Morrison Bros. co. 918AC Series Manual

1
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
!
!
rev.10-20-2021
The 918AC Series is designed to provide a visible and audible alarm. It is an A.C. powered device intended
to be located in an ordinary location. The 918AC Series System Interface is congurable for one to four
Intrinsically Safe, normally open or normally closed, dry contact inputs and from zero to four form C (SPDT),
dry contact outputs. The outputs may be congured as normally disengaged or normally engaged (fail-safe).
Two possible applications are use as an overll alarm or as an interstitial alarm.
Failure to follow any or all of the warnings and instructions in this document could result in a hazardous
liquid spill, which could result in property damage, environmental contamination, re, explosion, serious
injury or death.
Le fait de ne pas se conformer à l’un ou l’autre des avertissements ou à l’une ou l’autre des directives
apparaissant dans ce document pourrait donner lieu à des déversements de liquides dangereux, lesquels
pourraient engendrer des dommages matériels, des risques de contamination environnementale,
d’incendie ou d’explosion, des blessures graves ou la mort.
Contents
Specications.....................................................................................................................................2
Installation and Testing......................................................................................................................3
Mounting ......................................................................................................................................4
Steps to Wire and Congure the System Interface............................................................................5
Input Module(s) ............................................................................................................................5
Facilities Section of the System Interface ....................................................................................7
Output Module(s) (if so equipped) ............................................................................................... 8
Completion ...................................................................................................................................10
Steps to Congure the 918AC Series System Interface Motherboard ..............................................11
Auto-Silence .................................................................................................................................11
Audible Alarm ..............................................................................................................................12
‘Heartbeat’ Function ......................................................................................................................13
Steps to Test the 918AC Series System Interface.............................................................................. 14
Operation ...........................................................................................................................................16
Use as an Overll Alarm ..............................................................................................................16
Use as in Interstitial Alarm ...........................................................................................................16
Maintenance ..................................................................................................................................... 17
Monthly ........................................................................................................................................17
Yearly........................................................................................................................................... 18
DIP Switch Conguration Tables ......................................................................................................19
Input Module ................................................................................................................................19
Output Module..............................................................................................................................19
Motherboard .................................................................................................................................19
Replacement Parts .............................................................................................................................21
918AC System Interface Control Drawing B-7767-14.....................................................................22
918AC Series System Interface
Installation, Operation, and Maintenance Instructions

2
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
Specications
Description
The 918AC Series System Interface is intended to be located in an Ordinary Location. Its inputs are
intrinsically safe for use with Class I, Division 1 Group D. T4 Hazardous location with either normally open or
normally closed dry contacts.
WARNING: This is an intrinsically safe device and must be wired in accordance with National Electrical Code
Article 500. This device and its wiring may not share any junction box, conduit, or raceway with any other type
circuit or wiring. Do not perform live maintenance. Do not substitute components with anything other than
Morrison Bros. Co. components. Care must be taken to avoid an ignition hazard from impact or friction with the
enclosure.
AVERTISSEMENT: Cet appareil intrinsèquement sécuritaire doit être branché conformément à l’article
500 du code électrique national. Il se peut que ce dispositif et son câblage ne partagent pas de boîte de
connexion, de conduit ou de canalisation avec un autre type de circuit ou de câblage. Ne menez pas de travaux
de maintenance sous tension. Ne remplacez les composantes que par des composantes de Morrison Bros. Co.
Assurez-vous d’éviter le risque d’inammation pouvant découler d’un impact ou de friction avec l’enceinte.
Entity Parameters for Channel Inputs (Terminal P1 on each Dry Contact Input Module)
VOC = 4.935 VDC ISC = 99.697 mA Ca = 0.37 μF La = 1.43 μH PO = 0.123 W
Output Module Contact Rating
240 VAC Maximum
5 Amps Maximum
System Interface Input Power
Nominal Input Voltage: 120/240VAC
Maximum Current Draw: 0.0325A
Maximum Power Consumption: 1.77W
Line Frequency: 50/60Hz
Power Supply Protection Fuse Rating: 1.0A FA 5x20mm
Operating Temperature
-40ºF to 140ºF (-40ºC to 60ºC) to 100% humidity
Enclosure Rating
NEMA 4X
Maximum Wiring Distance
Maximum wiring distance between Alarm and input device is 5000 ft.

