Monicon GTR-85 User manual

GTR-85
Generator Controller
Owner’s Manual
TEL:886-4-2422-2598
FAX:886-4-2422-2491
Web Site:http://www.monicon.com.tw
E-mail:[email protected]
1

Table of contents
1 Introduction......................................................................................................................... 1
1.1 GTR-85 Panel.......................................................................................................... 1
1.1.1 Indicators....................................................................................................... 1
1.1.2 Rotary Switch Function ................................................................................. 1
1.1.3 Push-Button Function.................................................................................... 1
1.2 Wire Terminal........................................................................................................... 2
1.3 CASE DIMENSIONS ............................................................................................... 4
1.4 Specifications........................................................................................................... 4
1.4.1 General ......................................................................................................... 4
1.4.2 Controller Function........................................................................................ 4
1.4.3 Network function: .......................................................................................... 5
1.4.4 Panel function: .............................................................................................. 5
1.4.5 Protection function: ....................................................................................... 5
1.5 Wiring....................................................................................................................... 5
1.5.1 Wiring example ............................................................................................. 5
1.5.2 Connection in short distance......................................................................... 6
1.5.3 Connection with modem................................................................................ 6
1.5.4 Inside fuse and protecting value.................................................................... 6
1.5.5 Group connection.......................................................................................... 6
2 Communication protocol for user monitoring...................................................................... 7
2.1 Communication Interface......................................................................................... 7
2.1.1 Connect with GTR85 via RS-485 interface.................................................... 7
2.1.2 Transmit information via MTR-1.................................................................... 8
2.1.3 C8 command description............................................................................... 9
2.1.4 Example for AC line voltage, phase voltage, and current readout................11
3 Software manual............................................................................................................... 15
3.1 GTR85 software installation................................................................................... 15
3.2 GTR85 software description................................................................................... 16
3.2.1 Button.......................................................................................................... 16
3.3 Parameters description.......................................................................................... 18
3.3.1 ATS page .................................................................................................... 18
3.3.2 System page ............................................................................................... 25
3.3.3 Input page................................................................................................... 28
3.3.4 Output page ................................................................................................ 30
3.3.5 Misc. page……………………………………………………………...30
i

1 Introduction
1.1 GTR-85 Panel
1.1.1 Indicators
Power
Run
Stop
Trip
Alarm
Over Crank
High Water Temp.
Over Speed
Low Oil Pressure
1.1.2 Rotary
Switch
Function
Network
Allow online authorized user entry to perform
monitoring and control.
ATS
The engine starts automatically, when shorted
ATS1 and ATS2 terminal behind the controller
under ATS mode.
Manual
User starts the engine directly.
Off
Shutdown the engine or forbid start function.
1.1.3 Push-Butt
on Function
PAGE
Change LCD display page for reading more
information.
Light Test
Test lights for solid, clear and brightness. It also tests
alarm.
Reset
1. First time “Reset” shutdown the alarm.
Second time “Reset” clears fault lights.
2. Holding down for a longer period will produce
1st and 2nd time “Reset” functions.
3. Turn on the LCD backlight.
Figure 1 – GTR85 Panel
1

