Multiform M20/S User manual

- 1 -
M20/S –M40/S Telemetry Outstation
Southern Water Variant V3.3C
A MULTIFORM Product
Designed & Built in the UK

- 2 -
Table of Contents
Safety policy & Mains Connection.
Safety Information….…...………….………………………………………………. 3
Connection and Indicators.
Installation Details………………….………………....……………………………. 4
Initial Power-Up Guide……………...…………………………………..…………. 5
Configuration (Using Configuration Package).
System Tab….….……………….………………………………………….………. 6
Digital Tab…………………….……………………………………………………. 7
Analogue Tab…...………………….………………………………………………. 8
Analogue Totals (Derived Analogues)……...…………….….…………………….. 9
Pseudo Digitals Tab…………………...….……………………………….………. 10
Combinations Tab………...…………..….………….……………………………. 11
Connection Tab…………………….………………………..……………………. 12
Digital Monitor Tab……………….……….……………….…………………….. 13
Analogue Monitor Tab…………………..…………………………………………14
Analogue Total Monitor…...……………………………….……………………... 15
Event Logging………………………...….……………………………….………. 16
Periodic Logging...…………………………………………………………………17
Total Logging……………………………………………………………………....18
Operational Set-Up.
Comms Monitor……………………………………………………………………19
CBM Monitor & About Function………………………………………………….20
DIL Switch Functions…..……………..…………….……………………………. 21
Overview of Modes of Operation...…….…………………………………………. 22
I/O Mapping………………………….……….…………….…………………….. 23
Contact Details.
Contact Details……………………….……….…………….…………………….. 24
Warranty & WEEE…..……….……..……………….……………………25

Multiform M20/M40 Outstation Handbook 11/11/2019
- 3 -
SAFETY INFORMATION
Please read before proceeding with Installation or Commissioning
This unit should only be installed, operated, serviced or repaired by suitable trained or
authorised personnel.
No unauthorised or untrained personnel must open or remove the cover without
isolating the mains supply first.
Before connecting Mains supply check that the 110V/ 240V switch on the PCB is correct
for the voltage applied. Personal injury and/or Permanent damage to the unit are possible
if the incorrect supply is connected. Supply is AC 50Hz, fused at a maximum of 3 Amps.
Connection to the mains supply is via a 4-way connector next to the transformer at the top
of the PCB marked: -
E = Earth Connection (Must be Completed)
N = Neutral
E = Earth
L = Live
Always ensure correct connection before powering, incorrect connection may result in
personal injury and/or component failure.
The mains input is protected within the Unit by a 250mA quick blow 20mm glass fuse.
Replacement must only be carried out with the supply isolated externally, (Only replace
with a fuse of correct value)
Secondary supply is protected by a 250mA SB fuse
Removal of the modem must not be completed until unplugged from the BT socket.
On No account must the unit be installed, commissioned or repaired in adverse weather
conditions i.e., thunder, lightning, Rain etc.
These safety notices are not exhaustive and user must maintain their own safe working
practices.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 4 -
Installation Details
Mounting and Enclosure.
Enclosure is rated at IP65 and is mounted via a mounting tab at each corner of the case.
I/O Connections.
Digital & Analogue inputs are connected to the 3 columns of disconnect terminals towards the bottom of
the PCB. I/O numbers are clearly marked on the PCB.
The First two columns are for digital inputs (Volt Free) and the third column is for Analogue inputs
Digital Digital Analogue
IP1
IP2
IP3
IP4
IP5
IP6
IP7
IP8
COMMON
IP17
IP18
IP19
IP20
IP21
IP22
IP23
IP24
COMMON
ANA 1 +
ANA 1 –
ANA 2 +
ANA 2 –
ANA 3 +
ANA 3-
ANA 4 +
ANA 4 –
GROUND
IP9
IP10
IP11
IP12
IP13
IP14
IP15
IP16
COMMON
IP25
IP26
IP27
IP28
IP29
IP30
IP31
IP32
COMMON
ANA 5 +
ANA 5 –
ANA 6 +
ANA 6 –
ANA 7 +
ANA 7-
ANA 8 +
ANA 8 –
GROUND
Notes:
Digital Inputs. The Inputs are deemed to be closed (1 shown on display) when a connection less
than 1K is present.
Analogue Inputs. All Inputs are referenced to Ground. An Analogue Isolator must be fitted if mixed
Commons are used.
External 12V For powering external sensors (Fused @ 200mA)
Cnt 1 Fast Count Input 1
Cnt 2 Fast Count Input 2 (Only fitted to M40)
12V
0V
Cnt 1
Cnt 2

