MrCool MCDP Series User manual

Signature Series
MCDP* Series Coils
Please read this manual carefully before installation and keep it for future reference.
Due to updates and constantly improving performance, the information and instructions within this
manual are subject to change without notice. Please visit www.mrcool.com/documentation to
ensure you have the latest version of this manual.
Version Date: 05-24-21
Installation Manual

Save these instructions for future reference
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in
manuals, be alert to the potential for personal injury or death.
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.
Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves
and protective clothing.
The Clean Air Act of 1990 bans the intentional venting
of refrigerant (CFCs, HCFCs and HFCs) as of July
1, 1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration
may be levied for noncompliance.
General........................................................................2
Shipping and Packing List ...........................................2
Unit Dimensions ..........................................................3
Maintenance..............................................................10
INSTALLATION INSTRUCTIONS
Signature Series Evaporator Coils
Page 1 mrcool.com
Manufactured By:
MRCOOL®,LLC
48 Remington Way
Hickory, KY 42051

These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
condensing units or heat pumps. Each coil is equipped with
of a refrigerant metering device. Either a refrigerant
a thermal expansion valve (ordered separately) may be
used in condensing unit applications. A check / expansion
valve (ordered separately) is the only metering device
approved for use in heat pump applications.
as shown in Figure 2. Indoor coils will physically match the
furnace supply air opening with the same letter designation
in the model number (see Figure 1).
MCDP*18A MCDP*24A MCDP*24B
Nominal size - tons 1.5 2 2 2.5/3 2.5/3
Suction / vapor o.d. - sweat 7/8 (22.2) 7/8 (22.2) 7/8 (22.2) 7/8 (22.2) 7/8 (22.2)
Liquid o.d. - sweat 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Condensate drain (fpt) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19)
Net face area sq. ft. (m2) 3.5 (0.33) 3.21 (0.30) 3.21 (0.30) 4.08 (0.38) 4.08 (0.38)
Tube diameter - in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Number of rows 2 3 3 3 3
Fins per in. (m) 18 (709) 12 (472) 12 (472) 12 (472) 12 (472)
lbs. (kg) 1 package 44 (20) 44 (20) 49 (22) 57 (26) 58 (26)
MCDP*48B
Nominal size - tons 2.5/3 4 4 4/5 5
Suction / vapor o.d. - sweat 7/8 (22.2) 7/8 (22.2) 7/8 (22.2) 7/8 (22.2) 7/8 (22.2)
Liquid o.d. - sweat 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Condensate drain (fpt) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19)
Net face area sq. ft. (m2) 4.08 (0.38) 5.25 (0.49) 5.25 (0.49) 6.42 (0.60) 6.42 (0.60)
Tube diameter - in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Number of rows 3 3 3 3 3
Fins per in. (m) 12 (472) 12 (472) 12 (472) 12 (472) 12 (472)
lbs. (kg) 1 package 60 (27) 71 (32) 72 (33) 84 (38) 85 (39)
Package 1 of 1 contains the following:
1 - MCDP* evaporator coil
1 - Bag assembly containing:
3 - Straight coil locators (24B, 30/36B, 30/36C, 48C,
60D)
3 - Coil locators — 2 angular and 1 straight coil locators
(18A, 24A, 30/36A, 48B, 50/60C)
6 - #8 screws for fastening coil locators
1 - Liquid line stub (3/8” copper swedged)
1 - Warranty card
1 - Installation instructions
damage, immediately contact the last carrier.
MCDP* downflow evaporator coils are designed for use with
MCDP*30/36A MCDP*30/36B
MCDP*30/36C MCDP*48C MCDP*50/60C MCDP*60D
Page 2
mrcool.com