3
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
!
!
Installation and Testing
WARNINGS
• Fire Hazard – Death or serious injury could result from spilled liquids.
• You must be trained to install or maintain this alarm. Stop now if you have not been trained.
• Any modication of this unit beyond what is outlined in this instruction will void product warranty.
• For your safety, it is important to follow local, state, federal and/or OSHA rules that apply to working inside,
above, or around the storage tank and piping area. Use all personal protective equipment required for working
in the specic environment.
• This device is intended to be used as an auxiliary warning to the operator of an abnormal condition of
the system, such as a possible overll situation and should not be the only system in place to prevent an
unwanted condition, such as preventing a tank from overlling. It is the sole responsibility of the operator to
continuously prevent any spillage regardless of the situation.
• Tanks could be under pressure. Vapors could be expelled from tank vents, piping, valves or ttings while
performing maintenance. Vapors could catch re or cause an explosion. Avoid sparks, open ame, or hot tools
when working on tank system.
• Use a dampened cloth when cleaning the alarm enclosure to prevent static buildup and discharge.
• In the event of malfunction, contact Morrison Bros. Customer Service.
AVERTISSEMENTS
• Risque d’incendie – Un déversement de liquide pourrait entraîner des blessures graves ou la mort.
• Vous devez avoir reçu une formation pour installer cette alarme ou en assurer la maintenance. Arrêtez-vous
immédiatement si vous n’avez reçu aucune formation à cet eet.
• Toutes les modications apportées à cette unité autres que celles indiquées dans ces directives engendreront
l’annulation de la garantie du produit.
• Pour assurer votre sécurité, il est important de vous conformer à la réglementation locale, d’État, fédérale
ou OSHA régissant les travaux à l’intérieur, au-dessus ou autour du réservoir de stockage et de la zone de
canalisation. Utilisez tout l’équipement de protection individuelle exigé pour travailler dans l’environnement
spécique.
• Cet appareil est destiné à être utilisé comme mécanisme avertissant l’opérateur d’un état anormal du système
tel une situation de remplissage excessif et ne devrait pas être le seul système en place pour empêcher un état
indésirable, par exemple, un réservoir qui se remplit trop. L’opérateur a l’entière responsabilité de s’assurer
continuellement de prévenir tout déversement, quelle que soit la situation.
• Les réservoirs pourraient être sous pression. Des vapeurs pourraient être expulsées des conduits d’aération,
des canalisations, des soupapes ou des raccords du réservoir durant la maintenance. Les vapeurs pourraient
s’enammer ou engendrer une explosion. Évitez les étincelles, les ammes nues ou les outils chauds lors de
travaux menés dans le système du réservoir.
• Utilisez un linge humide pour nettoyer l’enceinte de l’alarme an de prévenir l’accumulation d’électricité
statique et les décharges.
• En cas de défaillance, communiquez avec le service à la clientèle de Morrison Bros.
Note: As dened in Article 501 – Class 1 Locations of NFPA 70, this apparatus and its connected wiring are
intrinsically safe. Under normal conditions this apparatus and its wiring cannot release sucient energy to
ignite a specic ignitable atmospheric mixture by opening, shorting, or grounding.

4
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
WARNING:
Interconnect wiring between the sensor(s) and the System Interface unit must be kept totally isolated and
separate from any other wiring. This wiring must not share any junction box, conduit, raceway, or xtures with
circuits other than those dened by NEC as being intrinsically safe for all Class 1 locations.
These inputs are ground referenced and only require “basic insulation.”
AVERTISSEMENT:
Le câblage d’interconnexion entre la jauge et l’unité d’alarme doit être complètement isolé et distinct du reste
du câblage. Le câblage ne doit partager aucune boîte de connexion, aucun conduit, aucune canalisation, ni
aucun accessoire avec des circuits autres que ceux dénis par NEC comme étant intrinsèquement sécuritaires
pour tous les emplacements de classe 1.
Ces entrées sont mises à la terre et ne requièrent qu’une « isolation de base ».
Location:
The System Interface enclosure is only approved for operation outside of all hazardous locations as dened by
the National Electrical Code or NFPA 70.
Mounting
To maintain the enclosure’s NEMA 4X rating
• Three openings have been provided in the bottom of the NEMA 4X enclosure for
connection and wiring. Only use Thomas & Betts Cat. No. H050GR-TB or H050-TB or
equivalent ½” hubs in these openings.
• Mounting tabs have been provided with the product to mount the enclosure; do not make
additional holes in this enclosure.
• Ensure that both cover latches are latched at all times.
Failure to follow these instructions voids any assurance that the enclosure is NEMA 4X.
!