1.2 Wire Terminal
Figure 2 – GTR82 wire terminal
Table 1 – GTR82 back description
Continental terminal description
Symbol Description Symbol Description
1 ++ DC power (Battery +) 21 R Analog input, R phase volt
2 GND Ground (Battery -) 22 S Analog input, S phase volt
3 Motor Output, starter relay 23 T Analog input, T phase volt
4 Valve Output, fuel valve relay 24 N Analog input, N phase volt
5 Output 3 Output, Aux 3 relay 25 R.CT. L Analog input, R line current (L)
6 Output 2 Output, Aux 2 relay 26 R.CT. S Analog input, R line current (S)
7 Alarm Output, alarm relay 27 S.CT. L Analog input, S line current (L)
8 Trip 1 Output, electrical trip relay 28 S.CT. S Analog input, S line current (S)
9 Trip 2 Output, electrical trip relay 29 T.CT. L Analog input, T line current (L)
10 Input 2 Digital input,Aux 2 switch 30 T.CT. S Analog input, T line current (S)
11 Input 0 Digital input,Aux 0 switch 31 F.L. Sen. Analog input, Fuel level sensor
(option)
12 Input 3 Digital input,Aux 3 switch 32 W.T. Sen. Analog input, Water temp.
sensor
13 L.O.P. Digital input, Low oil press.
switch 33 O.P. Sen. Analog input, Oil pressure
sensor
14 H.W.T. Digital input, High water temp.
switch 34 Spare Spare
15 ALT. Digital input,Alternator plus 35 Spare Spare
16 Input 1 Digital input,Aux 1 switch 36 Spare Spare
17 ATS 1 Digital input, shorted with ATS2 37 Output
0_2 Output, Aux. 0 relay
18 ATS 2 Digital input, shorted with ATS1 38 Output
0_1 Output, Aux. 0 relay
19 F.D. 1 Analog input, Frequency detect
terminal 39 Output
1_2 Output, Aux. 1 relay
20 F.D. 2 Analog input, Frequency detect
terminal 40 Output
1_1 Output, Aux. 1 relay
VARIABLE REGISTER DESCRITOPN
Symbol Description Symbol Description
AC voltage calibration Oil Pressure calibration
AC Ampere calibration Fuel Level calibration
Water Temp. calibration
DC POWER STATUS DESCRIPTION
Symbol Description
2

OK: Solid “green” LED
DC power polarity fault
RS-485 COMMUNICATION PORT
Symbol Description
1. Battery +
2. A
3. B
4. GND
Note:
1. Output Relay function can be changed according users requirements.
2. Output Trip Relay is intended to be used to trip the Breaker or AVR filed current in order to cut off load to
the generator.
3. VRs are adjustment for matching tolerance between external and internal measuring meter readout.
3

1.3 CASE DIMENSIONS
Figure 3 – GTR85 side view
Figure 4 – GTR85 back view
1.4 Specifications
1.4.1 General
DC Supply:
8 ~ 36 VDC
Power Consumption:
Max. 10 W
Measuring Voltage:
10 ~ 300 VAC (Phase to Neutral, Accuracy 1.5 %)
Measuring Current:
../5 A (secondary current readout below 0.15 A
shows zero on LCD display. Accuracy 1.5 %)
Measuring Frequency:
0 ~ 80 Hz (Min AC Volt: 8 V)
Charger AC Output Voltage Sensitivity:
3 V ~ 70 V Peak to Peak
Charger AC Output Frequency Sensitivity:
62 Hz ~ 10,000 Hz
Relay Output:
10 A /30 VDC
Operating system:
Windows 98, Windows ME, Windows 2000,
Windows XP (recommend)
Communication Protocol:
RS-485 (Dynamic encryption by Monicon technology)
Operating Temperature Range:
-10 ℃~ +60 ℃
Dimension (W x H x D):
144 mm x 144 mm x 74 mm
Panel Cut-out (W x H):
138 mm x 138 mm
Weight:
1.4 Kg (3.08 lb.)
1.4.2 Controller Function
LCD display:
1. Three phase-phase voltage
2. Three line current
3. Three phase-neutral voltage
4. Frequency
5. RPM
6. Battery Voltage
7. Run hours
8. Coolant Temperature
9. Oil Pressure
10.PF
11.KW
12.KWH
13.KVAR
4