A B D E F H
MCDP*18A
14-1/8 359
17-1/2 445
13-1/2 343
15-1/2 394 8-3/4 222
6-1/4 159 3 76 2 51
MCDP*24A 5 127 5 127
MCDB*24B 16-1/2 419 1/2 13
16-1/8 410
13-1/2 343
6-1/8 156 3 76
2 51
16-1/2 419 1/2 13
21 533
20 508
19 483 10-1/2 267MCDP*48B 20 508 16-1/2 419 8-1/8 206 4 102 2-1/4 57
20 508 1/2 13
23-5/8 600 24-1/2 622 22-1/2 572 12-1/4 311 3-1/2 89 17-3/16 437 2-1/4 57
23-1/2 597 1/2 13
2
(51)
A
B
C
D
E
G
F
1
(25)
1
(25)
1−3/32
(28)
26−1/8
(664)
1
(25)
1−15/16
(49) 23−3/16
(589)
Outlet
Opening
Inlet
Opening
CONDENSATE
DRAIN
Outlet
Opening
Inlet
Opening
AIR
FLOW
SIDE VIEWFRONTVIEW
LIQUID LINE
(MCDP*18, 30/36, 48)
SUCTION (Vapor)LINE
(MCDP*24, 60)
1/2 (13)
22−5/8
(575)
H
H
SUCTION (Vapor) LINE
(MCDP*18, 30/36, 48)
LIQUID LINE
(MCDP*24, 60)
Liquid and Suction Line locations are reversed on MCDP*24 and MCDP*60 models.
MCDB*30/36A
MCDB*30/36B
MCDB*30/36C
MCDP*48C
MCDP*50/60C
MCDP*60D
Page 3 mrcool.com

“A” Width
Furnaces
MCDP*18A
MCDP*24A
MCDP*30/36A
14‐1/2
(368)
33 (838) new models
40 (1016) older models
16-3/8
(416)
13‐3/8
(340)
33 (838) newer models
40 (1016) older models
WARNING!
Coil Cabinet Wider
Than Furnace Cabinet
(Supply Air Openings
Match)
14-1/8 (359)
14-1/8 (359)
16-1/8 (410)
Physical
Match
MCDP*24B
MCDP*30/36B
14-1/8(359)
16-1/8(410)
17‐1/2
(446)
“B” Width
Furnaces
WARNING!
Coil Cabinet Wider
Than Furnace Cabinet
(Supply Air Openings
Match)
MCDP*48B 20 (508)
)644(2/1‐71)644(2/1‐71
21 (533)
Coil opening will physically match the furnace supply air opening with the same letter designation in the model
number.
Downflow Gas Furnaces - MCDP* Coils
Page 4
mrcool.com

19-7/8
(504)
MCDP*30/36C
MCDP*48C
16-1/8 (410)
20 (508)
Physical
Match
21 (533)
“C” Width
Furnaces
WARNING!
Coil Cabinet Wider
Than Furnace Cabinet
(Supply Air Openings
Match)
MCDP*50/60C 23-5/8 (600)
23-5/8
(546)
MCDP*60D 23-5/8 (600)
Physical
Match
24-1/2 (622)
“D” Width
Furnaces
24-1/2 (622)
21 (533) 24-1/2 (622)
33 (838) new models
40 (1016) older models
33 (838) new models
40 (1016) older models
C D 30/36 A N P A
P
C = Coil
Airflow (D = Downflow)
Capacity
(MBTU/H)
Coil Dimension
A =14.5 in
B =17.5 in
C = 21 in
D = 24.5 in
M
M = MRCOOL
Page 5 mrcool.com
A = 2nd Gen
Refrigerant
Case
C = Unpainted
U = Uncased
P = Painted
Metering Device
O =Orifice
T =TXV
C =Capillary
P =Piston
N =R410
R =R-22

The MCDP* coils are shipped with a 10 psi dry air holding
charge. Puncture the suction line rubber plug to release
the charge. Remove the rubber plug.
If there is no pressure when the rubber plug is
punctured, check the coil for leaks before installing the
Remove and discard the plug which is in the distributor
body.
to accommodate the supply air opening and the plenum. If
the unit is installed against a wall, the rear edge of the
opening must be at least 1” (25 mm) from the wall. Cut an
appropriately sized opening.
GAS
FURNACE
COIL LOCATOR BRACKETS
ALIGN THE COIL
LOCATOR BRACKET
WITH THE REAR AND
SIDES OF THE COIL
CABINET.
USE STRAIGHT OR
ANGULAR COIL
LOCATOR BRACKETS,
DEPENDING ON
MODEL AND
ALIGNMENT
REQUIREMENTS
FASTEN BRACKETS
TO FURNACE AND
COIL CABINET WITH
#8 SCREWS
SEAL BETWEEN
ADAPTER RAILS
AND FURNACE.
ED1P COIL
1.
of the unit with the matching plenum, then lower the
unit over the plenum. The coil cabinet must be either
level or sloped slightly toward the drain outlet and
secured and sealed to the plenum. If the furnace and
coil cabinet are the same size, skip to step 3.
Front to Rear
-18A, -24A, -24B,
-30/36A, -30/36B 14-1/4” (394 mm)
23” (584 mm)
-30/36C, -48B, -48C 19” (483 mm)
-50/60C, -60D 22-1/2” (571 mm)
Do not install screws through the drain pan.
2. —Install the provided coil locator
brackets on the coil. Align the coil locator brackets
with the rear and sides of the coil cabinet. Figure
2 illustrates how the furnace, coil and coil locator
not contact coil slabs.
There must be an airtight seal between the top of
sealing strips, caulking, or equivalent sealing method
between the plenum and the furnace cabinet to ensure
a tight seal. Return air must not be drawn from a room
where this furnace or any gas-fueled appliance (i.e.,
water heater), or carbon monoxide-producing device
3. —Seal between the furnace cabinet and the
coil cabinet to prevent air leaks.
4.
of the furnace and the coil cabinet.
All indoor cabinets be taped after installation to seal
will be reduced if air leakage exists.
The refrigerant line sets should be sized according to
the recommendations given in the condensing unit or
heat pump installation instructions (see Table 3 for sweat
to match line set connections.
MCDP* Unit
Page 6
mrcool.com