5
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
Steps to Wire and Congure the System Interface
Imput Module(s)
1. Preparation
a. Open the front cover of the System Interface by releasing the two cover latches and swinging the
cover open.
b. Remove and retain the two screws with their at washers. Remove the metal cover of the
intrinsically safe section (see Figure 1).
2. Wiring
a. Run two oil and gas resistant wires from each input device to the location where the System
Interface will be mounted. Enter the enclosure through the LEFT bottom opening ONLY. If a
junction box is used, do NOT attach the wires of the input device(s) at this time. If the input device
is a Normally-Closed contact, connect the two wires together at the device end. If the device is a
Normally-Open contact, verify that the two wires are not connected to one another.
b. Connect the two wires from each input device to the two screw terminals for each channel input of
the Channel Input Connector (P1) for each Input Module (see Figure 2 and Figure 3).
Strip o about ¼ inch (5mm) of insulation from the wire and twist the ends of the wire.
The Channel Input Connector Insert the wire fully into the connector & snug the screw.
Figure 2 Wiring the Channel Input Connector
Intrinsically
Safe Section
Facilities
Section
Figure 1 Basic Layout of the 918AC

6
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
c. Verify that they are securely held in the connector by gently tugging on them.
d. Plug the connector onto the Channel Input pins of the Dry Contact Input Module (see Figure 3).
Figure 3 Plug the Channel Input Connector onto the Channel Input Pins of the Alarm Circuit Board
e. Repeat steps 2 through 2.d for each remaining Input Channel.
3. Conguration
a. For Normally Open Contact Input Devices: If the input device to be connected to a particular Dry
Contact Input Module utilize normally open contacts, verify that the DIP switch on that module,
SW1, is in the “ON” position (see Figure 4).
b. For Normally Closed Contact Input Devices: If the input device to be connected to a particular
Dry Contact Input Module utilizes normally closed contacts, place the DIP switch on that module,
SW1, in the “OFF” position (see Figure 4).
Figure 4 Conguring Input Mode with SW1
4. Completion
a. Inspect all of the wiring to verify that it has been done properly. Correct any discrepancies and re-
inspect.
b. When the installation has passed inspection, reinstall the cover over the Intrinsically Safe section of
the System Interface.
i. Place the cover in place and very loosely install the screws with their at washers as shown
in Figure 5
Figure 5 Installing the I.S. Cover

7
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
ii. Gently push the cover over to the wall of the enclosure and secure in place with the screws.
iii. Snug the screws down.
IMPORTANT NOTE: Verify that the power is shut o and the appropriate “Lockout/Tagout” (LOTO)
procedure is being adhered to before attempting any power wiring. This is true for
both the Power Input to the System Interface and the devices connected to the Output
Modules.
Facilities Section of the System Interface
NOTE:
A circuit breaker must be:
• included in this installation
• suitably located and easily reached
• marked as the disconnecting device for the 918AC being installed
1. Preparation
a. Remove the cover over the Facilities section of the System Interface (see Figure 1).
b. Remove and retain the three screws that secure the cover in place.
c. Remove the cover.
2. Wiring
a. Unplug the System Interface power input connector (J401/LNG) from the Motherboard.
b. Wire AC power from a dedicated circuit breaker, to the System Interface connector with the proper
wire per the appropriate electrical codes. Wiring shall be in accordance with the National Electric
Code and local regulation. Enter the enclosure through the center bottom hole ONLY.
c. Be sure to connect input ground to the Intrinsic Safety Grounding Stud on the baseplate of the
Figure 918AC inside the enclosure (see Figure 6).
d. Connect the Intrinsic Safety Grounding Stud to an appropriate ground. Refer to NFPA 70, Article
504 for ground suitability.
Figure 6 Intrinsic Safety Grounding Stud
e. Strip the wire as shown in Figure 2.
f. Insert the wire fully into the power input connector & snug the screw
g. Repeat 2.e through 2.f for the remaining wires.
i. “L” → “Line” or HOT
ii. “N” → “Neutral”
iii. “G” → “Ground”
h. Verify that the wires are securely held in the connector by gently tugging on them.
i. Connect the input power to the Motherboard at J401/LNG being sure to pay attention to the
polarization of the connector.
j. DO NOT APPLY POWER TO THE SYSTEM INTERFACE.

