[MODE] Blank (Not specified), AUTO, COOL, DRY, FAN, HEAT, SEASON page 25
* As selectable items vary according to the current settings, refer to the User’s Manual
of the SL4 central control.
[SET TEMP.] By default, the temperature can be set in the range of 18 deg C to 30 deg C in
increments of 0.5 deg C. When an operating mode is selected, the range is extended
to the upper and lower limits of the selected mode.
(In the SL4 central control, Fahrenheit and Celsius can be switched, and the upper and
lower limits of the set temperature can be extended. Refer to the User’s Manual of the
SL4 central control.)
[ENERGY SAVING] Blank (Not specified), ON, OFF page 9
[SILENT] Blank (Not specified), ON, OFF
* Priority is given to the silence of the outdoor unit. This function cannot be applied to
some indoor units.
<For HMU group ( page 32)>
[RUN/STOP] Blank (Not specified), RUN, STOP
[LOCK] Blank (Not specified), ALL LOCK, ALL UNLOCK, RUN/STOP, MODE, SET TEMP.,
RUN/STOP & MODE, RUN/STOP & SET TEMP., MODE & SET TEMP.
* As selectable items vary according to the current settings, refer to the User’s Manual
of the SL4 central control.
[MODE] Blank (Not specified), AUTO, COOL, PUMP, HEAT, SEASON page 25
* As selectable items vary according to the current settings, refer to the User’s Manual
of the SL4 central control.
[SET TEMP.]
By default, the temperature (Outlet water temperature) can be set in the range of
15 deg C to 30 deg C in increments of 0.5 deg C. When an operating mode is selected,
the range is extended to the upper and lower limits of the selected mode.
(In the SL4 central control, Fahrenheit and Celsius can be switched, and the upper and
lower limits of the set temperature can be extended. Refer to the User’s Manual of the
SL4 central control.)
[ENERGY SAVING] Blank (Not specified), ON, OFF page 11
[SET TEMP. 2] The temperature (Inlet water temperature or Remote control temperature) can be set
in the range of 5 deg C to 55 deg C in increments of 0.5 deg C.
<For Q-ton group ( page 32)>
Note
• Set the items depend on the application.
• Set storage hot water temperature (HW TEMP.) higher than keep warm temperature by 5°C or more.
Ex.) When keep warm temperature is 60°C, set storage hot water temperature higher than 65°C.
[HW TEMP.] By default, the temperature can be set in the range of 60 deg C to 90 deg C in
increments of 1 deg C.
(In the SL4 central control, Fahrenheit and Celsius can be switched, and the
upper limits of the temperature can be changed. Refer to the User’s Manual of
the SL4 central control.)
[SET HW AMOUNT] Hot water storage amount can be set in the range of 10 % to 100 % in
increments of 10 %.
[ANTI-LEGIONELLA] Click the ON or OFF button.
[PEAK-CUT] The [Peak-cut %] can be set at 0%, 40%, 60% and 80%.
To cancel, click 100%.
[SILENT] Click the ON or OFF button.