MYPIN TD Series User manual

TD Series Temperature Controller
Instruction Manual
Thanks a lot for selecting the product!
Before operating this instrument, please carefully read this
manual and fully understand its contents. If any probroms,
please contact our sales or distributors whom you buy from.
This manual is subject to change without prior notice.
Warning
Please do not turn on the power supply until all of the wiring is
completed. Otherwise electrical shock, fire or malfunction
may result.
Do not wire when the power is on. Do not turn on the
power supply when cleaning this instrument. Do not
disassemble, repair or modify the instrument. This may
cause electrical shock, fire or malfunction.Use this instru-
ment in the scope of its specifications. Otherwise fire or
malfunction may result.The use life of the output relay is
quite different according to is capacity and condictions. If
use out of its scope, fire or malfunction may result.
Applications
TAseries of temperature controller is available for many TC
or RTD input, adopt some advanced techonology such multi
digital filter circuit, autotune PID, fuzzy PID that make it
is very precise, stable, strong anti-interference and
simple operation. The instrument is widely applied to
Panel
This instrument should beinstalled in a domestic environment.
Otherwires electricla shock, fire or malfunction may result.
To avoid using this instrument in environment full of dust
or caustic gas.
To avoid using this instrument in environment of strong
shock or concussion.
To avoid using this instrument in environment of overflow
water or explosive oil.
The power supply wire should not put together with large
current wire to aviod electromagnetic radiation, If it must to
put together, we suggest to use a individual pipe.
In case the instrument is used in environment of strong noise,
(such as motor, transformer, solenoid, etc.)Acurrent suppresser
or noise filter should be used.
Power supply 90-260V AC/DC 50/60Hz
Consumption ≤ 5VA
Display range -199~1800℃
Accuracy 0.3%F.S ± 2digit
Sampling cycle
≤ 300ms
Main output RELAY:
normal open
AC 250V/3A DC 30V/3A COS¢=1
SSR/LOGIC :24V DC ± 2V/ 20mA
Specifications
RELAY:
normal open
AC 250V/3A DC 30V/3A COS¢=1
SSR/LOGIC:24V DC12V/ 30mA
K 0~999℃/0~1200℃
J 0~999℃ /0~1200℃
T -150~400℃ (Special order)
S 0~1600℃
Rt Pt100 -199~600℃
Cu50 -50~150℃
Alarm
Input
T/C
Withstand voltage strength
1500V Rms
(Between power terminal and the housing)
Min 50M Ω(500V DC)
(Betweenpower terminal and the housing)
Environment temperature
Save temperature
Environment humidity
Weight
0~50℃
-10~60℃
35~85%RH
Insulation resistance
MountingandSizes
+
+
+
↑
D
↑
B
A
↑
↑
E
↑
↑
C
↑
GH
Sizes
Model
TD4
TD6
TD9
TD7
44.5+0.5 45+0.5 65 65 48 48 8 80
43.5+0.5 91+0.5 65 115 48 96 12 80
67.5+0.5 67.5+0.5 95 95 72 72 12 100
91+0.5 91+0.5 115 115 96 96 12 100
A B C D E F G H
Parameter Setting &Autotuning
☆Parameters setting:
A:Indisplay estate,press SET,P/MV lamp on means SV setting,
while off means MV manual output setting,but only on manual
operation & input connect do MV settable. B: Press the
<<
/
Mkey to select the digit you want to modify; C: Press and
key to modify the numerals; D: Press SET key to confirm.
☆In autotuning estate,output value modification is
impossible.
☆Antotuning operation.
In display estate,press SET and <</M key at the same time
until AT/M lamp flahses.Then ithe instrument is under
autotuning estate.Press again to quite.
Power on
↓
↓
Displays temperature unit
↓
Input up limit
3S
3S
3S
Measured displaying
Set displaying
↓
Shift and flashes
Modify
SET
Stop flashing
↓
Confirm
Self-check
All LED on
Input type
≤ 350g
E 0~1000℃
Caution
TD8 91+0.5 43.5+0.5 65 115 96 48 12 80
Input low limit
↓
In Manual operation/Non-autotune estate, press and hold
/ key for more than 3 seconds to enter/quit the below
menu for display range settings.