8
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
Output Module(s) (if so equipped)
NOTE: See “Output Module Contact Rating” section of the “Specications” section of this document (on
page 2, above) for the contact rating for the output modules.
NOTE: The 918AC “outputs” do not provide any power of themselves; these are dry-contact switches only.
Supplied power runs through them to control your devices.
1. Wiring
a. Wiring shall be in accordance with the National Electric Code and local regulation. Enter the
enclosure from the right bottom hole only.
b. Strip the wire as shown in Figure 2.
c. Insert the wire fully into the connector & snug the screw
d. Repeat 1.b through 1.c above for the remaining wires as required by your application.
i. “C” → “COMMON”
ii. “NO” → “Normally-Open” contacts (C → NO only when relay is activated)
iii. “NC” → “Normally-Closed” contacts (C → NC only when relay is de-activated)
iv. Verify that the wires are securely held in the connector by gently tugging on them.
e. Connect the Output Connector to the Output Module connector, P1, as shown in Figure 7.
Figure 7 Connecting the Output Connector to the Output Module connector, P1
f. Repeat 1 through 1.e for each remaining Output Module.
2. Conguration
a. Alarm Channel – Congures a Dry Contact Output Module to respond to specic input channels.
Each Output Module may be congured to be activated by one or more input channels in any
combination. This is accomplished by setting DIP switch positions one through four of S2 either
ON (selecting a channel) or OFF (not selecting a channel).

9
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
Figure 8 - Output Module Alarm Channel Conguration
i. Locate the four position DIP switch, S2, on the Output Module to be congured
(see Figure 8).
ii. Place DIP switch Position One in the “ON” position to congure the output module to
respond to Input Channel One or in the “OFF” position to congure the Output Module to
not respond to Input Channel one.
iii. Place DIP switch Position Two in the “ON” position to congure the output module to
respond to Input Channel Two or in the “OFF” position to congure the Output Module to
not respond to Input Channel two.
iv. Place DIP switch Position Three in the “ON” position to congure the output module
to respond to Input Channel Three or in the “OFF” position to congure the Output Module
to not respond to Input Channel three.
v. Place DIP switch Position Four in the “ON” position to congure the output module to
respond to Input Channel Four or in the “OFF” position to congure the Output Module to
not respond to Input Channel four.
b. Relay Mode – Congure the Dry Contact Output Module as Normally-Deactivated or Normally-
Activated (fail-safe)
NOTE: Fail-Safe mode swaps the denition of the relay contact state. Normally-Open (NO) contacts become
Normally-Closed (NC) and Normally-Closed (NC) contacts become Normally-Open (NO).
ON = Respond to
this Channel’s Alarm
OFF = Do NOT
Respond to this
Channel’s Alarm
Channel 4
Channel 3
Channel 2
Channel 1

10
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
Figure 9 - Output Module Mode Conguration
i. Locate the single position DIP switch, S1, on the Output Module to be congured (see
Figure 9).
ii. Place this DIP switch in the “OFF” position if the output is to be congured as Normally-
Deactivated.
iii. Place this DIP switch in the “ON” position if the output is to be congured as Normally-
Activated (Failsafe).
Completion
1. Inspect all of the wiring to verify that it has been done properly. Correct any discrepancies and re-inspect.
2. When the installation has passed inspection, reinstall the cover over the Facilities section of the System
Interface
a. Place the cover in place and install the three screws.
b. Snug the screws down.
ON = Normally
Activated
OFF = Normally
Deactivated