Multiform M20/M40 Outstation Handbook 11/11/2019
- 5 -
Initial Power up Guide
1. Ensure all I/O and supply connections have been completed and checked before proceeding.
2. Check all the DIL switches next to the LED’s are OFF (Towards Left side of the PCB)
3. Ensure 110/240V switch is selected correctly. Switch the mains supply on and connect the battery
leads, the unit will now start its power up sequence.
4. Observe the LED’s toward the centre of the PCB.
Green PWR LED should be illuminated indicating the presence of the system 5V.
Green WDOG LED will flash rapidly for 5 seconds upon power up whilst the unit checks for bootable
code. The LED will then blink every four seconds indicating a healthy heartbeat.
Red TX & RX LED’s will strobe whilst either the PSTN or GSM modem is set-up.
Green DCD LED will illuminate whilst PSTN or GSM modems are connected with a remote modem.
After power up and boot code is loading (WDOG LED flashing rapidly for 5 seconds) the display will
show the Multiform Start-up banner followed by the Site Name, time & date (This may be corrupt if no
configuration is loaded).
Communications with either a GSM or PSTN modem is checked. If no modem is found the unit will
display “Modem Error” for 5 seconds then revert to standard I/O display.
If a GSM modem is found the display will show “Searching” followed by “Registered” then again revert
to I/O display
A PSTN modem will show “Connected” followed by the I/O display.
The top line of the display indicates digital inputs 1-16 followed by the Mains & Battery status. The
bottom line displays scaled Analogue Input values scrolling every 4 seconds.
For Extended I/O units the second bank of 16 digital inputs is displayed (alternately with bank 1) every 4
seconds, with ‘#2’ being shown after the digital inputs to indicate the second bank. i.e. Inputs 17-32
The normal state for both Mains & Battery is indicated by a “1”, with Battery status followed by Mains.
Note: There is a small time delay of 4 seconds for the mains failed flag to change on power failure due
to voltage within the reservoir capacitor.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 6 -
Configuration
System Tab
M20/M40 units are configured using the configuration tool supplied by Multiform Design.
Note: Communications with the M20/40 is controlled via the Outstation Id. Therefore the ID selected on
the configuration package must match that of the Outstation
If you are unsure of the outstation Site ID, upload and save the configuration as standard.
Options for setting the following items: - Site Name, Site ID, Dial Out Telephone Numbers, Model Type,
Time & Date and Engineer On Site Input selection.
Selecting the ‘Outstation Model’ will automatically select the correct communication options and
available I/O.
SMS Duty-Roster. Phone numbers, quantity of officers and day and time of changeover. (See SMS
Section, page 17, for more details).
‘Log start of day’. Set as required to enable daily totals to be calculated.
‘Outstation Callback’. Test function to cause the outstation to dial out to the first number on the dial out
list for testing purposes.
System Counters. Monitoring communication and outstation resets.
Once user defined data has been entered
Select ‘File’ and ‘Save As’ to save your configuration before proceeding.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 7 -
Digital Tab
Input Name Description of Input monitored Wet Well
On Text Text to show when the input is On (Shorted to common) Normal
Off Text Text to show when the input is Off (Open Circuit) High
Alarm Dial Out To select if the Outstation starts a dial out Both
Alarm Enable Enable this input to cause an alarm dial out Select as required
On Time Delay before generating an alarm in seconds (Max 8640) 30
Off Time Delay before generating an alarm in seconds (Max 8640) 30
Counter Start Selects Edge event to count on On Closing
Event Log Enable Event Log to record ON/OFF changes Select as required
Use the ‘Next’ tab for further digital inputs.
When digital inputs selections are completed click the ‘Analogue’ tab.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 8 -
Analogue Tab
Input Name Description of Input being monitored Wet Well
Units Units of measurement Metres
Input Source Select Source of data to be monitored Count
Scale Factor and Offset This is for scaling Y=mX+c format 0.7 & -1.2
Calculate Self Scaling Button See Fig. Below.
Hysteresis Hysteresis required 0.3
Display Display on LCD Enabled
Log period Select logging period (mins) Pull down list
Log En Enable periodic logging on this channel Select as required
Sample Period Number of samples for averaging Pull down list
Enable Select to make trip value active Select as required
Analogue Trip Values Enter required trip (alarm) level 1.2
1, To set up analogue scaling enter first the range 0/4-20mA
2, Enter the Upper Limit & Lower Limits, Press the “=” and
the Scale Factor & Offset will be automatically in filled.
3, Click “Use Values” to enter in the configuration program
.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 9 -
Notes:
If any Analogue Trip values are enabled ensure that the ‘Pseudo Digital’ tab is selected to configure the
alarm dial out and time delay functions for the selected Trips.
When changing logging parameters ensure that the logs are cleared. See Logging section
Use the ‘Next’ tab for Analogue Totals.
Analogue Totals (Derived Analogues)
Input Source Source of data for logging Select as required
Units Unit of Measurement of input source For display only
Conditional Input Digital I/P to be active to enable logging Select Input as required
Mask Add Conditional I/P to ‘Pump Run Mask’ Select as required
to enable solo pump run conditions.
Scale Factor Scale (multiplication) factor to be applied Enter as required
Display ‘Check’ to display instantaneous log value Select as required
on Masterstation (displays previous days
log value otherwise).
Total Units Unit of measurement for logged data Enter as required
Log En Enable logging Select as required
Flow Meter I/P Select CBM flow meter Pulse or mA

