusting the mounting angle, do not remove
the self-locking nut at the center.
It may fall, resulting in injury.
Never use the unit in a bathroom or other location
with excessive moisture (more than 90% RH).
Never use the unit where it may be exposed to rain.
Otherwise, it may result in electrical shock or re.
Select a place with rigid structural strength and
install the unit securely.
Make sure to install every part securely.
Always use the specied anchor bolts, nuts and washers.
Otherwise, it may result in fall or injury.
Wiring work must be performed by qualied persons
in accordance with national wiring regulations.
Poor connection or improper wiring work could cause electric shock or re.
For installation and maintenance work, wear gloves.
Otherwise, it may result in injury.
If the fans get dirty, clean off the dirt of them.
Parts may fall due to the vibration, which could cause injury.
Do not use the unit when any abnormal vibration
has been detected on the unit.
There are risks of injury by falling the unit or parts.
Make sure to turn off the circuit isolator when
suspending use for a long time.
It could cause electrical shocks or re by fault current resulting
from deteriorated insulation.
This appliance can be used by children aged from
8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of
experience and knowledge if they have been given
supervision or instruction concerning use of the
appliance in a safe way and understand the hazards
involved. Children shall not play with the appliance.
Cleaning and user maintenance shall not be made
by children without supervision.
* The mounting angle of the unit is selectable
from the following 19 angles to the mounting
surface:
-22.5°, -11.3°, 0°, 11.3°, 22.5°, 33.8°, 45°,
56.3°, 67.5°, 78.8°, 90°, 101.3°, 112.5°, 123.8°,
135°, 146.3°, 157.5°, 168.8°, 180°
* When it is mounted directly on the ceiling,
-22.5° is not allowed.
* Mount the unit with the mounting plates facing
outside. If there is an obstacle preventing to
do so, use the mounting plates facing inside.
In such cases, interchange the left and right
mounting plates.
Ceiling surface-mounting Ceiling-suspension Wall mounting
* Selectable angle range: -11.3 to
180°
* To use -22.5°, provide 15 mm or
greater between the mounting
surface and the mounting plate.
* If 900 mm or greater, anti
vibration is necessary.
* If 900 mm or greater, anti
vibration is necessary.
Horizontal air direction Vertical air direction
Unit
Unit
Unit
Unit
Unit
Unit
900 mm
or less*
900 mm or
less*
100
mm or
more
100 mm or
more
100 mm or more
Mounting
plate
Mounting
plate
Mounting plate
Mounting plate
Mounting
plate
Mounting plate
Direct mounting
* The gure shows ceiling surface-mounting.
Ceiling-suspension
Adjusting the Mounting Angle
The wind direction is selectable using 19-angle
adjustment.
1. When adjusting the angle after installation of the
unit, remove the angle adjustment bolts, and then,
loosen the self-locking nuts.
2. After adjusting the angle, reinstall the angle
adjustment bolts, tighten them, and rmly secure
with the self-locking nuts.
CAUTION
When adjusting the mounting angle, do not
remove the self-locking nut at the center.
It may fall, resulting in injury.
Mounting plate
Anchor bolt
(commercially available) Washer
(commercially available)
Nut x 2
(commercially available)
Unit
Mounting plate
Hook bolt
(commercially available)
Washer
(commercially available)
Nut x 2
(commercially available)
Nut
(commercially available)
Unit
Mounting plate
Angle adjustment bolt
Unit
Self-locking nut
Terminal cover
Details of
mounting plate
Trial Operation
After completing installation, check that every wire is connected properly, the unit operates properly, and the
unit is installed securely and does not produce vibration or abnormal noises. When a resonance is found,
introduce some measures to avoid the resonance point.
If any trouble is found, it must be immediately corrected. Explain correct operation to the user (customer).