11
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
Steps to Congure the 918AC Series System Interface Motherboard
Auto-Silence
Select which input channels will automatically silence after a 3 minute timeout period.
Figure 10 - Motherboard Auto-Silence Conguration
1. Locate the four position, Auto-Silence DIP switch, SW101, on the Motherboard (see Figure 10).
2. Place DIP switch Position One in the “ON” position to congure the Motherboard to automatically silence
an alarm on channel one after timeout. Place DIP switch Position One in the “OFF” position to congure the
Motherboard to continuously indicate an alarm on channel one.
3. Place DIP switch Position Two in the “ON” position to congure the Motherboard to automatically silence
an alarm on channel two after timeout. Place DIP switch Position Two in the “OFF” position to congure the
Motherboard to continuously indicate an alarm on channel two.
4. Place DIP switch Position Three in the “ON” position to congure the Motherboard to automatically silence
an alarm on channel three after timeout. Place DIP switch Position Three in the “OFF” position to congure
the Motherboard to continuously indicate an alarm on channel three.
5. Place DIP switch Position Four in the “ON” position to congure the Motherboard to automatically silence
an alarm on channel four after timeout. Place DIP switch Position Four in the “OFF” position to congure
the Motherboard to continuously indicate an alarm on channel four.
ON = Autosilence
Activated for
Channel
OFF = Autosilence
Deactivated for
Channel

12
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
Audible Alarm
Select which channels will produce an audible alarm.
Figure 11 - Motherboard Buzzer Conguration
1. Locate the four position, Buzz DIP switch, SW102, on the Motherboard (see Figure 11).
2. Place DIP switch Position One in the “ON” position to congure the Motherboard to provide both an audible
and a visual alarm for input channel one. Place DIP switch Position One in the “OFF” position to congure
the Motherboard to only provide a visual alarm for channel one.
3. Place DIP switch Position Two in the “ON” position to congure the Motherboard to provide both an audible
and a visual alarm for input channel two. Place DIP switch Position Two in the “OFF” position to congure
the Motherboard to only provide a visual alarm for channel two.
4. Place DIP switch Position Three in the “ON” position to congure the Motherboard to provide both an
audible and a visual alarm for input channel three. Place DIP switch Position Three in the “OFF” position to
congure the Motherboard to only provide a visual alarm for channel three.
5. Place DIP switch Position Four in the “ON” position to congure the Motherboard to provide both an audible
and a visual alarm for input channel four. Place DIP switch Position Four in the “OFF” position to congure
the Motherboard to only provide a visual alarm for channel four.
ON = Audible
Alarm Activated
for Channel
OFF = Audible
Alarm Silenced
for Channel

13
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
‘Heartbeat’ Function
Enable/disable the heartbeat function.
NOTE: The heartbeat function will periodically ash the indicators on the front cover of the System Interface
to show observers that power is on. Any alarm condition present will override the heartbeat function. The
heartbeat function is disabled in the factory by default. By enabling the heartbeat function, it will remain active
(even after a power cycle) until disabled.
Figure 12 - Motherboard Reset Button
1. Open the front cover of the System Interface by releasing the two cover latches and swinging the cover open.
2. Locate the reset push button on the motherboard.
3. With power applied to the System Interface, press and hold the reset button.
4. On the front cover of the System Interface, press and hold the Silence/Test button.
5. Release the reset button.
6. Once you hear a beep from the System Interface, release the Silence/Test button.
Note: If the beep is followed by a quick ash of the indicators, the heartbeat function was enabled. If the beep
was not followed by a quick ash of the indicators the heartbeat function was disabled.