Sweat Size Size
All sizes 7/8 (22.0) 3/8 (9.5)
1-1/8” adapter.
1.
against the piping plate and around the piping stubs,
and sweat in the suction line. The heat shield must be
in place to guard against heat damage to the paint.
2. Slide the liquid line compression nut onto the provided
the liquid line stub for brazing.
3. Braze liquid line and coil connections. Use a silver
alloy brazing rod (5 or 6 percent silver alloy for copper-
to-copper connections or 45 percent silver alloy for
copper-to-brass or copper-to-steel connections).
4. Remove the heat shield after brazing and allow the
connections to cool.
5. Select the appropriate refrigerant metering device:
check/expansion valve.
thermal expansion valve. Refer to either the outdoor unit
installation instruction, product catalog or price book for
approved metering device.
ORIFICE OR
CHECK/EXPANSION
VALVE
O-RING
SUCTION LINE
ORIFICE
HOUSING
STRAINER
DISTRIBUTOR
TUBES
LIQUID LINE
STUB
SENSING
BULB
O-RING
NYLON SEAT
1.
pointing toward the distributor (see Figure 3).
2. Apply a small amount of refrigerant oil on the O-ring
3.
The suction line service port has no core. Make sure
that the service port cap is tightened securely.
4. Insulate the refrigerant lines at the connections to
prevent sweating.
of the suction line and seal cabinet opening.
All piping, metering devices and connections must
be insulated to prevent moisture damage caused by
sweating.
To install the check/thermal expansion valve:
1.
housing (see Figure 3).
2. Apply a small amount of refrigerant oil on the O-ring
(shipped with the valve assembly) and place it securely
3.
4. Screw the liquid line compression nut (with the liquid
line) on the threaded end of the expansion valve.
5. Install the expansion valve equalizer line on the suction
line service port.
tightened securely.
6. Use the clamp provided with the valve assembly to
secure the sensing bulb to the suction line.
The sensing bulb must be positioned as shown in Figure
3 to ensure proper valve operation.
All piping, metering devices, and connections must
be insulated to prevent moisture damage caused by
sweating. If the equipment is not properly insulated,
moisture could damage other equipment.
Slide insulation up to the cabinet to cover all
Page 7 mrcool.com

