MYPIN TA Series User manual

TA Series of Temperature Controller
Instruction Manual
Thank you for selecting our controller!
Before operating this instrument, please carefully read this
manual and fully understand its contents. If any probroms,
please contact our sales or distributors whom you buy from.
This manual is subject to change without prior notice.
Warning
Please do not connect your controller to main power until
all of your wiring is complete and checked.Otherwise elec-
trical shock, fire or malfunction may result.
Do not wire when the power is on. Do not turn on the
power supply when cleaning this instrument. Do not
disassemble, repair or modify the instrument. This may
cause electrical shock, fire or malfunction.Use this instru-
ment in the scope of its specifications. Otherwise fire or
malfunction may result. The internal relay’s service life is
greatly dependent on the current and voltage switched by
its contacts. Over-stressing the contacts with too much
current or switching vltage above the contact rating will
greatly shorten the life of the relay.
Applications
TAseries of temperature controller is available for many TC
or RTD input, adopt some advanced techonology such multi
digital filter circuit, autotune PID, fuzzy PID that make it
is very precise, stable, strong anti-interference and
simple operation. The instrument is widely applied to
Panel
This instrument is not rated foroutdoor use and should be used in
a climate controlled environment.
Installing in an environment heavy laden with dust or contain-
ing corrosive gasses will cause your controller to fail.
Do not install near water spray, oil spray, or in an environ-
ment where water can condense inside the unit.
Avoid running power leads in parallel with high voltage or
heavy current carrying conductors that may induce high
voltages into the unit. If you must run incoming power
near high voltage or heavy current carrying conductors, we
suggest that you run the power inside metal conduit that is
grounded on one end only.
If installing in an electrically noisy environment, we sug-
gest that you protect the unit with a current suppressor or
noise filter.
Power supply 90-260V AC/DC 50/60Hz
Consumption ≤ 5VA
Display range -199~1800℃
Accuracy 0.3%F.S ± 2digit
Sampling cycle
≤ 300ms
Main output RELAY:normal open AC 250V/5A DC 30V/5A COS¢=1
SSR/LOGIC:24V DC ± 2V/ 20mA
Specifications
RELAY: normal open AC 250V/5A DC 30V/5A COS¢=1
SSR/LOGIC:24V DC ± 2V/ 30mA
K 0~1200℃(negtive temp customized)
J 0~1200℃(negtive temp customized)
T -150~400℃ (customized only)
S 0~1600℃
Rt Pt100 -199~600℃
Cu50 -50~150℃
Alarm
Input
T/C
Withstand voltage strength
Others Please mention when ordering
1500V Rms
(Between power terminal and the housing)
Min 50M
Ω(
500VDC
)
(Between power terminal and the housing)
Environment temperature
Storage temperature
Environment humidity
Weight
0~50℃
-10~60℃
35~85%RH
Insulation resistance
MountingandSizes
+
+
+
↑
D
↑
B
A
↑
↑
E
↑
↑
C
↑
GH
Sizes
Model
TA4
TA6
TA9
TA7
44.5+0.5 45+0.5 65 65 48 48 8 80
43.5+0.5 91+0.5 65 115 48 96 12 80
91+0.5 91+0.5 95 95 96 96 12 80
67.5+0.5 67.5+0.5 115 115 72 72 12 80
A B C D E F G H
Parameter Setting
Setting steps
A: Select the parameter you want to modify
B: Press the << /AT key to select the digit you
want to modify
C: Press key and key to modify the numerals
D: Press SET key to confirm
Power on
↓
↓
Displays temperature unit
↓
Input UP limit
3S
3S
3S
Measured displaying(PV)
Set displaying(SV)
↓
Shift and flashes
Modify SV preset value
SET
Stop flashing
↓
Confirm
Self-check
All LED on
Input type
≤350g
E 0~1000℃
Caution
TA8 91+0.5 43.5+0.5 65 115 96 48 12 80
>>
>
>
Input LOW limit
↓
In Non-autotune estate, press and hold / key for more
than 5 seconds can enter/quit the under menu: (Normally
the program will refresh the value of the parameters
by itself, the user no need make modifications. )
↓
1
>>
>
>
Low display value, it is adjust-
able by the input signal.
eg. K type 0-800C, LSP=0.0
automation systems of mechanism, chemical industrial,
chinaware, light industrial, metallurgy and petroleum chemical
industrial. It is also applied to the production line of foodstuff,
packing, printing, dry machine, metal heat process equipment
to control the temperature.
Up display value, it is adjustable
by the input signal.
eg. K type 0-800C, USP=100.0
↓AL1 hysteresis setting value.
Range ±90, factory setting 1.0
SET
↓
⑦
↑
℃
O U T 1 O U T 2 ATAL
SET
TA
>
>
>>
/AT
PV
SV
①
②
③
④
→
→
→
↑↑
⑥⑤
①. PV / parameter symbols
②. SV / parameters set value
③. Indication lamps
OUT1: Heating/Main control output lamp
On: Output Off: No output
OUT2:
Alam2 output lamp
On: Output Off: No output
AT: On: Autotune Off: Non-autotune
AL: Alarm 1 lamp On: Alarm Off: No Alarm
④.Set key Parameter Setting/Changing
⑤.Shift/Autotune key
Press this key to shift digit of parameter value setting.
Or hold this key for more than 3s can enter/quit autotune
estate. When enter autotune estate, AT lamp on. When
quit autotune estate, AT lamp off.
⑥.Up key ⑦.Down key
TA□□ - □□□□
Models
Input signals:Default: K,J,E, S,PT100,Cu50
1:4-20mA/0-10V/0-75mV F: others
OUT2/AL2:R: RELAY S: SSR/Logic
T:SCR N:None
OUT1: I: 4-20mA V:0-10V DC
R: RELAY S: SSR/Logic
AL1:R:RELAY S:SSR/Logic T:SCR
Power supply: Default:90-260V AC/DC
E: 24VDC or 18-30V AC/DC
Sizes 4: 48H ×48W 6: 48H ×96W
TA series of temperature controller
7: 72H ×72W 8: 96H ×48W 9: 96H ×96W
>>
>
>
/AT
→
F
+
↑
↑
MYPIN
SET
SET
TEMPERATURE CONTROLLER
>
>

TA Series of Temperature Controller
Instruction Manual
Thank you for selecting our controller!