14
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
Steps to Test the 918AC Series System Interface
1. Determine which of the devices connected to the Output Module(s) need to be disconnected before beginning
this test. Remove the cover over the Facilities Section and unplug these Output Channels.
2. Apply power to the System Interface.
3. Press and hold the “Silence/Test” pushbutton on the front panel of the System Interface. All of the indicators
on the front panel should blink and the audible enunciator should sound.
4. Release the “Silence/Test” button.
5. Test the connection at the alarm and wiring
a. For Normally Open Contact Inputs:
i. Create an alarm condition:
1. If a junction box was used and the wires are not connected to the input device, connect
the two wires together at the input device end for each input device.
2. If a junction box was not used or the 918AC input was connected to the input device,
activate each input device.
ii. The System Interface should show an alarm until the Test/Cancel button is pushed.
iii. If the input being tested is congured to sound the audible enunciator (buzzer), then the
System Interface should also sound the alarm.
iv. Verify that the Output Module(s) (if they are installed) and the devices they are connected
to respond as congured.
NOTE: There is an indicator ☼ on the output module (see Figure 13) that illuminates when the relay is
activated. It is only visible when the Facilities section cover is removed (see Figure 13).
v. If the System Interface fails to respond properly, check the connections and retest until
results are satisfactory.
vi. Repeat for each channel.
b. For Normally Closed Contact Inputs:
i. Create an alarm condition:
1. If a junction box was used and the wires are not connected to the input device,
disconnect the two wires at the input device end for each input device.
2. If a junction box was not used or the 918AC input was connected to the input
device, activate each input device.
ii. The System Interface should show an alarm until the Test/Cancel button is pushed.
iii. If the input being tested is congured to sound the audible enunciator (buzzer), then the
System Interface should also sound the alarm.
iv. Verify that the Output Module(s) (if they are installed) and the devices they are connected
to respond as congured.
NOTE: There is an indicator ☼ on the output module (see Figure 13) that illuminates when the relay is
activated. It is only visible when the Facilities section cover is removed.
1. If the System Interface fails to respond properly, check the connections and retest
until results are satisfactory.
2. Repeat for each channel.
Figure 13 - Location of the Output Board Indicator
6. Connect the wires from the System Interface Unit to the wires of the input device(s) at the junction box for
each device, if not already done. Replace the junction box cover(s).
7. It is recommended to simulate an alarm condition and manually trigger the alarm using input device(s) (Clock
Gauge, oat switch or other dry contact device). If it does not, check wiring at junction box and verify
that the installation procedure was performed correctly. The alarm can be silenced after being activated by
pressing the Test/Cancel button.
8. Remove power from the System Interface.
INDICATOR

15
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
!
!
rev.10-20-2021
DO NOT PROCEED PAST THIS POINT UNTIL ALL TESTS HAVE BEEN PASSED
9. Plug in all Output Connectors to their respective Output Module(s) that were previously disconnected and
reinstall the cover over the Facilities Section of the System Interface.
10. Close the enclosure and secure.
11. Power may be applied to the System Interface and the unit put into service.
IMPORTANT: Install the included Warning Tag where it will be visible to the operator lling or unloading the
tank that is tted with this alarm system, if applicable.
Failure to follow any or all of the warnings and instructions in this document could result in a hazardous
liquid spill, which could result in property damage, environmental contamination, re, explosion, serious
injury or death.
Le fait de ne pas se conformer à l’un ou l’autre des avertissements ou à l’une ou l’autre des directives
apparaissant dans ce document pourrait donner lieu à des déversements de liquides dangereux, lesquels
pourraient engendrer des dommages matériels, des risques de contamination environnementale,
d’incendie ou d’explosion, des blessures graves ou la mort.

16
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
Operation
The 918AC Series System Interface may be used in applications where one to four sets of normally open or
normally closed dry contacts are available. Two possible applications are use as an overll alarm or as an
interstitial alarm. These two uses are addressed below.
Use as an Overll Alarm
Use with the Morrison Brothers 918 Clock Gauge or other similar input device.
1. Prior to lling a tank,
a. Check for an existing overll condition by observing the front panel.
i. A blinking channel indicator and no audible alarm tells you that there is an existing, auto-
silenced alarm on that channel.
ii. A solidly illuminated indicator tells you that there is an existing, manually acknowledged
alarm on that channel.
b. Check the overall operation of the System Interface.
i. Press and hold the “Silence/Test” button while listening to the Audible Alarm and observing
the Channel Alarm Indicator(s).
ii. All of the Visual Enunciators should be slowly blinking
iii. The Audible Enunciator/Alarm should be loud and strong, sounding about one second on
and one second o.
2. If an overll occurs while lling the tank, the Channel Alarm Indicator associated with the overll condition
will ash and, if congured to do so, the Audible Alarm will sound.
a. The alarm can be acknowledged and silenced by pressing the “Silence/Test” button on the front of
the Alarm.
b. If the alarm is not silenced by the operator, and the channel is congured to “Auto-Silence”, then the
System Interface will continue in the alarm state for no more than the timeout period at which point
it will silence itself. The visual indicator on the front panel will continue to blink, showing a new,
un-acknowledged alarm.
Use as an Interstitial Alarm
1. Should the contacts associated with an interstitial switch be activated, the System Interface will immediately
go into an alarm state; it will illuminate the Channel Alarm Indicator associated with the alarm condition and,
if congured to do so, sound the Audible Alarm.
2. If the System Interface is congured to “auto-silence” on the channel associated with the interstitial sensor,
and the alarm is not silenced manually by pressing the “Silence/Test” button, the System Interface will
continue in this alarm state for no more than its timeout period at which point it will silence itself. The visual
indicator on the front panel will continue to blink, showing a new, un-acknowledged alarm.
3. If an operator acknowledges the alarm condition by pressing the “Silence/Test” button, the System Interface
will silence the audible enunciator (if congured to sound on this input) and the channel alarm indicator will
illuminate continuously until the alarm condition is removed.
4. To check for an alarm state once the Alarm has silenced itself simply observe the front panel. A blinking
channel indicator and no audible alarm tells you that there is an existing, auto-silenced alarm on that channel.
A channel indicator which is continuously illuminated indicates that there is an existing, acknowledged
(silenced) alarm.

