OPERATION
1.Turn on the power supply to heater.
2.Rotate thermostat knob fully clockwise. This heater is equipped with a fan delay, so the fan will be
delayed 45-60 seconds after the element is energized.
3.Allow the room to reach desired temperature, then rotate thermostat knob counter clockwise until
thermostat clicks. Fan will continue to run for 45-60 seconds to purge warm air from heater enclosure.
The heater will continue to cycle on and off in the selected temperature range.
4.For remote thermostat operation, remove wire nut on wires marked T1 and T2. Connect single pole
remote thermostat to T1 and T2. Thermostat wiring must be the same size as power supply wiring. See
specification chart for minimum wire size.
NOTE: The wall thermostat cycles the heating element only. Direct runs of supply service leads L1
& L2 supplies continuous power to the fan motor, and the heater should be considered live at all
times. Move the disconnect switch to the off position or disconnect power at main distribution box
before any maintenance work. Turning the thermostat to low position will not disconnect the heater.
NOTE: This heater is equipped with a manual reset limit control. The front grille must be removed to
reset limit. Disconnect power before reset button is pushed.
SPECIFICATIONS
MODEL NO. VOLTS WATTAGE * BTU/HR AMPERAGE MIN. **WIRE SIZE60
°°
°°
°
C
E3035 120 1500/750 5120/2560 12.5/6.25 12 AWG.
E3045 120 1500/750 5120/2560 12.5/6.25 12 AWG.
E3055 120 1500/750 5120/2560 12.5/6.25 12 AWG.
E3038 120 1800/900 6143/3072 15/7.5 12 AWG.
E3048 120 1800/900 6143/3072 15/7.5 12 AWG.
E3058 120 1800/900 6143/3072 15/7.5 12 AWG.
F3032 208 2000/1000 6826/3413 9.6/4.8 14 AWG.
F3042 208 2000/1000 6826/3413 9.6/4.8 14 AWG.
F3052 208 2000/1000 6826/3413 9.6/4.8 14 AWG.
H3032 240/208 2000/1000 6826/5120 8.33/4.16 14 AWG.
1500/750 3413/2560 7.22/3.6
H3042 240/208 2000/1000 6826/5120 8.33/4.16 14 AWG.
1500/750 3413/2560 7.22/3.6
H3052 240/208 2000/1000 6826/5120 8.33/4.16 14 AWG.
1500/750 3413/2560 7.22/3.6
G3032 277 2000/1000 6826/3413 7.22/3.61 14 AWG.
G3042 277 2000/1000 6826/3413 7.22/3.61 14 AWG.
G3052 277 2000/1000 6826/3413 7.22/3.61 14 AWG.
* Factory wired for higher wattage, field convertible to lower wattage. Form 9940
** Use copper wire only. All wiring must conform to N.E.C. and local electrical codes. Rev. 01/06
WARNING: It should be noted that the 3000 series units feature a fan delay control to allow for
element pre-heat and more critically fan purge of heat at the end of thermostat cycle. If the units are
turned off with disconnect while the motor is operating, the residual heat may allow the manual reset
thermal limit to cycle, this may lead to service calls and unnecessary returns of the units. To turn these
units off with the disconnect switch, the thermostat should first be turned to low position, fan
should be allowed to complete the purge cycle. These units have a label attached that states “ DO NOT
DISCONNECT UNIT WHILE FAN IS RUNNING”. This applies to any unit that has the disconnect option.