REMOVE ACCESS PANEL
A
REMOVE RUBBER PLUG FROMBOTH LIQUID
AND SUCTIONLINES
B
NITROGEN
HIGH
LOW
EITHER REMOVE OR PUSH PIPE WRAPPINGBACK
THROUGH HOLE IN PIPINGPLATE BEFORE LINE
SETCONNECTION AND BRAZING.
C
DCONNECTPIPESECONNECT GAUGES AND
START NITROGEN FLOW
FPLACE A WET RAGAGAINST PIPING
PLATE AND AROUND THE SUCTION
LINE CONNECTION.
GBRAZE CONNECTION. ALLOW PIPE TO
COOLBEFORE REMOVINGWETRAG
FROM TXV SENSING BULB AND PIPING
PANELAREA.
NOTE - REFER TO OUTDOOR UNIT INSTALLATION
INSTRUCTIONS FOR REFRIGERANT PIPING SIZE
REQUIREMENTS.
NOTE - REFRIGERANT LINE SETS
SHOULD BE ROUTED TO ALLOW
FILTER ACCESSIBILITY.
NOTE -MCDP* SERIES UNITS USE NITROGEN OR DRY AIR AS A
HOLDING CHARGE. IF THERE IS NO PRESSURE WHEN THE
RUBBER PLUGS ARE REMOVED, CHECK THE COIL FOR LEAKS
BEFORE INSTALLING.
REFER TO INSTRUCTIONS PROVIDED WITH OUTDOOR
UNIT FOR LEAK TESTING, EVACUATINGAND CHARGING
PROCEDURES
FLOW REGULATED NITROGEN (AT 1 TO 2 PSIG)
THROUGH THE REFRIGERATION GAUGE SET INTO THE
VALVE STEM PORT CONNECTION ON THE OUTDOOR
UNIT LIQUID LINE SERVICE VALVE AND OUT OF THE
VALVE STEM PORT CONNECTION ON THE SUCTION
SERVICE VALVE.
PLEASE READ IMPORTANT ISSUES CONCERNING BRAZING
OPERATIONS ON PREVIOUS PAGE BEFORE PROCEEDING.
NOTE - Use silver alloybrazing rods with five or six percent
minimum silver alloy for copper-to-copper brazing, 45
percent alloy for copper-to-brass and copper-to-steel
brazing.
BRAZE
SUCTION
LINE
USE WET RAGS
WHEN BRAZING
SUCTION LINE
Page 8
mrcool.com

After removal of drain pan plug(s), check drain hole(s)
to verify that drain opening is fully open and free of any
debris. Also check to make sure that no debris has
fallen into the drain pan during installation that may plug
up the drain opening.
Connect the main drain and route downward to drain line
or sump. Do not connect drain to a closed waste system.
be connected and routed to a
The following best practices are recommended to ensure
better condensate removal:
•
than both drain connections at drain pan.
•
homeowner will notice drainage.
•
vented and a trap installed. Refer to local codes.
Proper air volume MUST be provided over the evaporator
coil. To ensure that the static pressure is within the proper
range, take a draft gauge reading as follows:
Access panel must be removed before drilling air test
holes.
ABOVE
FINISHED
SPACE?
OVERFLOW DRAIN LINE
ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOTPOSSIBLE TO
ROUTE OVERFLOW DRAIN LINE, INSTALL LOW VOLTAGE
OVERFLOW SWITCH KIT. WIRE KIT TO SHUT DOWN
COMPRESSOR PER INSTRUCTIONS.
NO
YES
CLEAN OUT
VENT
PRESS IN
(DO NOT GLUE)
VENT MUST EXTEND
ABOVE HEIGHT OF
COIL DRAIN PAN BY
TWO INCHES (51 MM)
1” X 3/4” X 3/4”
REDUCING
TEE WITH
PLUG
PVC SCH 40 P- OR
J-TRAP 3/4”
OVERFLOW
DRAIN
OPTIONAL
SAFETY
PAN
FURNACE DRAIN PAN
WHENA COILIS LOCATED ABOVE A FINISHED SPACE, A 3/4” (19.1 MM) SECONDARY DRAIN
LINE MUST BE:
CONNECTED TO SECONDARY DRAIN PAN
OR
CONNECTED TO THE OVERFLOW DRAIN OUTLET OF THE FURNACE DRAIN PAN.
TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES —
GENERALLY, TWO INCHES (51 MM).
DRAIN LINE SHOULD
SLOPE A MINIMUM OF
ONE INCH PER 10
FEET (25 MM PER 3
METERS)
NOTE — WHEN A FURNACE IS LOCATED ABOVE A FINISHED SPACE, THE SECONDARY DRAIN
PAN MUST HAVE A LARGER FOOTPRINT THAN THE FURNACE .
MAIN
DRAIN
TO APPROVED
DRAIN
FOR NEGATIVE PRESSURE COILS (BLOWER
AFTER COIL) TRAPS ARE REQUIRED ON ALL
DRAIN LINES CONNECTED TO COIL.
COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET
AND MALE ADAPTER, TWO-PART DESIGN FOR USE WHERE
OBSTRUCTIONS PREVENT DIRECT THREADING
SECONDARY
DRAIN PAN
2”
(51 MM)
TRAP DEPTH
Page 9 mrcool.com