17
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
!
!
Maintenance
WARNINGS
• Fire Hazard – Death or serious injury could result from spilled liquids.
• You must be trained to install or maintain this alarm. Stop now if you have not been trained.
• Any modication of this unit beyond what is outlined in this instruction will void product warranty.
• For your safety, it is important to follow local, state, federal and/or OSHA rules that apply to working inside,
above, or around the storage tank and piping area. Use all personal protective equipment required for working
in the specic environment.
• This device is intended to be used as an auxiliary warning to the operator of an abnormal condition of the
system, such as a possible overll situation and should not be the only system in place to prevent an unwanted
condition, such as preventing a tank from overlling. It is the sole responsibility of the operator to continuously
prevent any spillage regardless of the situation.
• Tanks could be under pressure. Vapors could be expelled from tank vents, piping, valves or ttings while
performing maintenance. Vapors could catch re or cause an explosion. Avoid sparks, open ame, or hot tools
when working on tank system.
• Use a dampened cloth when cleaning the alarm enclosure to prevent static buildup and discharge.
• In the event of malfunction, contact Morrison Bros. Customer Service.
AVERTISSEMENTS
• Risque d’incendie – Un déversement de liquide pourrait entraîner des blessures graves ou la mort.
• Vous devez avoir reçu une formation pour installer cette alarme ou en assurer la maintenance. Arrêtez-vous
immédiatement si vous n’avez reçu aucune formation à cet eet.
• Toutes les modications apportées à cette unité autres que celles indiquées dans ces directives engendreront
l’annulation de la garantie du produit.
• Pour assurer votre sécurité, il est important de vous conformer à la réglementation locale, d’État, fédérale
ou OSHA régissant les travaux à l’intérieur, au-dessus ou autour du réservoir de stockage et de la zone de
canalisation. Utilisez tout l’équipement de protection individuelle exigé pour travailler dans l’environnement
spécique.
• Cet appareil est destiné à être utilisé comme mécanisme avertissant l’opérateur d’un état anormal du système
tel une situation de remplissage excessif et ne devrait pas être le seul système en place pour empêcher un état
indésirable, par exemple, un réservoir qui se remplit trop. L’opérateur a l’entière responsabilité de s’assurer
continuellement de prévenir tout déversement, quelle que soit la situation.
• Les réservoirs pourraient être sous pression. Des vapeurs pourraient être expulsées des conduits d’aération,
des canalisations, des soupapes ou des raccords du réservoir durant la maintenance. Les vapeurs pourraient
s’enammer ou engendrer une explosion. Évitez les étincelles, les ammes nues ou les outils chauds lors de
travaux menés dans le système du réservoir.
• Utilisez un linge humide pour nettoyer l’enceinte de l’alarme an de prévenir l’accumulation d’électricité
statique et les décharges.
• En cas de défaillance, communiquez avec le service à la clientèle de Morrison Bros.
There are two scheduled maintenance operations:
• MONTHLY: Test the overall operation of the System Interface (see 2 below)
• YEARLY: Check the Enclosure for water ingress (see 0 below)
Monthly
1. If necessary, clean the System Interface enclosure with a damp cloth.
2. Test the overall operation of the Alarm no less than once per month.
a. Press and hold the “Silence/Test” button while listening to the audible alarm and observing the
Channel Alarm indicator(s).
• Audible Alarm is loud and strong, sounding about one second on and one second o.
• Channel Alarm Indicator(s) is (are) blinking.