14.KVA
1.4.3 Network function:
Remote start/stop the controller by two wires
network circuitry
Parameter setting and reading
Input and output monitor
Fault history readout
Data acquisition can be done from a remote
site
1.4.4 Panel function:
Manual start / stop engine.
Automatically start / stop engine by ATS.
Reset the controller.
Light test.
1.4.5 Protection function:
Engine respect:
1. Over crank protection
2. Low oil pressure protection
3. High water temperature protection
4. Low water level protection
5. Over speed protection
Generator respect:
1. Over load protection
2. Short circuit protection
3. Over voltage protection
4. Under voltage protection
5. High frequency protection
6. Low frequency protection
Battery respect:
1. Low battery indicator/ alarm
2. High battery indicator/ alarm
3. Charge failure indicator
4. Start prohibit on weak battery power
Peripheral respect:
1. Lower fuel level protection
2. Aux. 2
3. Aux. 3
1.5 Wiring
1.5.1 Wiring example
Figure 5 – GTR85 wiring diagram
5

1.5.2 Connection in short distance
Figure 6 – GTR85 local connection diagram
1.5.3 Connection with modem
Figure 7 – GTR85 remote connection diagram
1.5.4 Inside fuse and protecting value
Fuse1:100 mA
Fuse2:750 mA
Fuse3:6 A
1.5.5 Group connection
1. Every controller must be have its own identified number to support software recognition. Go to System /
Misc. page, and change its id number.
2. Group wiring:
The MTR-1 terminal pin 1 and pin 4 are the power supplied ports, so just one MTR-1 needs to be
connected with pin 1,2,3,4, and others connect with pin 2, 3 only.
6

Figure 8 – Group connection diagram
Note: It is strong suggestion that using another power source to power the communication card (MTR-1), If
the wire length over 25 meters. This prevents the MTR-1 go in an unpredictable condition by voltage drop.
2 Communication protocol for user monitoring (start)
2.1 Communication Interface
2.1.1 Connect with GTR82 via RS-485 interface
Connection method1
Master device (RS-485) ÙGTR85 as slave device (RS485)
Master device UART configuration
9600 bps, no parity, 9 data bits, 1 stop bits
The leading 8 bits information defines as “Address”, when the 9th bit sets to 1 (or logic high), and it defines as
“Data” when the 9th bit sets to 0 (or logic low).
Information transmitting format
The master device transmitting information form includes three parts that are Address, Command as well as
Data in three bytes.
Address represents the GTR85’s identified number.
Command represents with function group that master device invoke to be executed.
Data represents which exactly command that master device invoke to be executed.
Encryption processing
Each byte of the transmitting information must be encrypted as follow; let’s say FID, the factory ID number, is
7

0x6F.
Data processing Example
Address = Address XOR FID Address = 0x41 XOR 0x6F = 0x2E
Command = Command XOR FID Command = 0xC8 XOR 0x6F = 0xA7
Data = Data XOR FID Data = 0x05 XOR 0x6F = 0x6A
For example, the master device transmits information to GTR85 controller via RS485 should be 0x2E then
0xA7 and then 0x6A as sequence.
Information receiving format
The master device receiving information form includes two parts Echo and Check.
Echo represents the information that GTR85 responds to the master device transmitting information.
Check is used for master device checks the accuracy of the receiving information.
Receiving information processing
Data processing Example
Echo = Echo XOR FID Echo = 0x6F XOR 0x6F = 0x00
Check = Check XOR FID Check = 0x91 XOR 0x6F = 0xFE
The master device receives information from GTR85 controller via RS485 should be 0x00 and then 0xFE.
2.1.2 Transmit information via MTR-1
Connection method 2
Master device (RS-232) ÙMTR-1 as interface (RS232 ÅÆ RS-485) ÙGTR85 controller as slave device
(RS485)
Device port configuration
19200 bps, no parity, 8 data bits, 2 stop bits
Information transmitting format
The master device transmitting information form includes four parts that are Start, Address, Command as
well as Data in seven bytes.
Transmitted information
Format Start Address Command Function
Example | 4 1 C 8 0 5
The start byte, ‘|’ (0x7C in hexadecimal form), is the synchronous character of the MTR-1. The description of
Address, Command and Data are the same as defined in section 2.1.1.
All transmitting information should be transfer from hexadecimal to twoASCII characters, for example, if the
Address is 0x41, then the transmitting data is ‘4’ ‘1’, or 0x34 0x31 in hexadecimal form.
Encryption process
Data processing Example Split into two ASCII characters
Address = Address XOR FID Address = 0x41 XOR 0x6F = 0x2E 2E
Command = Command XOR FID Command = 0xC8 XOR 0x6F = 0xA7 A7
Data = Data XOR FID Data = 0x05 XOR 0x6F = 0x6A 6A
The master device transmits information to GTR85 controller via MTR-1 interface should be ‘|’ ‘2’ ‘E’ ‘A’ ‘7’ ‘6’
‘A’ in character way, or 0x7C 0x32 0x69 0x65 0x67 0x66 0x65 in binary way.
Information receiving format
The format of receiving information form MTR-1 includes four bytes, and is combined with Echo and Check
two parts. The descriptions of Echo and Check are the same as defined in section 2.1.1.
Received information
Format Echo Check
Example 6 F 9 1
8