SET
↓
1
>>
>
>
Low limit value, it is adjustable
by the input signal.
automation systems of mechanism, chemical industrial,
chinaware, light industrial, metallurgy and petroleum chemical
industrial. It is also applied to the production line of foodstuff,
packing, printing, dry machine, metal heat process equipment
to control the temperature.
Up limit value, it is adjustable
by the input signal.
↓SET
AL1 hysteresis setting value.
Range ±90, factory setting 1.0
SET
↓
TD □□ - □□□□
Models Input signals:Default: K,J,T,S,Pt100/mA,lN
OUT2/AL2: R:RELAY S:SSR/Logic
-T:SCR N:Non
OUT1: I:4-20mA R:RELAY
S:SSR/Logic T:SCR
AL1:R:RELAY S:SSR/Logic T:SCR
Power supply:Default:90-260V AC/DC
E:24VDC or 18-30V AC/DC
Sizes: 4:48H ×48W 6:48H ×96W
TA series of temperature controller
7:72H ×72W 8:96H ×48W
9:96H ×96W
>>
>
>
/M
F
+
↑
↑
↑
MYPIN
mV mV 0-75mV
mA mA 4-20mA /0-10V
①. PV / parameter symbols
②. SV / parameters preset value
③. Indication lamps
OUT1: Heating/Main control output lamp
On: Output Off: No output
OUT2/AL2:
Colling/Alarm 2 output lamp
On: Output Off: No output
AT/M: On: manual operation Off: auto operation
Flash: under autotuning estate
P/MV: SV/MV display setting
On: MV manual output Off: SV setting
AL1: Alarm 1 lamp On: Alarm Off: No Alarm
AL2: Alarm 21 lamp On: Alarm Off: No Alarm
④.Set key Parameter Setting/Changing
⑤.Shift/Autotune key Press this key to shift digit of
parameter value setting. Or hold this key for more than 3
seconds can enter/quit autotune estate. When enter
autotune estate, AT lamp on. When quit autotune estate,
AT lamp off.
⑥.Up key ⑦.Down key
↑
O U T 1 OUT2/ AT/M
AL1
SET
>
>
/M
PV
SV
①
②
③
④
→
→
→↑
↑⑥⑤
→
P / M V A L 2
>
>
>
>
⑦
>>
>
>

TD Series Temperature Controller
Instruction Manual
Thanks a lot for selecting the product!
Before operating this instrument, please carefully read this
manual and fully understand its contents. If any probroms,
please contact our sales or distributors whom you buy from.
This manual is subject to change without prior notice.
Warning
Please do not turn on the power supply until all of the wiring is
completed. Otherwise electrical shock, fire or malfunction
may result.
Do not wire when the power is on. Do not turn on the
power supply when cleaning this instrument. Do not
disassemble, repair or modify the instrument. This may
cause electrical shock, fire or malfunction.Use this instru-
ment in the scope of its specifications. Otherwise fire or
malfunction may result.The use life of the output relay is
quite different according to is capacity and condictions. If
use out of its scope, fire or malfunction may result.
Applications
TAseries of temperature controller is available for many TC
or RTD input, adopt some advanced techonology such multi
digital filter circuit, autotune PID, fuzzy PID that make it
is very precise, stable, strong anti-interference and
simple operation. The instrument is widely applied to
Panel
This instrument should beinstalled in a domestic environment.
Otherwires electricla shock, fire or malfunction may result.
To avoid using this instrument in environment full of dust
or caustic gas.
To avoid using this instrument in environment of strong
shock or concussion.
To avoid using this instrument in environment of overflow
water or explosive oil.
The power supply wire should not put together with large
current wire to aviod electromagnetic radiation, If it must to
put together, we suggest to use a individual pipe.
In case the instrument is used in environment of strong noise,
(such as motor, transformer, solenoid, etc.)Acurrent suppresser
or noise filter should be used.