Before operating this instrument, please carefully read this
manual and fully understand its contents. If any probroms,
please contact our sales or distributors whom you buy from.
This manual is subject to change without prior notice.
Warning
Please do not connect your controller to main power until
all of your wiring is complete and checked.Otherwise elec-
trical shock, fire or malfunction may result.
Do not wire when the power is on. Do not turn on the
power supply when cleaning this instrument. Do not
disassemble, repair or modify the instrument. This may
cause electrical shock, fire or malfunction.Use this instru-
ment in the scope of its specifications. Otherwise fire or
malfunction may result. The internal relay’s service life is
greatly dependent on the current and voltage switched by
its contacts. Over-stressing the contacts with too much
current or switching vltage above the contact rating will
greatly shorten the life of the relay.
Applications
TA series of temperature controller is available for many TC
or RTD input, adopt some advanced techonology such multi
digital filter circuit, autotune PID, fuzzy PID that make it
is very precise, stable, strong anti-interference and
simple operation. The instrument is widely applied to
Panel
This instrument is not rated foroutdoor use and should be used in
a climate controlled environment.
Installing in an environment heavy laden with dust or contain-
ing corrosive gasses will cause your controller to fail.
Do not install near water spray, oil spray, or in an environ-
ment where water can condense inside the unit.
Avoid running power leads in parallel with high voltage or
heavy current carrying conductors that may induce high
voltages into the unit. If you must run incoming power
near high voltage or heavy current carrying conductors, we
suggest that you run the power inside metal conduit that is
grounded on one end only.
If installing in an electrically noisy environment, we sug-
gest that you protect the unit with a current suppressor or
noise filter.
Power supply 90-260V AC/DC 50/60Hz
Consumption ≤ 5VA
Display range -199~1800℃
Accuracy 0.3%F.S ± 2digit
Sampling cycle
≤ 300ms
Main output RELAY:normal open AC 250V/5A DC 30V/5A COS¢=1
SSR/LOGIC:24V DC ± 2V/ 20mA
Specifications
RELAY: normal open AC 250V/5A DC 30V/5A COS¢=1
SSR/LOGIC:24V DC ± 2V/ 30mA
K 0~1200℃(negtive temp customized)
J 0~1200℃(negtive temp customized)
T -150~400℃ (customized only)
S 0~1600℃
Rt Pt100 -199~600℃
Cu50 -50~150℃
Alarm
Input
T/C
Withstand voltage strength
Others Please mention when ordering
1500V Rms
(Between power terminal and the housing)
Min 50M
Ω(
500VDC
)
(Between power terminal and the housing)
Environment temperature
Storage temperature
Environment humidity
Weight
0~50℃
-10~60℃
35~85%RH
Insulation resistance
MountingandSizes
+
+
+
↑
D
↑
B
A
↑
↑
E
↑
↑
C
↑
GH
Sizes
Model
TA4
TA6
TA9
TA7
44.5+0.5 45+0.5 65 65 48 48 8 80
43.5+0.5 91+0.5 65 115 48 96 12 80
91+0.5 91+0.5 95 95 96 96 12 80
67.5+0.5 67.5+0.5 115 115 72 72 12 80
A B C D E F G H
Parameter Setting
Setting steps
A: Select the parameter you want to modify
B: Press the << /AT key to select the digit you
want to modify
C: Press key and key to modify the numerals
D: Press SET key to confirm
Power on
↓
↓
Displays temperature unit
↓
Input UP limit
3S
3S
3S
Measured displaying(PV)
Set displaying(SV)
↓
Shift and flashes
Modify SV preset value
SET
Stop flashing
↓
Confirm
Self-check
All LED on
Input type
≤350g
E 0~1000℃
Caution
TA8 91+0.5 43.5+0.5 65 115 96 48 12 80
>>
>
>
Input LOW limit
↓
In Non-autotune estate, press and hold / key for more
than 5 seconds can enter/quit the under menu: (Normally
the program will refresh the value of the parameters
by itself, the user no need make modifications. )
↓
1
>>
>
>
Low display value, it is adjust-
able by the input signal.
eg. K type 0-800C, LSP=0.0
automation systems of mechanism, chemical industrial,
chinaware, light industrial, metallurgy and petroleum chemical
industrial. It is also applied to the production line of foodstuff,
packing, printing, dry machine, metal heat process equipment
to control the temperature.
Up display value, it is adjustable
by the input signal.
eg. K type 0-800C, USP=100.0
↓AL1 hysteresis setting value.
Range ±90, factory setting 1.0
SET
↓
⑦
↑
℃
O U T 1 O U T 2 ATAL
SET
TA
>
>
>>
/AT
PV
SV
①
②
③
④
→
→
→
↑↑
⑥⑤
①. PV / parameter symbols
②. SV / parameters set value
③. Indication lamps
OUT1: Heating/Main control output lamp
On: Output Off: No output
OUT2:
Alam2 output lamp
On: Output Off: No output
AT: On: Autotune Off: Non-autotune
AL: Alarm 1 lamp On: Alarm Off: No Alarm
④.Set key Parameter Setting/Changing
⑤.Shift/Autotune key
Press this key to shift digit of parameter value setting.
Or hold this key for more than 3s can enter/quit autotune
estate. When enter autotune estate, AT lamp on. When
quit autotune estate, AT lamp off.
⑥.Up key ⑦.Down key
TA□□ - □□□□
Models
Input signals:Default: K,J,E, S,PT100,Cu50
1:4-20mA/0-10V/0-75mV F: others
OUT2/AL2:R: RELAY S: SSR/Logic
T:SCR N:None
OUT1: I: 4-20mA V:0-10V DC
R: RELAY S: SSR/Logic
AL1:R:RELAY S:SSR/Logic T:SCR
Power supply: Default:90-260V AC/DC
E: 24VDC or 18-30V AC/DC
Sizes 4: 48H ×48W 6: 48H ×96W
TA series of temperature controller
7: 72H ×72W 8: 96H ×48W 9: 96H ×96W
>>
>
>
/AT
→
F
+
↑
↑
MYPIN
SET
SET
TEMPERATURE CONTROLLER
>
>

TA Series of Temperature Controller
Instruction Manual
Thank you for selecting our controller!