Receiving information processing
1. Transfer the twoASCII characters of the Echo part into one byte, for example ‘6’ ‘F’ Î0x6F.
2. Transfer the twoASCII characters of the Check part to one byte, for example ‘9’ ‘1’ Î0x91.
3. XOR process, Echo = Echo XOR FID, Check = Check XOR FID.
4. Check the accuracy of the receiving information. The receiving information is correct, only when the value
of the de-encrypted information is equal to 0xFE.
2.1.3 C8 command description
Code Description
00 Controller Type
The readout value represents the type of the
GTR controller. The value 0x80 represents the
controller is GTR80, 0x82 represents the
controller is GTR82, … etc.
01 Current page of LCD
02 R-S voltage low byte
03 S-T voltage low byte
04 T-R voltage low byte
05 R-S voltage high byte
06 S-T voltage high byte
07 T-R voltage high byte
08 Integral of frequency
09 Decimal of frequency
0A R-N voltage
0B S-N voltage
0C T-N voltage
0D Power factor
The value 102 represents that wiring is wrong.
The value 101 represents that Power factor is
lead.
The value between 100 and 55 represents
current power factor, and the power factor is
value / 100.
The value 55 represents power factor under
0.55.
0E Thousands number of the KW
0F Hundreds number of the KW
10 Tens number of the KW
11 Units number of the KW
12 Decimal point of the KW
13 Decimal of the KW
14 Hundred thousands number of the KWH
15 Ten thousands number of the KWH
16 Thousands number of the KWH
17 Hundreds number of the KWH
18 Tens number of the KWH
19 Units number of the KWH
1A
1B RPM high byte calculated from frequency
1C RPM low byte calculated from frequency
1D Battery voltage
The battery voltage is calculated from the
readout value divided 5.
1E
1F Digital output status
Each digit represents an output relay status, 0:
off; 1: on.
Bit 0: Aux. output 0
Bit 1: Aux. output 1
Bit 2: Aux output 2
Bit 3: Trip relay
Bit 4: Alarm output
Bit 5: Aux. output 3
Bit 6: Motor output
Bit 7: Valve output
20
21
22 Indicator status of group A
Each bit represents a light on the penal, 0: off;
1: on.
Bit 0: Run indicator
Bit 1: Stop indicator
Bit 2: Trip indicator
Bit 3: Alarm indicator
Bit 4: Over crank indicator
Bit 5: High water temperature indicator
Bit 6: Over speed indicator
Bit 7: Low oil pressure indicator
23
24
25
26 Second number of run hour
27 Minute number of run hour
28 Hour number of run hour
9