Power supply 90-260V AC/DC 50/60Hz
Consumption ≤ 5VA
Display range -199~1800℃
Accuracy 0.3%F.S ± 2digit
Sampling cycle
≤ 300ms
Main output RELAY:
normal open
AC 250V/3A DC 30V/3A COS¢=1
SSR/LOGIC :24V DC ± 2V/ 20mA
Specifications
RELAY:
normal open
AC 250V/3A DC 30V/3A COS¢=1
SSR/LOGIC:24V DC12V/ 30mA
K 0~999℃/0~1200℃
J 0~999℃ /0~1200℃
T -150~400℃ (Special order)
S 0~1600℃
Rt Pt100 -199~600℃
Cu50 -50~150℃
Alarm
Input
T/C
Withstand voltage strength
1500V Rms
(Between power terminal and the housing)
Min 50M Ω(500V DC)
(Betweenpower terminal and the housing)
Environment temperature
Save temperature
Environment humidity
Weight
0~50℃
-10~60℃
35~85%RH
Insulation resistance
MountingandSizes
+
+
+
↑
D
↑
B
A
↑
↑
E
↑
↑
C
↑
GH
Sizes
Model
TD4
TD6
TD9
TD7
44.5+0.5 45+0.5 65 65 48 48 8 80
43.5+0.5 91+0.5 65 115 48 96 12 80
67.5+0.5 67.5+0.5 95 95 72 72 12 100
91+0.5 91+0.5 115 115 96 96 12 100
A B C D E F G H
Parameter Setting &Autotuning
☆Parameters setting:
A:Indisplay estate,press SET,P/MV lamp on means SV setting,
while off means MV manual output setting,but only on manual
operation & input connect do MV settable. B: Press the
<<
/
Mkey to select the digit you want to modify; C: Press and
key to modify the numerals; D: Press SET key to confirm.
☆In autotuning estate,output value modification is
impossible.
☆Antotuning operation.
In display estate,press SET and <</M key at the same time
until AT/M lamp flahses.Then ithe instrument is under
autotuning estate.Press again to quite.
Power on
↓
↓
Displays temperature unit
↓
Input up limit
3S
3S
3S
Measured displaying
Set displaying
↓
Shift and flashes
Modify
SET
Stop flashing
↓
Confirm
Self-check
All LED on
Input type
≤ 350g
E 0~1000℃
Caution
TD8 91+0.5 43.5+0.5 65 115 96 48 12 80
Input low limit
↓
In Manual operation/Non-autotune estate, press and hold
/ key for more than 3 seconds to enter/quit the below
menu for display range settings.
SET
↓
1
>>
>
>
Low limit value, it is adjustable
by the input signal.
automation systems of mechanism, chemical industrial,
chinaware, light industrial, metallurgy and petroleum chemical
industrial. It is also applied to the production line of foodstuff,
packing, printing, dry machine, metal heat process equipment
to control the temperature.
Up limit value, it is adjustable
by the input signal.
↓SET
AL1 hysteresis setting value.
Range ±90, factory setting 1.0
SET
↓
TD □□ - □□□□
Models Input signals:Default: K,J,T,S,Pt100/mA,lN
OUT2/AL2: R:RELAY S:SSR/Logic
-T:SCR N:Non
OUT1: I:4-20mA R:RELAY
S:SSR/Logic T:SCR
AL1:R:RELAY S:SSR/Logic T:SCR
Power supply:Default:90-260V AC/DC
E:24VDC or 18-30V AC/DC
Sizes: 4:48H ×48W 6:48H ×96W
TA series of temperature controller
7:72H ×72W 8:96H ×48W
9:96H ×96W
>>
>
>
/M
F
+
↑
↑
↑
MYPIN
mV mV 0-75mV
mA mA 4-20mA /0-10V
①. PV / parameter symbols
②. SV / parameters preset value
③. Indication lamps
OUT1: Heating/Main control output lamp
On: Output Off: No output
OUT2/AL2:
Colling/Alarm 2 output lamp
On: Output Off: No output
AT/M: On: manual operation Off: auto operation
Flash: under autotuning estate
P/MV: SV/MV display setting
On: MV manual output Off: SV setting
AL1: Alarm 1 lamp On: Alarm Off: No Alarm
AL2: Alarm 21 lamp On: Alarm Off: No Alarm
④.Set key Parameter Setting/Changing
⑤.Shift/Autotune key Press this key to shift digit of
parameter value setting. Or hold this key for more than 3
seconds can enter/quit autotune estate. When enter
autotune estate, AT lamp on. When quit autotune estate,
AT lamp off.