1. Remove access panel.
2. Drill two 5/16” (8 mm) air test holes in the right front
access panel; hole locations are shown in Figure 6.
Replace the panel.
3. Connect draft gauge. Zero end of draft gauge scale
connects to air entering hole of the coil. Insert gauge
hoses into test holes about 5/16” (8 mm). Seal around
holes with sealant.
4. Turn off power to the outdoor unit, then set the
thermostat for high stage cooling.
1-1/2”
1-1/2”
NOTE: Remove panel
before drilling test holes.
RIGHT FRONT
ACCESS PANEL
1”
1”
5. Table 4 lists the range of air volumes and equivalent
draft gauge readings for this unit. Observe draft gauge
reading. If reading is above required air volume,
decrease blower speed. Refer to furnace wiring
diagram for changing direct drive blower speed. Do not
exceed maximum air volume as indicated in diagram
blower speed table.
6. After required draft gauge readings are obtained,
remove draft lines and seal air test holes.
7. Set the room thermostat to desired temperature.
A trained technician or service agency must perform
maintenance and service on equipment. At the beginning
of each heating or cooling season, indoor coils should be
cleaned.
on coils. These chemicals are not necessary to dissolve
used to dissolve oils and greases, which generally are not
present on most installations.
Do not use alkaline washes to dissolve oxides such as zinc
oxide, aluminum oxide, and iron oxide (rust). These three
oxides are more corrosion-resistant than base metals.
Dissolving or removing them will cause an increase in
corrosion.
cleaning requires the use of acidic or alkaline cleaners,
cleaner from all equipment components. (Be careful
to prevent damage or corrosion of the components
connected to the system or areas surrounding the
equipment being cleaned.)
1. Remove the coil from the cabinet and take the coil to
an appropriate place to clean it.
2. Vacuum or brush the coil to remove matted and
3. If oil deposits are present, spray the coil with ordinary
household liquid detergent. Allow detergent to soften
deposits. Wait 10 minutes.
For units in coastal regions, fresh water will
dissolve salt deposits. (Wash coils with fresh water at
4. Spray the coil at a vertical angle of 30 to 45 degrees
with a constant stream of water at moderate pressure.
A pressure washer with a fan nozzle will work best. Do
not spray the coil from a horizontal direction.
5. Direct the spray so that any debris is washed out of the
coil and base pan. For most residential units, hot water
is not necessary.
coil will require removing parts from the unit, and it
Attempting to blow water through a coil will slow the
6. Replace the coil into the cabinet.
Page 10
mrcool.com

Resistance Resistance Resistance Resistance
Pa Pa Pa Pa
18A .05 12 370 175 .05 12 255 121 24A .05 12 315 150 .05 12 335 157
.08 19 510 240 .07 17 305 144 .09 22 465 220 .10 25 490 231
.10 25 645 305 .09 22 355 167 .14 35 595 280 .15 37 600 284
.15 37 815 385 .12 30 395 186 .20 50 725 345 .20 50 705 332
.20 50 980 465 .15 37 435 205 .25 62 825 390 .25 62 790 373
.25 62 1115 525 .18 44 520 245 .30 75 910 430 .30 75 870 411
.30 75 1250 590 .20 50 600 284 .35 87 1000 470 .35 87 940 444
.35 87 1395 660 .25 62 690 325 .40 100 1080 510 .40 100 1020 481
.40 100 1535 725 .30 75 775 365 .50 125 1225 580 .45 112 1090 514
.45 112 1645 725 .35 86 845 399 .60 150 1370 645 .51 127 1160 547
.50 125 1760 830 .39 97 920 433
.55 137 1870 880 .50 125 1505 711
24B .06 15 400 190 .07 17 400 189 .10 25 600 283 .10 25 600 283
.09 22 500 235 .10 25 500 236 .13 32 700 330 .14 35 700 330
.13 32 600 285 .15 37 600 283 .16 40 800 378 .18 45 800 378
.17 42 700 330 .20 50 700 330 .20 50 900 425 .23 57 900 425
.23 57 800 380 .26 65 800 378 .24 60 1000 472 .27 67 1000 472
.27 67 900 425 .32 80 900 425 .28 70 1100 519 .32 80 1100 519
.33 82 1000 470 .39 97 1000 472 .33 82 1200 566 .38 95 1200 566
.39 97 1100 520 .46 115 1100 519 .38 94 1300 614 .43 107 1300 614
.47 117 1200 565 .54 135 1200 566 .43 107 1400 661 .49 122 1400 661
.05 12 525 245 .05 12 410 194 .06 15 600 285 .07 17 600 283
.08 19 660 310 .08 19 495 233 .08 20 700 330 .10 25 700 330
.10 25 795 375 .10 25 580 273 .10 25 800 380 .13 32 800 378
.15 37 980 465 .15 37 785 371 .13 32 900 425 .17 42 900 425
.20 50 1165 550 .20 50 995 469 .16 40 1000 470 .21 52 1000 472
.25 62 1320 625 .25 62 1155 546 .19 47 1100 520 .25 62 1100 519
.30 75 1475 695 .30 75 1320 624 .22 55 1200 565 .29 72 1200 566
.35 87 1605 760 .35 87 1465 692 .26 65 1300 615 .34 85 1300 614
.40 100 1735 820 .40 100 1610 761 .29 72 1400 665 .38 95 1400 661
.43 107 1805 855 .45 112 1730 816
.46 115 1875 885 .50 125 1850 872
48B .14 35 1200 566 .17 42 1200 566 .05 12 595 280 .05 12 575 271
.16 40 1300 614 .20 50 1300 614 .10 25 860 405 .10 25 820 386
.19 47 1400 661 .23 57 1400 661 .15 37 1060 500 .15 37 995 469
.22 55 1500 708 .26 65 1500 708 .20 50 1235 580 .20 50 1170 551
.25 62 1600 755 .29 72 1600 755 .25 62 1395 655 .25 62 1320 623
.28 70 1700 802 .32 80 1700 802 .30 75 1545 730 .35 75 1445 682
.30 75 1800 850 .36 90 1800 850 .35 87 1675 790 .35 87 1575 744
.34 85 1900 897 .42 105 1900 897 .40 99 1805 850 .40 100 1710 807
.37 92 2000 944 .45 112 2000 944 .45 112 1925 910 .45 112 1825 861
.50 124 2030 960 .50 125 1915 904
Table 4. MCDP* Coil Air Volume and Static Pressure Resistance
Page 11 mrcool.com