Before operating this instrument, please carefully read this
manual and fully understand its contents. If any probroms,
please contact our sales or distributors whom you buy from.
This manual is subject to change without prior notice.
Warning
Please do not connect your controller to main power until
all of your wiring is complete and checked.Otherwise elec-
trical shock, fire or malfunction may result.
Do not wire when the power is on. Do not turn on the
power supply when cleaning this instrument. Do not
disassemble, repair or modify the instrument. This may
cause electrical shock, fire or malfunction.Use this instru-
ment in the scope of its specifications. Otherwise fire or
malfunction may result. The internal relay’s service life is
greatly dependent on the current and voltage switched by
its contacts. Over-stressing the contacts with too much
current or switching vltage above the contact rating will
greatly shorten the life of the relay.
Applications
TA series of temperature controller is available for many TC
or RTD input, adopt some advanced techonology such multi
digital filter circuit, autotune PID, fuzzy PID that make it
is very precise, stable, strong anti-interference and
simple operation. The instrument is widely applied to
Panel
This instrument is not rated foroutdoor use and should be used in
a climate controlled environment.
Installing in an environment heavy laden with dust or contain-
ing corrosive gasses will cause your controller to fail.
Do not install near water spray, oil spray, or in an environ-
ment where water can condense inside the unit.
Avoid running power leads in parallel with high voltage or
heavy current carrying conductors that may induce high
voltages into the unit. If you must run incoming power
near high voltage or heavy current carrying conductors, we
suggest that you run the power inside metal conduit that is
grounded on one end only.
If installing in an electrically noisy environment, we sug-
gest that you protect the unit with a current suppressor or
noise filter.
Power supply 90-260V AC/DC 50/60Hz
Consumption ≤ 5VA
Display range -199~1800℃
Accuracy 0.3%F.S ± 2digit
Sampling cycle
≤ 300ms
Main output RELAY:normal open AC 250V/5A DC 30V/5A COS¢=1
SSR/LOGIC:24V DC ± 2V/ 20mA
Specifications
RELAY: normal open AC 250V/5A DC 30V/5A COS¢=1
SSR/LOGIC:24V DC ± 2V/ 30mA
K 0~1200℃(negtive temp customized)
J 0~1200℃(negtive temp customized)
T -150~400℃ (customized only)
S 0~1600℃
Rt Pt100 -199~600℃
Cu50 -50~150℃
Alarm
Input
T/C
Withstand voltage strength
Others Please mention when ordering
1500V Rms
(Between power terminal and the housing)
Min 50M
Ω(
500VDC
)
(Between power terminal and the housing)
Environment temperature
Storage temperature
Environment humidity
Weight
0~50℃
-10~60℃
35~85%RH
Insulation resistance
MountingandSizes
+
+
+
↑
D
↑
B
A
↑
↑
E
↑
↑
C
↑
GH
Sizes
Model
TA4
TA6
TA9
TA7
44.5+0.5 45+0.5 65 65 48 48 8 80
43.5+0.5 91+0.5 65 115 48 96 12 80
91+0.5 91+0.5 95 95 96 96 12 80
67.5+0.5 67.5+0.5 115 115 72 72 12 80
A B C D E F G H
Parameter Setting
Setting steps
A: Select the parameter you want to modify
B: Press the << /AT key to select the digit you
want to modify
C: Press key and key to modify the numerals
D: Press SET key to confirm
Power on
↓
↓
Displays temperature unit
↓
Input UP limit
3S
3S
3S
Measured displaying(PV)
Set displaying(SV)
↓
Shift and flashes
Modify SV preset value
SET
Stop flashing
↓
Confirm
Self-check
All LED on
Input type
≤350g
E 0~1000℃
Caution
TA8 91+0.5 43.5+0.5 65 115 96 48 12 80
>>
>
>
Input LOW limit
↓
In Non-autotune estate, press and hold / key for more
than 5 seconds can enter/quit the under menu: (Normally
the program will refresh the value of the parameters
by itself, the user no need make modifications. )
↓
1
>>
>
>
Low display value, it is adjust-
able by the input signal.
eg. K type 0-800C, LSP=0.0
automation systems of mechanism, chemical industrial,
chinaware, light industrial, metallurgy and petroleum chemical
industrial. It is also applied to the production line of foodstuff,
packing, printing, dry machine, metal heat process equipment
to control the temperature.
Up display value, it is adjustable
by the input signal.
eg. K type 0-800C, USP=100.0
↓AL1 hysteresis setting value.
Range ±90, factory setting 1.0
SET
↓
⑦
↑
℃
O U T 1 O U T 2 ATAL
SET
TA
>
>
>>
/AT
PV
SV
①
②
③
④
→
→
→
↑↑
⑥⑤
①. PV / parameter symbols
②. SV / parameters set value
③. Indication lamps
OUT1: Heating/Main control output lamp
On: Output Off: No output
OUT2:
Alam2 output lamp
On: Output Off: No output
AT: On: Autotune Off: Non-autotune
AL: Alarm 1 lamp On: Alarm Off: No Alarm
④.Set key Parameter Setting/Changing
⑤.Shift/Autotune key
Press this key to shift digit of parameter value setting.
Or hold this key for more than 3s can enter/quit autotune
estate. When enter autotune estate, AT lamp on. When
quit autotune estate, AT lamp off.