Multiform M20/M40 Outstation Handbook 11/11/2019
- 10 -
Pseudo Digitals Tab
Programme the internal Mains & Battery inputs the same as
standard Digital Inputs.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 11 -
Combinations Tab
First Digital I/P Select First combined input Inputs are digital or analogue trips
Invert Tick if input to be inverted for result. I.e. Off
Select Digital I/P I/P 2, 3 & 4 Inputs are digital or analogue trips
Select AND / OR Select combination attributes AND or OR
Alarm Enable Select if Alarm Dial-out is required

Multiform M20/M40 Outstation Handbook 11/11/2019
- 12 -
The configuration is now ready to upload to the unit. Ensure that the configuration is now saved using
the ‘File’ and ‘Save’ functions. Connection Tab
Ensure that you Connect the Outstation local lead or Modem to the correct port
Select the correct method of connection required. I.e. Local or Remote and which comm. port to use.
Comms parameters are saved in a small file so that selections are not required after every restart of the
M20/M40 config package.
When selected press the ‘Connect’ button
The bottom of the screen will now show connected and the baud rate settings.
Now use the ‘Config’ tab to select whether to ’Upload’ or ’Download’ a configuration.
Once the configuration is loaded you can monitor the Digital & Analogue inputs using the specified tab.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 13 -
Digital Monitor Tab
All the digital I/O details, including name, status & counts are displayed on the left with the digital values
shown on the right. The two rows showing real and timed values (The ‘real’ values change as the inputs
change whereas the ‘filtered’ values only change after their On/Off time delays have elapsed).
The Outstation Mains, Battery and Configuration status are also shown.
Counter Number of times input has changed state (Counts on either edge as per configuration).
Daily Count Number of counts in the last 24Hr period as set by day start on system configuration.
Minutes Run Minutes active in the last 24Hr period as set by day start on system configuration.
The data is snapshot and must be updated using the ‘Update Single’ button.
For timed updates click the up/down tabs to update at
10, 20, 30 & 60 seconds for commissioning purposes.
To hold the LCD display on a particular bank of inputs use the “Scroll Toggle” to hold or continue
rotation of the display.
Note: The counter values only increment after their filter time has been exceeded.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 14 -
Analogue Monitor Tab
A graphical bar indicates the read analogue inputs with a range of 0-20mA.
The values marked at the beginning and the ends of the bar are the scaled values.
Trip markers are placed along the analogue scale indicating all enabled trip values, the numerical values
of which are shown in the right hand column.
This page is updated in the same way as for the Digital status page, refresh by pressing the ‘Update
Single’ button or by selecting the auto refresh option using the up/down buttons.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 15 -
Analogue Total Monitor
Used to monitor Analogue Totals to aid commissioning of system.
Shows results of any Analogue Total points configured.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 16 -