⑥.Up key ⑦.Down key
↑
O U T 1 OUT2/ AT/M
AL1
SET
>
>
/M
PV
SV
①
②
③
④
→
→
→↑
↑⑥⑤
→
P / M V A L 2
>
>
>
>
⑦
>>
>
>

TD Series Temperature Controller
Instruction Manual
Thanks a lot for selecting the product!
Before operating this instrument, please carefully read this
manual and fully understand its contents. If any probroms,
please contact our sales or distributors whom you buy from.
This manual is subject to change without prior notice.
Warning
Please do not turn on the power supply until all of the wiring is
completed. Otherwise electrical shock, fire or malfunction
may result.
Do not wire when the power is on. Do not turn on the
power supply when cleaning this instrument. Do not
disassemble, repair or modify the instrument. This may
cause electrical shock, fire or malfunction.Use this instru-
ment in the scope of its specifications. Otherwise fire or
malfunction may result.The use life of the output relay is
quite different according to is capacity and condictions. If
use out of its scope, fire or malfunction may result.
Applications
TAseries of temperature controller is available for many TC
or RTD input, adopt some advanced techonology such multi
digital filter circuit, autotune PID, fuzzy PID that make it
is very precise, stable, strong anti-interference and
simple operation. The instrument is widely applied to
Panel
This instrument should beinstalled in a domestic environment.
Otherwires electricla shock, fire or malfunction may result.
To avoid using this instrument in environment full of dust
or caustic gas.
To avoid using this instrument in environment of strong
shock or concussion.
To avoid using this instrument in environment of overflow
water or explosive oil.
The power supply wire should not put together with large
current wire to aviod electromagnetic radiation, If it must to
put together, we suggest to use a individual pipe.
In case the instrument is used in environment of strong noise,
(such as motor, transformer, solenoid, etc.)Acurrent suppresser
or noise filter should be used.
Power supply 90-260V AC/DC 50/60Hz
Consumption ≤ 5VA
Display range -199~1800℃
Accuracy 0.3%F.S ± 2digit
Sampling cycle
≤ 300ms
Main output RELAY:
normal open
AC 250V/3A DC 30V/3A COS¢=1
SSR/LOGIC :24V DC ± 2V/ 20mA
Specifications
RELAY:
normal open
AC 250V/3A DC 30V/3A COS¢=1
SSR/LOGIC:24V DC12V/ 30mA
K 0~999℃/0~1200℃
J 0~999℃ /0~1200℃
T -150~400℃ (Special order)
S 0~1600℃
Rt Pt100 -199~600℃
Cu50 -50~150℃
Alarm
Input
T/C
Withstand voltage strength
1500V Rms
(Between power terminal and the housing)
Min 50M Ω(500V DC)
(Betweenpower terminal and the housing)
Environment temperature
Save temperature
Environment humidity
Weight
0~50℃
-10~60℃
35~85%RH
Insulation resistance
MountingandSizes
+
+
+
↑
D
↑
B
A
↑
↑
E
↑
↑
C
↑
GH
Sizes
Model
TD4
TD6
TD9
TD7
44.5+0.5 45+0.5 65 65 48 48 8 80
43.5+0.5 91+0.5 65 115 48 96 12 80
67.5+0.5 67.5+0.5 95 95 72 72 12 100
91+0.5 91+0.5 115 115 96 96 12 100
A B C D E F G H
Parameter Setting &Autotuning
☆Parameters setting:
A:Indisplay estate,press SET,P/MV lamp on means SV setting,
while off means MV manual output setting,but only on manual
operation & input connect do MV settable. B: Press the
<<
/
Mkey to select the digit you want to modify; C: Press and
key to modify the numerals; D: Press SET key to confirm.
☆In autotuning estate,output value modification is
impossible.
☆Antotuning operation.
In display estate,press SET and <</M key at the same time
until AT/M lamp flahses.Then ithe instrument is under
autotuning estate.Press again to quite.
Power on
↓
↓
Displays temperature unit
↓
Input up limit
3S
3S
3S
Measured displaying
Set displaying
↓
Shift and flashes
Modify
SET
Stop flashing
↓
Confirm
Self-check
All LED on
Input type
≤ 350g
E 0~1000℃
Caution
TD8 91+0.5 43.5+0.5 65 115 96 48 12 80
Input low limit
↓
In Manual operation/Non-autotune estate, press and hold
/ key for more than 3 seconds to enter/quit the below
menu for display range settings.