⑥.Up key ⑦.Down key
TA□□ - □□□□
Models
Input signals:Default: K,J,E, S,PT100,Cu50
1:4-20mA/0-10V/0-75mV F: others
OUT2/AL2:R: RELAY S: SSR/Logic
T:SCR N:None
OUT1: I: 4-20mA V:0-10V DC
R: RELAY S: SSR/Logic
AL1:R:RELAY S:SSR/Logic T:SCR
Power supply: Default:90-260V AC/DC
E: 24VDC or 18-30V AC/DC
Sizes 4: 48H ×48W 6: 48H ×96W
TA series of temperature controller
7: 72H ×72W 8: 96H ×48W 9: 96H ×96W
>>
>
>
/AT
→
F
+
↑
↑
MYPIN
SET
SET
TEMPERATURE CONTROLLER
>
>

TA Series of Temperature Controller
Instruction Manual
Thank you for selecting our controller!
Before operating this instrument, please carefully read this
manual and fully understand its contents. If any probroms,
please contact our sales or distributors whom you buy from.
This manual is subject to change without prior notice.
Warning
Please do not connect your controller to main power until
all of your wiring is complete and checked.Otherwise elec-
trical shock, fire or malfunction may result.
Do not wire when the power is on. Do not turn on the
power supply when cleaning this instrument. Do not
disassemble, repair or modify the instrument. This may
cause electrical shock, fire or malfunction.Use this instru-
ment in the scope of its specifications. Otherwise fire or
malfunction may result. The internal relay’s service life is
greatly dependent on the current and voltage switched by
its contacts. Over-stressing the contacts with too much
current or switching vltage above the contact rating will
greatly shorten the life of the relay.
Applications
TA series of temperature controller is available for many TC
or RTD input, adopt some advanced techonology such multi
digital filter circuit, autotune PID, fuzzy PID that make it
is very precise, stable, strong anti-interference and
simple operation. The instrument is widely applied to
Panel
This instrument is not rated foroutdoor use and should be used in
a climate controlled environment.
Installing in an environment heavy laden with dust or contain-
ing corrosive gasses will cause your controller to fail.
Do not install near water spray, oil spray, or in an environ-
ment where water can condense inside the unit.
Avoid running power leads in parallel with high voltage or
heavy current carrying conductors that may induce high
voltages into the unit. If you must run incoming power
near high voltage or heavy current carrying conductors, we
suggest that you run the power inside metal conduit that is
grounded on one end only.
If installing in an electrically noisy environment, we sug-
gest that you protect the unit with a current suppressor or
noise filter.
Power supply 90-260V AC/DC 50/60Hz
Consumption ≤ 5VA
Display range -199~1800℃
Accuracy 0.3%F.S ± 2digit
Sampling cycle
≤ 300ms
Main output RELAY:normal open AC 250V/5A DC 30V/5A COS¢=1
SSR/LOGIC:24V DC ± 2V/ 20mA
Specifications
RELAY: normal open AC 250V/5A DC 30V/5A COS¢=1
SSR/LOGIC:24V DC ± 2V/ 30mA
K 0~1200℃(negtive temp customized)
J 0~1200℃(negtive temp customized)
T -150~400℃ (customized only)
S 0~1600℃
Rt Pt100 -199~600℃
Cu50 -50~150℃
Alarm
Input
T/C
Withstand voltage strength
Others Please mention when ordering
1500V Rms
(Between power terminal and the housing)
Min 50M
Ω(
500VDC
)
(Between power terminal and the housing)
Environment temperature
Storage temperature
Environment humidity
Weight
0~50℃
-10~60℃
35~85%RH
Insulation resistance
MountingandSizes
+
+
+
↑
D
↑
B
A
↑
↑
E
↑
↑
C
↑
GH
Sizes
Model
TA4
TA6
TA9
TA7
44.5+0.5 45+0.5 65 65 48 48 8 80
43.5+0.5 91+0.5 65 115 48 96 12 80
91+0.5 91+0.5 95 95 96 96 12 80
67.5+0.5 67.5+0.5 115 115 72 72 12 80
A B C D E F G H
Parameter Setting
Setting steps
A: Select the parameter you want to modify
B: Press the << /AT key to select the digit you
want to modify
C: Press key and key to modify the numerals
D: Press SET key to confirm
Power on
↓
↓
Displays temperature unit
↓
Input UP limit
3S
3S
3S
Measured displaying(PV)
Set displaying(SV)
↓
Shift and flashes
Modify SV preset value
SET
Stop flashing
↓
Confirm
Self-check
All LED on
Input type
≤350g
E 0~1000℃
Caution
TA8 91+0.5 43.5+0.5 65 115 96 48 12 80
>>
>
>
Input LOW limit
↓
In Non-autotune estate, press and hold / key for more
than 5 seconds can enter/quit the under menu: (Normally
the program will refresh the value of the parameters
by itself, the user no need make modifications. )
↓
1
>>
>
>
Low display value, it is adjust-
able by the input signal.
eg. K type 0-800C, LSP=0.0
automation systems of mechanism, chemical industrial,
chinaware, light industrial, metallurgy and petroleum chemical
industrial. It is also applied to the production line of foodstuff,
packing, printing, dry machine, metal heat process equipment
to control the temperature.
Up display value, it is adjustable
by the input signal.
eg. K type 0-800C, USP=100.0
↓AL1 hysteresis setting value.
Range ±90, factory setting 1.0
SET
↓
⑦
↑
℃
O U T 1 O U T 2 ATAL
SET
TA
>
>
>>
/AT
PV
SV
①
②
③
④
→
→
→
↑↑
⑥⑤
①. PV / parameter symbols
②. SV / parameters set value
③. Indication lamps
OUT1: Heating/Main control output lamp
On: Output Off: No output
OUT2:
Alam2 output lamp
On: Output Off: No output
AT: On: Autotune Off: Non-autotune
AL: Alarm 1 lamp On: Alarm Off: No Alarm
④.Set key Parameter Setting/Changing
⑤.Shift/Autotune key
Press this key to shift digit of parameter value setting.
Or hold this key for more than 3s can enter/quit autotune
estate. When enter autotune estate, AT lamp on. When
quit autotune estate, AT lamp off.