29 100 hour number of run hour
2A R phase current low byte
2B S phase current low byte
2C T phase current low byte
2D R phase current high byte
2E S phase current high byte
2F T phase current high byte
30 Value of coolant temperature
The value 0xFF (255) represents the coolant
temperature sensor is open.
The value 0xFE (254) represents the coolant
temperature is over 120 ℃.
The value 0xFD (253) represents the coolant
temperature is below 40 ℃.
The value 0xFC (252) represents the coolant
temperature sensor is short.
The other value represents current coolant
temperature, for example, the readout value is
0x55 (85) that represents 85 ℃.
31 Value of lubricant pressure
The value 0xFF (255) represents the lubricant
pressure sensor is open.
The value 0xFE (254) represents the lubricant
pressure is over 150 PSI.
The value 0xFD (253) represents the lubricant
pressure is 0 PSI.
The value 0xFC (252) represents the lubricant
pressure sensor is short.
The other value represents current lubricant
pressure, for example, the readout value 0x55
(85) represents 85 PSI.
32 Value of fuel level
The value 0xFF (255) represents the fuel level
sensor is open.
The value 0xFE (254) represents the fuel level
is full.
The value 0xFD (253) represents the fuel level
is empty.
The value 0xFC (252) represents the fuel level
sensor is short.
The other value represent current coolant level,
for example, the readout value is 0x55 (85)
that represents 85 %.
33 Maximum page of LCD
34 Decimal of the KVA
35 Decimal point of the KVA
36 Units number of the KVA
37 Tens number of the KVA
38 Hundreds number of the KVA
39 Thousands number of the KVA
3A RPM low byte calculated by charger
3B RPM high byte calculated by charger
3C
3D
3E System information
3F Value of lubricant temperature
The value 0xFF (255) represents the lubricant
temperature sensor is open.
The value 0xFE (254) represents the lubricant
temperature is over 120 ℃.
The value 0xFD (253) represents the lubricant
temperature is below 40 ℃.
The value 0xFC (253) represents the lubricant
temperature sensor is short.
The other value represents current lubricant
temperature, for example, the value is 0x55
(85) that represents 85 ℃.
40 Trip code
41 Alarm code
42 U-V voltage low byte
43 V-W voltage low byte
44 W-U voltage low byte
45 U-V voltage high byte
46 V-W voltage high byte
47 W-U voltage high byte
48 Remote run down-count counter
49 Remote run down-count aide counter
4A
4B
4C
4D
4E
4F
50 U-N voltage
51 V-N voltage
52 W-N voltage
10

Ratio of AC voltage
Mask readout value with binary value
11111000B and right shift 3 digits to get the
voltage ratio index.
Ratio index = readout value >> 3
Ratio
index System
voltage Line voltage
ratio Phase voltage
ratio
0 110V 0.01 1
1 120V 0.01 1
2 190V 0.01 1
3 208V 0.01 1
4 220V 0.01 1
5 380V 0.01 1
6 440V 0.02 2
7 480V 0.02 2
8 3300V 0.1 10
53
9 660V 0.03
Ratio
index CT ratio CT ratio
0 20:5 15 1000:5
1 30:5 16 1500:5
2 40:5 17 2000:5
3 50:5 18 3000:5
4 60:5 19 4000:5
5 80:5 20 5000:5
6 100:5 21 6000:5
7 150:5 22 10:5
8 200:5 23 15:5
9 300:5 24 75:5
10 400:5 25 250:5
11 500:5 26 750:5
12 600:5 27 1200:5
13 800:5 28 2500:5
14 900:5
3
54 Ratio of current transformer
Mask readout value with binary value
11111000B and right shift 3 digits to get the
current ratio index.
Ratio index = readout value >> 3
2.1.4 Example for AC line voltage, phase voltage, and current readout
R-S voltage readout
1. Let’s say the GTR85 controller address is 0x41, the factory ID number (FID) is 0x6F, the RS voltage is
220V and the system voltage is 220V.
2. Get the voltage ratio:
a. Master device should send 0x41 0xC8 0x53 as an original command and data.
b. After encryption factory ID number 0x6F, the command should like 0x2E 0xA7 0x3C.
c. Receiving information:
i. Master device via MTR-1 connect to GTR85: The transmitting information should be “| 2 EA7 3 C”.
The receive Echo and Check are “4F91”. The receiving information is “20FE” after encrypt with
factory ID number (FID, 0x6F).
ii. Master device direct connect to GTR85: The command transmitting information should be 0x2E
0xA7 0x3C. The receive Echo and Check are 0x4F 0x91. The receiving information is 0x20 0xFE
after encrypt with factory ID number, FID 0x6F.
d. The readout of voltage ratio is 0x20 (32).
e. Mask the Echo value with binary value 11111000B and right shift three digit, and the answer is 0x04.
f. Check the look up table and get the ratio 0.01 and the system volt is 220V.
3. Get the R-S voltage low byte:
a. Master device should send 0x41 0xC8 0x02 as an original command and data.
b. After encryption factory ID number 0x6F, the command should like 0x2E 0xA7 0x6D.
c. Receiving information:
i. Master device via MTR-1 connect to GTR85: The transmitting information should be “| 2 EA7 6 D”.
The receive Echo and Check are “9F91”. The receiving information is “F0FE” after encrypt with
factory ID number, FID 0x6F.
ii. Master device direct connect to GTR85: The command transmitting information should be 0x2E
0xA7 0x6D. The receive Echo and Check are 0x9F 0x91. The receiving information is 0xF0 0xFE
11