18
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
!
!
rev.10-20-2021
b. If alarm does not sound or the Channel Alarm Indicators do not blink, verify that power is applied to
the System Interface and re-test. If the alarm still does not sound replace the System Interface or call
Morrison Bros. Co Customer Service.
c. Inspect the warning tag located near the tank ll or o-loading area. If the tag is damaged or
dicult to read, contact Morrison Bros. at (800) 553-4840 for a free replacement tag.
Yearly
This check is to be performed no less than once per year.
1. Check the Enclosure for water ingress.
a. Carefully open the System Interface enclosure.
b. Inspect the interior of enclosure to determine if any water has inltrated the enclosure. If water has
inltrated the enclosure, take corrective action to seal the points of ingress.
c. Inspect the electronics for corrosion. If there is corrosion present on the electronic assembly(ies)
• Take corrective action to seal the enclosure from further water ingress.
• Contact Morrison Bros. Co. for further action.
d. Close and secure the enclosure. Verify that the cover is fully seated to the enclosure base.
2. Perform Monthly check as outlined above to verify the overall operation of the System Interface.
3. It is recommended to simulate an alarm condition and manually trigger the alarm using input device (Clock
Gauge, oat switch or other dry contact device). Disconnect devices wired to the Output Modules as
necessary before performing this check. If it does not, check wiring at junction box and verify that the
installation procedure was performed correctly. The alarm can be silenced after being activated by pressing
the “Silence/Test” button. Reconnect the Output devices previously disconnected once the test is passed and
complete.
Failure to follow any or all of the warnings and instructions in this document could result in a hazardous
liquid spill, which could result in property damage, environmental contamination, re, explosion, serious
injury or death.
Le fait de ne pas se conformer à l’un ou l’autre des avertissements ou à l’une ou l’autre des directives
apparaissant dans ce document pourrait donner lieu à des déversements de liquides dangereux, lesquels
pourraient engendrer des dommages matériels, des risques de contamination environnementale,
d’incendie ou d’explosion, des blessures graves ou la mort.

19
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
DIP Switch Conguration Tables
Input Module
Table 1 Input Module SW1 - Normally Open/Normally Closed Contacts
Output Module
Table 2 Output Module S1 - Normally Activated/Deactivated
Table 3 Output Module - Channel Selection
Motherboard
Table 4 Motherboard SW101 – Auto-Silence
Position
Setting
ON OFF
1
Congures the input module for
Normally Open contacts
Congures the input module for
Normally Closed contacts
Position
Setting
ON OFF
1Normally Activated (failsafe) Normally Deactivated
Position
Setting
ON
Activation of this channel triggers
this output module to change state
OFF
Activation of this channel has no
eect on this output
1Channel 1 Channel 1
2Channel 2 Channel 2
3Channel 3 Channel 3
4Channel 4 Channel 4
Position
Setting
ON
This channel will automatically
silence the buzzer after 3 minutes.
The LED will remain blinking until
the input is deactivated or the
Silence/Test button is pressed.
OFF
This channel will only be
silenced by pressing the Silence/
Test button.
1Channel 1 Channel 1
2Channel 2 Channel 2
3Channel 3 Channel 3
4Channel 4 Channel 4
NOTE: This DIP switch will have no eect for a channel if that channel is congured as a silent channel
(below)

20
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0142 PP
rev.10-20-2021
Table 5 Motherboard SW102 - Buzzer Channel Select
Position
Setting
ON
When this channel input is
activated, the buzzer will sound
until the Auto-Silence period
passes (if so congured) or until
the Silence/Test button is pressed,
whichever comes rst.
OFF
This channel is a silent channel.
The buzzer will not sound when
this input is activated.
1Channel 1 Channel 1
2Channel 2 Channel 2
3Channel 3 Channel 3
4Channel 4 Channel 4
Other manuals for 918AC Series
1
Table of contents
Other Morrison Bros. co. Security System manuals
Popular Security System manuals by other brands

Kidde
Kidde DM3000 Installation sheet

Xtralis
Xtralis ADPRO FastTrace 2 series installation manual

Rutenbeck
Rutenbeck TC Easy Plus operating instructions

Tynetec
Tynetec reach ultra User and installation guide

Hoyles
Hoyles EXITGUARD EX204 User instructions

Lupus Electronics
Lupus Electronics LUPUSEC-XT1 manual