⑥.Up key ⑦.Down key
TA□□ - □□□□
Models
Input signals:Default: K,J,E, S,PT100,Cu50
1:4-20mA/0-10V/0-75mV F: others
OUT2/AL2:R: RELAY S: SSR/Logic
T:SCR N:None
OUT1: I: 4-20mA V:0-10V DC
R: RELAY S: SSR/Logic
AL1:R:RELAY S:SSR/Logic T:SCR
Power supply: Default:90-260V AC/DC
E: 24VDC or 18-30V AC/DC
Sizes 4: 48H ×48W 6: 48H ×96W
TA series of temperature controller
7: 72H ×72W 8: 96H ×48W 9: 96H ×96W
>>
>
>
/AT
→
F
+
↑
↑
MYPIN
SET
SET
TEMPERATURE CONTROLLER
>
>

Terminal configurations
(If any changed, please refer to the product showing.)
③ Incorrect Control : If the instrument has been used for a long
time, the user find the temperature is hard to rise up to the set
value, meanwhile the outsidesystem running well, there must be
something wrong with the parameters of the instrument.
The user need to re-autotuning the instrument. If the instrument
lostcontrol,pleasecheckiftheconnectionofthecontroliscorrect.
If external load is shorted, broken, wrong connection or compo-
nents is damaged, it will cause lost control as well.
④Display malfunction : “UUUU”: The input signal exeed
the measured range, or check “USP” value.
ON/OFF control: ▲Set value
←
LO HI
Alarm mode:▲ Set value △ Alarm value AL
LO HI
▲
↑
HYS
▲
Cooling
0:Deviation HI alarm
▲ △
↑←
LO HI
1: Deviatian LO alarm
△ ▲
↑
←
LO HI
2: Absolute value HI alarm
▲ △
↑
←
LO HI
3: Absolute value LO alarm
△ ▲
↑
←
LO HI
4: Section outside alarm △ ▲ △
HI
5: Section inside alarm
△ ▲ △
HI
Malfunction estimate
① No Display : Check all the connection and wiring if it is all
correct.Speciallypayattention tothe power supply terminalsand
signal input ternimals.
②Incorrect Didplay: Check ifthe input signal is conformity with
the selected symbol.
For TC input, please use the relative compensation cable.
For RTD input, please use low impedence cable. The 3 wires
should at the same length.
If all above mentioned is collect , pleaase use parameter
PVF to modify.
Heating ON OFF
Note:
All the factory setting value of deiation alarm is 1.0.
AL2 hysteresis setting value.
Range ±90, factory setting 1.0
↓
Password setting.
Factory setting 015
Decimal point setting:
0: INT display 1: One decimal point
↓
↓
↓
↓
↓
↓
↓
HOLD SET >3 S
↓
↓
↓
------------------------------------------
AL1 set range: –1999-9999
AL1 mode:
0: Deviation HI alarm 1: Deviation LO alarm
2: PV HI alarm 3: PV LO alarm
4: SV-PV > AL1 alarm 5: SV-PV <AL1 alarm
6: TC brokenalarm, 7:The first Low won’t alarm
The factory setting is 2
AL2 mode: The same as AL1.
Offset value,range: ±100.
Display valuePV = Measured value - PVF
Input signal selection
stands for K, J, E, S,Pt100,Cu50 or mA/V/mV
The factory setting is K
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
Integral time range 0.1-3600.
I=OFF means cancel integral time.
Derivative time range 0.1-3600. D=OFF means
cancel derivative time.
AL2 set range:–1999-9999.
↓
↓
↓
↓
↓
↓
Control hysteresis, range: ±100.
It is not available when P ≠OFF
Control Cycle Time(adjust to best fit your process)
Recommended starting settings: Relaly = 020sec
SSR =001sec. 4-20mA = 000 sec.
Control directions: HEAt: heating
COOL: cooling
Parameter lock code setting. LcK=000
means unlocked. LcK=010 means locked.
Temperature unit. C: ℃degree,
F: F degree.
2
TA6/TA8/TA9 are subject to the drawing
on the product.
Only function for 4-20mA/0-10V
means PID control;
means 4-20mA/0-10V analog output
High analog output(when available)
eg. 10-100℃for 4-20mA output, trH=100
Low analog output (when available)
eg. 10-100℃for 4-20mA output, trL=10
5
4
3
2
1 0
9
8
6
7
1
1 2
1 1
+
-
TC/mV
←
+
-
+
-
SSR
1 2
1 1
SSR
4
3
←
+
-
TA7
90-260V AC/DC
7
4
3
2
1 3
1 2
1 0
1 1
1A
B
B
+
-
5
6
9
8
1 8
1 7
NC
NO
OUT2/AL2
T1
G
▲
7
9
T2
4
3
+
-
+
-8
7
1 5
1 4
1 6
T1
G
▲
8
6
T2
RTD
7
6
3
2
1 3
1 2
1 1
9
1 0
1
A
B
B
AL1
4
8
1 5
1 4
5
1 6
2 4
2 3
2 2
2 1
2 0
1 9
1 8
1 7
TC
COM
OUT1
6
8
+
-
4-20mA
Application examples
1.Relay output control (for TA7)
Power supply
Heating cord
Heating
equipment
5
4
8
7
6
2
1
16
15
14
12
11
10
17
J-1
FUSE
AL1
OUT1
C
R
J
←
90-260V AC
3
13
←
P t
NO
NC
918
RTD
▲
↑
↑
↓
OFF ON
HYS
HY
HY
OFF ON
HY
ON OFF
OFF ON
HY
ON OFF
ON OFF ON
OFF ON OFF
SSR
SSR
4-20mA
TC
AL1
RTD
Relay
Relay
OUT1
90-260V AC/DC
SSR
AL1
Relay
OUT1
4-20mA
RTD
TA4
AL2
A
B
B
90-260V AC/DC
COM
NC
NO
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
Note:
Please operate according to the process in this instruc
tion manual. Press <</AT key2s to enter auto-tune mode,
AT lamp ON, it goes off when auto-tuned.
In most cases you should start-out by placing your con
troller in auto-tune mode. Once auto-tuned, your con
trollers should not require additional auto-tune cycle if
the environment its working in changes little. If your
controllers is being used to heat or cool a load with a large
thermal mass, then the auto-tuned values need to be re
duced by 5% -10%.