after encrypt with factory ID number, FID 0x6F.
d. The readout of R-S voltage low bye is 0xF0 (240).
4. Get R-S voltage high byte:
a. Master device should send 0x41 0xC8 0x05 as an original command and data.
b. After encryption factory ID number 0x6F, the command should like 0x2E 0xA7 0x6A.
c. Receiving information:
i. Master device via MTR-1 connect to GTR85: The transmitting information should be “| 2 EA 7 6 A”.
The receive Echo and Check are “3A91”. The receiving information is “55FE” after encrypt with
factory ID number, FID 0x6F.
ii. Master device direct connect to GTR85: The command transmitting information should be 0x2E
0xA7 0x6A. The receive Echo and Check are 0x3A 0x91. The receiving information is 0x55 0xFE
after encrypt with factory ID number, FID 0x6F.
d. The readout of R-S voltage low bye is 0x55 (85).
5. Combine the voltage high and low byte to get the RS true value.
a. High byte contribute value is 256 * 85 = 21760.
b. Low byte contribute value is 240.
c. The voltage ratio is 0.01.
d. So the answer is (21760 + 240) * 0.01 = 220 V
R-N voltage readout
1. Let’s say the GTR85 controller address is 0x41, the factory ID number, FID is 0x6F, the RN voltage is
127V and the voltage ratio is 220V.
2. Get the voltage ratio:
a. Master device should send 0x41 0xC8 0x53 as an original command and data.
b. After encryption factory ID number 0x6F, the command should like 0x2E 0xA7 0x3C.
c. Receiving information:
i. Master device via MTR-1 connect to GTR85: The transmitting information should be “| 2 EA7 3 C”.
The receive Echo and Check are “4F91”. The receiving information is “20FE” after encrypt with
factory ID number, FID 0x6F.
ii. Master device direct connect to GTR85: The command transmitting information should be 0x2E
0xA7 0x3C. The receive Echo and Check are 0x4F 0x91. The receiving information is 0x20 0xFE
after encrypt with factory ID number, FID 0x6F.
d. The readout of voltage ratio is 0x20 (32).
e. Mask the Echo value with binary value 11111000B and right shift three digit, and the answer is 0x04.
f. Check the look up table and get the ratio 1 and the system volt is 220V.
3. Get the R-N voltage:
a. Master device should send 0x41 0xC8 0x0Aas an original command and data.
b. After encryption factory ID number 0x6F, the command should like 0x2E 0xA7 0x65.
c. Receiving information:
i. Master device via MTR-1 connect to GTR85: The transmitting information should be “| 2 EA 7 6 5”.
The receive Echo and Check are “1091”. The receiving information is “7FFE” after encrypt with
factory ID number, FID 0x6F.
ii. Master device direct connect to GTR85: The command transmitting information should be 0x2E
0xA7 0x65. The receive Echo and Check are 0x10 0x91. The receiving information is 0x7F 0xFE
after encrypt with factory ID number, FID 0x6F.
d. The readout of R-N voltage is 0x7F (127)
4. The answer is 127 * 1 = 127V
12