Logging Tab
Event Logging
This Tab is used to Retrieve, View, Export & Print stored Event or Periodic data within the Outstation.
Use the ‘Event Log’, ‘Point Log’ or “Total Logs” buttons to select the required type of archived data.
For Event logging click the ‘Event Log Date’ control to select the start date for retrieval.
Click ‘Update Event Log’ button to start retrieval.
To store the log as an Excel spreadsheet, check the ‘Save’ checkbox then click ‘Update Event Log’
button.
The ‘Clear Event Log’ button can be used to erase the stored archive.
The M20/M40 will store 3968 time/date stamped events.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 17 -
Periodic Point Logging
To update Point log information select the required Tab i.e. ‘Ana 1’.
Select the date required from the ‘Point Log Date’ control.
Then click ‘Update Point Log’ button.
Note: Only Analogue channels that have been configured as active logging channels will have active
(selectable) tabs.
The ‘Clear Point Log’ button can be used to erase the stored archives.
The data will be displayed in a scrollable window. Repeat for all logged channels required.
M20/M40 unit will store 512 periodic logs per Analogue channel. For a standard 15 minute logging
period this equates to over 5 days of stored logs.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 18 -
Total Logging
To update Total log information select the required Tab i.e. ‘Total 1’.
Then click ‘Update Total Log’ button.
Note: Only Analogue Total channels that have been configured as active logging channels will have
active (selectable) tabs.
The ‘Clear Total Log’ button can be used to erase the stored archives.
The data will be displayed in a scrollable window. Repeat for all logged channels required.

Multiform M20/M40 Outstation Handbook 11/11/2019
- 19 -
COMMS MONITOR Tab
Used for monitoring communication via the PSTN or GSM modem ports.
Screen shot shows a typical Dial Out
Sequence & communications with a
Master Station .
Note. Some Master-Stations do not have
the clock sync function enabled
Screen shot shows a typical Dial In
Sequence & communications with a
Master Station .
Note. On a dial in request Event &
Periodic log is requested.
This will increase the overall time On-
Line.
“CLEAR” Clears the text
“HIDE” Returns to Normal configuration screen

Multiform M20/M40 Outstation Handbook 11/11/2019
- 20 -
CBM MONITOR
To display specific CBM data in an easy to read format.
Updating the Status IE, Digital Data click the “Update Status” Button
To update Totals and Analogue Values click the “Update Totals” Button
For Instantaneous Values, Select the “Display All” option then “Update Totals”
There may be a small time delay in updating the totals in Instantaneous modes due to scaling and
formatting functions.
Selecting the display all function has no effect on the returned data to scope.
This manual suits for next models
1
Table of contents
Popular Network Hardware manuals by other brands

ZinWave
ZinWave UNITIVITY 5000 user manual

Dveo
Dveo OnRamp/IP quick start guide

Adaptec
Adaptec LSM-FC2002 - Loop Resiliency And SES Module... installation guide

Videoswitch
Videoswitch Vi-R5216L Quick operation guide

ICP DAS USA
ICP DAS USA PMC-5151 quick start

TelcoBridges
TelcoBridges Tmedia TMP800 installation guide