The CtL setting.In most cases our control cycle should be
set to 10-20 seconds. For heating or coolin a load with a
large thermal mass, the value should be set to 30-40
seconds. If you are using a controller with a relay, setting
longer values will help to extend the life of your relay
contacts. Unless your process dictates longer cycle times,
the value should be set to 1-3 seconds to non-relay(SSR)
controls.The value should be set to 000 if 4-20mA cur
rent controls.
7
+
8
SSR
-

Terminal configurations
(If any changed, please refer to the product showing.)
③ Incorrect Control : If the instrument has been used for a long
time, the user find the temperature is hard to rise up to the set
value, meanwhile the outsidesystem running well, there must be
something wrong with the parameters of the instrument.
The user need to re-autotuning the instrument. If the instrument
lostcontrol,pleasecheckiftheconnectionofthecontroliscorrect.
If external load is shorted, broken, wrong connection or compo-
nents is damaged, it will cause lost control as well.
④Display malfunction : “UUUU”: The input signal exeed
the measured range, or check “USP” value.
ON/OFF control: ▲Set value
←
LO HI
Alarm mode:▲ Set value △ Alarm value AL
LO HI
▲
↑
HYS
▲
Cooling
0:Deviation HI alarm
▲ △
↑←
LO HI
1: Deviatian LO alarm
△ ▲
↑
←
LO HI
2: Absolute value HI alarm
▲ △
↑
←
LO HI
3: Absolute value LO alarm
△ ▲
↑
←
LO HI
4: Section outside alarm △ ▲ △
HI
5: Section inside alarm
△ ▲ △
HI
Malfunction estimate
① No Display : Check all the connection and wiring if it is all
correct.Speciallypayattention tothe power supply terminalsand
signal input ternimals.
②Incorrect Didplay: Check ifthe input signal is conformity with
the selected symbol.
For TC input, please use the relative compensation cable.
For RTD input, please use low impedence cable. The 3 wires
should at the same length.
If all above mentioned is collect , pleaase use parameter
PVF to modify.
Heating ON OFF
Note:
All the factory setting value of deiation alarm is 1.0.
AL2 hysteresis setting value.
Range ±90, factory setting 1.0
↓
Password setting.
Factory setting 015
Decimal point setting:
0: INT display 1: One decimal point
↓
↓
↓
↓
↓
↓
↓
HOLD SET >3 S
↓
↓
↓
------------------------------------------
AL1 set range: –1999-9999
AL1 mode:
0: Deviation HI alarm 1: Deviation LO alarm
2: PV HI alarm 3: PV LO alarm
4: SV-PV > AL1 alarm 5: SV-PV <AL1 alarm
6: TC brokenalarm, 7:The first Low won’t alarm
The factory setting is 2
AL2 mode: The same as AL1.
Offset value,range: ±100.
Display valuePV = Measured value - PVF
Input signal selection
stands for K, J, E, S,Pt100,Cu50 or mA/V/mV
The factory setting is K
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
Integral time range 0.1-3600.
I=OFF means cancel integral time.
Derivative time range 0.1-3600. D=OFF means
cancel derivative time.
AL2 set range:–1999-9999.
↓
↓
↓
↓
↓
↓
Control hysteresis, range: ±100.
It is not available when P ≠OFF
Control Cycle Time(adjust to best fit your process)
Recommended starting settings: Relaly = 020sec
SSR =001sec. 4-20mA = 000 sec.
Control directions: HEAt: heating
COOL: cooling
Parameter lock code setting. LcK=000
means unlocked. LcK=010 means locked.
Temperature unit. C: ℃degree,
F: F degree.
2
TA6/TA8/TA9 are subject to the drawing
on the product.
Only function for 4-20mA/0-10V
means PID control;
means 4-20mA/0-10V analog output
High analog output(when available)
eg. 10-100℃for 4-20mA output, trH=100
Low analog output (when available)
eg. 10-100℃for 4-20mA output, trL=10
5
4
3
2
1 0
9
8
6
7
1
1 2
1 1
+
-
TC/mV
←
+
-
+
-
SSR
1 2
1 1
SSR
4
3
←
+
-
TA7
90-260V AC/DC
7
4
3
2
1 3
1 2
1 0
1 1
1A
B
B
+
-
5
6
9
8
1 8
1 7
NC
NO
OUT2/AL2
T1
G
▲
7
9
T2
4
3
+
-
+
-8
7
1 5
1 4
1 6
T1
G
▲
8
6
T2
RTD
7
6
3
2
1 3
1 2
1 1
9
1 0
1
A
B
B
AL1
4
8
1 5
1 4
5
1 6
2 4
2 3
2 2
2 1
2 0
1 9
1 8
1 7
TC
COM
OUT1
6
8
+
-
4-20mA
Application examples
1.Relay output control (for TA7)
Power supply
Heating cord
Heating
equipment
5
4
8
7
6
2
1
16
15
14
12
11
10
17
J-1
FUSE
AL1
OUT1
C
R
J
←
90-260V AC
3
13
←
P t
NO
NC
918
RTD
▲
↑
↑
↓
OFF ON
HYS
HY
HY
OFF ON
HY
ON OFF
OFF ON
HY
ON OFF
ON OFF ON
OFF ON OFF
SSR
SSR
4-20mA
TC
AL1
RTD
Relay
Relay
OUT1
90-260V AC/DC
SSR
AL1
Relay
OUT1
4-20mA
RTD
TA4
AL2
A
B
B
90-260V AC/DC
COM
NC
NO
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
Note:
Please operate according to the process in this instruc
tion manual. Press <</AT key2s to enter auto-tune mode,
AT lamp ON, it goes off when auto-tuned.
In most cases you should start-out by placing your con
troller in auto-tune mode. Once auto-tuned, your con
trollers should not require additional auto-tune cycle if
the environment its working in changes little. If your
controllers is being used to heat or cool a load with a large
thermal mass, then the auto-tuned values need to be re
duced by 5% -10%.