Resistance Resistance Resistance Resistance
Pa Pa Pa Pa
.17 42 1395 660 .19 47 1400 661 .17 42 1395 660 .19 47 1400 661
.18 45 1450 685 .20 50 1450 684 .18 45 1450 685 .20 50 1450 684
.19 47 1500 710 .22 55 1500 707 .19 47 1500 710 .22 50 1450 684
.20 50 1545 730 .23 57 1555 733 .20 50 1545 730 .23 57 1555 733
.21 52 1605 755 .24 60 1600 755 .21 52 1605 755 .24 60 1600 755
.22 55 1645 775 .25 62 1645 777 .22 55 1645 775 .25 62 1645 777
.24 60 1700 805 .27 67 1710 807 .24 60 1700 805 .27 67 1710 807
.25 62 1750 825 .28 70 1745 824 .25 62 1750 825 .28 70 1745 824
.27 67 1805 850 .31 77 1800 850 .27 67 1805 850 .31 77 1800 850
.28 70 1845 870 .32 80 1850 874 .28 70 1845 870 .32 80 1850 874
.29 72 1905 900 .33 82 1890 892 .29 72 1905 900 .33 82 1890 892
.30 75 1950 920 .34 85 1950 920 .30 75 1950 920 .34 85 1950 920
.32 80 2000 945 .36 90 2000 944 .32 80 2000 945 .36 90 2000 944
.33 82 2055 970 .38 95 2050 968 .33 82 2055 970 .38 95 2050 968
.35 87 2105 995 .40 100 2105 993 .35 87 2105 995 .40 100 2105 993
.38 94 2150 1015 .43 107 2150 1015 .38 94 2150 1015 .43 107 2150 1015
.39 97 2200 1040 .45 112 2190 1034 .39 97 2200 1040 .45 112 2190 1034
Page 12
mrcool.com
Table 4. MCDP* Coil Air Volume and Static Pressure Resistance

Signature Series
Please read this manual carefully before installation and keep it for future reference.
Consult with the sales agency or manufacturer for details.
This manual suits for next models
14
Table of contents
Popular Industrial Equipment manuals by other brands

WOHLHAUPTER
WOHLHAUPTER Alu-Line Basic D 60 Series operating instructions

ABB
ABB HT573088 Operation manual

RK Rose+Krieger
RK Rose+Krieger RK MonoLine R Assembly instructions

ABB
ABB HT575792 Operation manual

Erskine Attachments
Erskine Attachments Forestry Mulching Mower Operator's manual

SNR
SNR NTN SNOE 200 Series Assembly, servicing and maintenance instructions