R-phase current readout
1. Let’s say the GTR85 controller address is 0x41, the factory ID number, FID is 0x6F, the R-phase current is
365A and the current ratio is 400:5.
2. Get the current ratio:
a. Master device should send 0x41 0xC8 0x54 as an original command and data.
b. After encryption factory ID number 0x6F, the command should like 0x2E 0xA7 0x3B.
c. Receiving information:
i. Master device via MTR-1 connect to GTR85: The transmitting information should be “| 2 EA7 3 B”.
The receive Echo and Check are “3F91”. The receiving information is “50FE” after encrypt with
factory ID number, FID 0x6F.
ii. Master device direct connect to GTR85: The command transmitting information should be 0x2E
0xA7 0x3B. The receive Echo and Check are 0x3F 0x91. The receiving information is 0x50 0xFE
after encrypt with factory ID number, FID 0x6F.
d. The readout of current ratio is 0x50 (80).
e. Mask the Echo value with binary value 11111000B and right shift three digit, and the answer is 0x0A.
f. Check the look up table and get the ratio 400:5, and the full scale is 400.
3. Get the R-phase current low byte:
a. Master device should send 0x41 0xC8 0x2Aas an original command and data.
b. After encryption factory ID number 0x6F, the command should like 0x2E 0xA7 0x45.
c. Receiving information:
i. Master device via MTR-1 connect to GTR85: The transmitting information should be “| 2 EA 7 4 5”.
The receive Echo and Check are “2D91”. The receiving information is “42FE” after encrypt with
factory ID number, FID 0x6F.
ii. Master device direct connect to GTR85: The command transmitting information should be 0x2E
0xA7 0x45. The receive Echo and Check are 0x2D 0x91. The receiving information is 0x42 0xFE
after encrypt with factory ID number, FID 0x6F.
d. The readout of R-phase current low bye is 0x42 (66).
4. Get the R-phase current high byte:
a. Master device should send 0x41 0xC8 0x2D as an original command and data.
b. After encryption factory ID number 0x6F, the command should like 0x2E 0xA7 0x42.
c. Receiving information:
i. Master device via MTR-1 connect to GTR85: The transmitting information should be “| 2 EA 7 4 2”.
The receive Echo and Check are “6191”. The receiving information is “0EFE” after encrypt with
factory ID number, FID 0x6F.
ii. Master device direct connect to GTR85: The command transmitting information should be 0x2E
0xA7 0x42. The receive Echo and Check are 0x61 0x91. The receiving information is 0x0E 0xFE
after encrypt with factory ID number, FID 0x6F.
d. The readout of R-phase current high bye is 0x0E (14).
5. Calculate the R-phase current by the following procedure:
if (full scale <= 80)
{
R-phase current = (256 * current-high-byte + current-low-byte) / 100;
Current display format is XX.X A
}
else if (full scale <= 200)
{
R-phase current = (256 * current-high-byte + current-low-byte) / 100;
Current display format is XXX.X A
}
13

else
{
R-phase current = (256 * current-high-byte + current-low-byte) / 10;
Current display format is XXXX A
}
So, the answer is (256 * 14 + 66) / 10 = 3650 / 10 = 365 A. (end)
14