The CtL setting.In most cases our control cycle should be
set to 10-20 seconds. For heating or coolin a load with a
large thermal mass, the value should be set to 30-40
seconds. If you are using a controller with a relay, setting
longer values will help to extend the life of your relay
contacts. Unless your process dictates longer cycle times,
the value should be set to 1-3 seconds to non-relay(SSR)
controls.The value should be set to 000 if 4-20mA cur
rent controls.
7
+
8
SSR
-

Terminal configurations
(If any changed, please refer to the product showing.)
③ Incorrect Control : If the instrument has been used for a long
time, the user find the temperature is hard to rise up to the set
value, meanwhile the outsidesystem running well, there must be
something wrong with the parameters of the instrument.
The user need to re-autotuning the instrument. If the instrument
lostcontrol,pleasecheckiftheconnectionofthecontroliscorrect.
If external load is shorted, broken, wrong connection or compo-
nents is damaged, it will cause lost control as well.
④Display malfunction : “UUUU”: The input signal exeed
the measured range, or check “USP” value.
ON/OFF control: ▲Set value
←
LO HI
Alarm mode:▲ Set value △ Alarm value AL
LO HI
▲
↑
HYS
▲
Cooling
0:Deviation HI alarm
▲ △
↑←
LO HI
1: Deviatian LO alarm
△ ▲
↑
←
LO HI
2: Absolute value HI alarm
▲ △
↑
←
LO HI
3: Absolute value LO alarm
△ ▲
↑
←
LO HI
4: Section outside alarm △ ▲ △
HI
5: Section inside alarm
△ ▲ △
HI
Malfunction estimate
① No Display : Check all the connection and wiring if it is all
correct.Speciallypayattention tothe power supply terminalsand
signal input ternimals.
②Incorrect Didplay: Check ifthe input signal is conformity with
the selected symbol.
For TC input, please use the relative compensation cable.
For RTD input, please use low impedence cable. The 3 wires
should at the same length.
If all above mentioned is collect , pleaase use parameter
PVF to modify.
Heating ON OFF
Note:
All the factory setting value of deiation alarm is 1.0.
AL2 hysteresis setting value.
Range ±90, factory setting 1.0
↓
Password setting.
Factory setting 015
Decimal point setting:
0: INT display 1: One decimal point
↓
↓
↓
↓
↓
↓
↓
HOLD SET >3 S
↓
↓
↓
------------------------------------------
AL1 set range: –1999-9999
AL1 mode:
0: Deviation HI alarm 1: Deviation LO alarm
2: PV HI alarm 3: PV LO alarm
4: SV-PV > AL1 alarm 5: SV-PV <AL1 alarm
6: TC brokenalarm, 7:The first Low won’t alarm
The factory setting is 2
AL2 mode: The same as AL1.
Offset value,range: ±100.
Display valuePV = Measured value - PVF
Input signal selection
stands for K, J, E, S,Pt100,Cu50 or mA/V/mV
The factory setting is K
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
Integral time range 0.1-3600.
I=OFF means cancel integral time.
Derivative time range 0.1-3600. D=OFF means
cancel derivative time.
AL2 set range:–1999-9999.
↓
↓
↓
↓
↓
↓
Control hysteresis, range: ±100.
It is not available when P ≠OFF
Control Cycle Time(adjust to best fit your process)
Recommended starting settings: Relaly = 020sec
SSR =001sec. 4-20mA = 000 sec.
Control directions: HEAt: heating
COOL: cooling
Parameter lock code setting. LcK=000
means unlocked. LcK=010 means locked.
Temperature unit. C: ℃degree,
F: F degree.
2
TA6/TA8/TA9 are subject to the drawing
on the product.
Only function for 4-20mA/0-10V
means PID control;
means 4-20mA/0-10V analog output
High analog output(when available)
eg. 10-100℃for 4-20mA output, trH=100
Low analog output (when available)
eg. 10-100℃for 4-20mA output, trL=10
5
4
3
2
1 0
9
8
6
7
1
1 2
1 1
+
-
TC/mV
←
+
-
+
-
SSR
1 2
1 1
SSR
4
3
←
+
-
TA7
90-260V AC/DC
7
4
3
2
1 3
1 2
1 0
1 1
1A
B
B
+
-
5
6
9
8
1 8
1 7
NC
NO
OUT2/AL2
T1
G
▲
7
9
T2
4
3
+
-
+
-8
7
1 5
1 4
1 6
T1
G
▲
8
6
T2
RTD
7
6
3
2
1 3
1 2
1 1
9
1 0
1
A
B
B
AL1
4
8
1 5
1 4
5
1 6
2 4
2 3
2 2
2 1
2 0
1 9
1 8
1 7
TC
COM
OUT1
6
8
+
-
4-20mA
Application examples
1.Relay output control (for TA7)
Power supply
Heating cord
Heating
equipment
5
4
8
7
6
2
1
16
15
14
12
11
10
17
J-1
FUSE
AL1
OUT1
C
R
J
←
90-260V AC
3
13
←
P t
NO
NC
918
RTD
▲
↑
↑
↓
OFF ON
HYS
HY
HY
OFF ON
HY
ON OFF
OFF ON
HY
ON OFF
ON OFF ON
OFF ON OFF
SSR
SSR
4-20mA
TC
AL1
RTD
Relay
Relay
OUT1
90-260V AC/DC
SSR
AL1
Relay
OUT1
4-20mA
RTD
TA4
AL2
A
B
B
90-260V AC/DC
COM
NC
NO
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
Note:
Please operate according to the process in this instruc
tion manual. Press <</AT key2s to enter auto-tune mode,
AT lamp ON, it goes off when auto-tuned.
In most cases you should start-out by placing your con
troller in auto-tune mode. Once auto-tuned, your con
trollers should not require additional auto-tune cycle if
the environment its working in changes little. If your
controllers is being used to heat or cool a load with a large
thermal mass, then the auto-tuned values need to be re
duced by 5% -10%.
The CtL setting.In most cases our control cycle should be
set to 10-20 seconds. For heating or coolin a load with a
large thermal mass, the value should be set to 30-40
seconds. If you are using a controller with a relay, setting
longer values will help to extend the life of your relay
contacts. Unless your process dictates longer cycle times,
the value should be set to 1-3 seconds to non-relay(SSR)
controls.The value should be set to 000 if 4-20mA cur
rent controls.
7
+
8
SSR
-

Terminal configurations
(If any changed, please refer to the product showing.)
③ Incorrect Control : If the instrument has been used for a long
time, the user find the temperature is hard to rise up to the set
value, meanwhile the outsidesystem running well, there must be
something wrong with the parameters of the instrument.
The user need to re-autotuning the instrument. If the instrument
lostcontrol,pleasecheckiftheconnectionofthecontroliscorrect.
If external load is shorted, broken, wrong connection or compo-
nents is damaged, it will cause lost control as well.
④Display malfunction : “UUUU”: The input signal exeed
the measured range, or check “USP” value.
ON/OFF control: ▲Set value
←
LO HI
Alarm mode:▲ Set value △ Alarm value AL
LO HI
▲
↑
HYS
▲
Cooling
0:Deviation HI alarm
▲ △
↑←
LO HI
1: Deviatian LO alarm
△ ▲
↑
←
LO HI
2: Absolute value HI alarm
▲ △
↑
←
LO HI
3: Absolute value LO alarm
△ ▲
↑
←
LO HI
4: Section outside alarm △ ▲ △
HI
5: Section inside alarm
△ ▲ △
HI
Malfunction estimate
① No Display : Check all the connection and wiring if it is all
correct.Speciallypayattention tothe power supply terminalsand
signal input ternimals.
②Incorrect Didplay: Check ifthe input signal is conformity with
the selected symbol.
For TC input, please use the relative compensation cable.
For RTD input, please use low impedence cable. The 3 wires
should at the same length.
If all above mentioned is collect , pleaase use parameter
PVF to modify.
Heating ON OFF
Note:
All the factory setting value of deiation alarm is 1.0.
AL2 hysteresis setting value.
Range ±90, factory setting 1.0
↓
Password setting.
Factory setting 015
Decimal point setting:
0: INT display 1: One decimal point
↓
↓
↓
↓
↓
↓
↓
HOLD SET >3 S
↓
↓
↓
------------------------------------------
AL1 set range: –1999-9999
AL1 mode:
0: Deviation HI alarm 1: Deviation LO alarm
2: PV HI alarm 3: PV LO alarm
4: SV-PV > AL1 alarm 5: SV-PV <AL1 alarm
6: TC brokenalarm, 7:The first Low won’t alarm
The factory setting is 2
AL2 mode: The same as AL1.
Offset value,range: ±100.
Display valuePV = Measured value - PVF
Input signal selection
stands for K, J, E, S,Pt100,Cu50 or mA/V/mV
The factory setting is K
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
Integral time range 0.1-3600.
I=OFF means cancel integral time.
Derivative time range 0.1-3600. D=OFF means
cancel derivative time.
AL2 set range:–1999-9999.
↓
↓
↓
↓
↓
↓
Control hysteresis, range: ±100.
It is not available when P ≠OFF
Control Cycle Time(adjust to best fit your process)
Recommended starting settings: Relaly = 020sec
SSR =001sec. 4-20mA = 000 sec.
Control directions: HEAt: heating
COOL: cooling
Parameter lock code setting. LcK=000
means unlocked. LcK=010 means locked.
Temperature unit. C: ℃degree,
F: F degree.
2
TA6/TA8/TA9 are subject to the drawing
on the product.
Only function for 4-20mA/0-10V
means PID control;
means 4-20mA/0-10V analog output
High analog output(when available)
eg. 10-100℃for 4-20mA output, trH=100
Low analog output (when available)
eg. 10-100℃for 4-20mA output, trL=10
5
4
3
2
1 0
9
8
6
7
1
1 2
1 1
+
-
TC/mV
←
+
-
+
-
SSR
1 2
1 1
SSR
4
3
←
+
-
TA7
90-260V AC/DC
7
4
3
2
1 3
1 2
1 0
1 1
1A
B
B
+
-
5
6
9
8
1 8
1 7
NC
NO
OUT2/AL2
T1
G
▲
7
9
T2
4
3
+
-
+
-8
7
1 5
1 4
1 6
T1
G
▲
8
6
T2
RTD
7
6
3
2
1 3
1 2
1 1
9
1 0
1
A
B
B
AL1
4
8
1 5
1 4
5
1 6
2 4
2 3
2 2
2 1
2 0
1 9
1 8
1 7
TC
COM
OUT1
6
8
+
-
4-20mA
Application examples
1.Relay output control (for TA7)
Power supply
Heating cord
Heating
equipment
5
4
8
7
6
2
1
16
15
14
12
11
10
17
J-1
FUSE
AL1
OUT1
C
R
J
←
90-260V AC
3
13
←
P t
NO
NC
918
RTD
▲
↑
↑
↓
OFF ON
HYS
HY
HY
OFF ON
HY
ON OFF
OFF ON
HY
ON OFF
ON OFF ON
OFF ON OFF
SSR
SSR
4-20mA
TC
AL1
RTD
Relay
Relay
OUT1
90-260V AC/DC
SSR
AL1
Relay
OUT1
4-20mA
RTD
TA4
AL2
A
B
B
90-260V AC/DC
COM
NC
NO
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
Note:
Please operate according to the process in this instruc
tion manual. Press <</AT key2s to enter auto-tune mode,
AT lamp ON, it goes off when auto-tuned.
In most cases you should start-out by placing your con
troller in auto-tune mode. Once auto-tuned, your con
trollers should not require additional auto-tune cycle if
the environment its working in changes little. If your
controllers is being used to heat or cool a load with a large
thermal mass, then the auto-tuned values need to be re
duced by 5% -10%.
The CtL setting.In most cases our control cycle should be
set to 10-20 seconds. For heating or coolin a load with a
large thermal mass, the value should be set to 30-40
seconds. If you are using a controller with a relay, setting
longer values will help to extend the life of your relay
contacts. Unless your process dictates longer cycle times,
the value should be set to 1-3 seconds to non-relay(SSR)
controls.The value should be set to 000 if 4-20mA cur
rent controls.