3 Software manual
3.1 GTR85 software installation
1. Step 1: open the GTR80 installation folder and
double click the file “setup.exe”. The setup wizard
will guide you to finish the whole installing
process.
2. Step 2: welcome screen.
3. Step 3: choose the destination folder.
4. Step 4:
5. Step 5: restart computer.
15

3.2 GTR85 software description
3.2.1 Button
Connection
The connection config window will display after
clicked this button. User need to be set comport,
connection method and controller ID. Then click
“Connect” button makes the communication working
between controller and computer.
Local connection setting window
Remote connection window
Disconnection
Click this button cuts off connection between
computer & controller
Open file
Open an existed configuration file of GTR85. It is
convenience for configuring the GTR85 controller
with the same requirement.
Save file
e the configuration of GTR85 in to a file as a
Sav
record or a configuration library.
Remote start
When the connection between GTR85 and software is
setup, User can remote start engine by two ways:
1. Enable the “Remote start run-time interval”
item then click OK. The engine will be started
at next second, and will be stopped until the
timer is expired, or click the remote stop
button.
2. Click OK directly, the engine will be started
and will be stopped if the communication is
failed or click the remote stop button.
Note: Communication may fail by many reasons, so it
hat u ethod 1 to remote
start the engine.
is strong suggestion t sing m
Remot p
e sto
t.
Reset
Click this button shuts down the running engine that
by network remote star
Click this button clears the fault indicate and set the
whole system in a normal status.
Panel
Click this button shows the controller’s panel and all
real time information.
16

Setting
Click this button shows the configuration screen.
Read all parameters
Click this button, all configuration settings will be
read from the GTR85 controller.
aram ters
Set all p e
Click this button, all configuration settings will
written into the GTR85 controller. be
About
Click this button shows the information of the the
Monicon instruments Co., Ltd. and the version of
GTR85 software.
Read parameters
Click this button reads all the parameters in the
current page that user selects.
Set param
eters
Click this button configures all the parameters in the
current page that user selects.
Refresh -
After configuring gsettin s to the GTR85 controller,
into the running procedure.
Clear MSG
the settings are in the un-working memory. Click this
button lets the GTR82 controller to refresh its settings
Click this button clears the texts in the message box.
17

3.3 Parameters description
3.3.1 ATS page
ATS Parameter
Range Default Description
Emergency start time delay
(TDES) 0,5~30sec 4sec. When utility (normal) power failure exceeds this
setting, the GTR85 starts generator.
Normal to emergency time
delay(TDNE) 0,5sec~ 30 sec 2sec. Time delay between the circuit switch transfers
from the utility (normal) power side to the
emergency power side. This function executed
by activation of EG side relay (terminal G39,
G40).
Emergency to normal
Time delay(TDEN) 0,5~30 sec 1sec. The interval between the circuit switch transfers
from emergency power side to the utility
(normal) power side after utility (normal) power
recovered. This function executed by activation
of MG side relay (terminal G37, G38).
TDOFF 0,25~5sec 0,5sec. The interval of circuit switch in the off state that
means the circuit switch neither in utility
(normal) power side nor in emergency power
side.
TDMP 0,5~7,5sec 5sec. The time delay of utility (normal) power
recovers from failure status to normal status.
Phase1/3 setting Phase1 Phase 3 Phase3 When single phase is selected, the utility
(normal) power connects to the terminal G34(U)
& G36(W).
3.3.2 System page
18
Table of contents
Other Monicon Controllers manuals
Popular Controllers manuals by other brands

ABB
ABB ACS800-17 Hardware manual

DayTronic
DayTronic 4000 Series instruction manual

Pool Technologie
Pool Technologie PRO DOSING ORP Instructions for use

Sorel
Sorel HCC 3 Installation and operating instructions

C.E. Nierhoff & Co
C.E. Nierhoff & Co C726 troubleshooting guide

ADLINK Technology
ADLINK Technology PXI -3950 user manual