SET
↓
1
>>
>
>
Low limit value, it is adjustable
by the input signal.
automation systems of mechanism, chemical industrial,
chinaware, light industrial, metallurgy and petroleum chemical
industrial. It is also applied to the production line of foodstuff,
packing, printing, dry machine, metal heat process equipment
to control the temperature.
Up limit value, it is adjustable
by the input signal.
↓SET
AL1 hysteresis setting value.
Range ±90, factory setting 1.0
SET
↓
TD □□ - □□□□
Models Input signals:Default: K,J,T,S,Pt100/mA,lN
OUT2/AL2: R:RELAY S:SSR/Logic
-T:SCR N:Non
OUT1: I:4-20mA R:RELAY
S:SSR/Logic T:SCR
AL1:R:RELAY S:SSR/Logic T:SCR
Power supply:Default:90-260V AC/DC
E:24VDC or 18-30V AC/DC
Sizes: 4:48H ×48W 6:48H ×96W
TA series of temperature controller
7:72H ×72W 8:96H ×48W
9:96H ×96W
>>
>
>
/M
F
+
↑
↑
↑
MYPIN
mV mV 0-75mV
mA mA 4-20mA /0-10V
①. PV / parameter symbols
②. SV / parameters preset value
③. Indication lamps
OUT1: Heating/Main control output lamp
On: Output Off: No output
OUT2/AL2:
Colling/Alarm 2 output lamp
On: Output Off: No output
AT/M: On: manual operation Off: auto operation
Flash: under autotuning estate
P/MV: SV/MV display setting
On: MV manual output Off: SV setting
AL1: Alarm 1 lamp On: Alarm Off: No Alarm
AL2: Alarm 21 lamp On: Alarm Off: No Alarm
④.Set key Parameter Setting/Changing
⑤.Shift/Autotune key Press this key to shift digit of
parameter value setting. Or hold this key for more than 3
seconds can enter/quit autotune estate. When enter
autotune estate, AT lamp on. When quit autotune estate,
AT lamp off.
⑥.Up key ⑦.Down key
↑
O U T 1 OUT2/ AT/M
AL1
SET
>
>
/M
PV
SV
①
②
③
④
→
→
→↑
↑⑥⑤
→
P / M V A L 2
>
>
>
>
⑦
>>
>
>

TD Series Temperature Controller
Instruction Manual
Thanks a lot for selecting the product!
Before operating this instrument, please carefully read this
manual and fully understand its contents. If any probroms,
please contact our sales or distributors whom you buy from.
This manual is subject to change without prior notice.
Warning
Please do not turn on the power supply until all of the wiring is
completed. Otherwise electrical shock, fire or malfunction
may result.
Do not wire when the power is on. Do not turn on the
power supply when cleaning this instrument. Do not
disassemble, repair or modify the instrument. This may
cause electrical shock, fire or malfunction.Use this instru-
ment in the scope of its specifications. Otherwise fire or
malfunction may result.The use life of the output relay is
quite different according to is capacity and condictions. If
use out of its scope, fire or malfunction may result.
Applications
TAseries of temperature controller is available for many TC
or RTD input, adopt some advanced techonology such multi
digital filter circuit, autotune PID, fuzzy PID that make it
is very precise, stable, strong anti-interference and
simple operation. The instrument is widely applied to
Panel
This instrument should beinstalled in a domestic environment.
Otherwires electricla shock, fire or malfunction may result.
To avoid using this instrument in environment full of dust
or caustic gas.
To avoid using this instrument in environment of strong
shock or concussion.
To avoid using this instrument in environment of overflow
water or explosive oil.
The power supply wire should not put together with large
current wire to aviod electromagnetic radiation, If it must to
put together, we suggest to use a individual pipe.
In case the instrument is used in environment of strong noise,
(such as motor, transformer, solenoid, etc.)Acurrent suppresser
or noise filter should be used.
Power supply 90-260V AC/DC 50/60Hz
Consumption ≤ 5VA
Display range -199~1800℃
Accuracy 0.3%F.S ± 2digit
Sampling cycle
≤ 300ms
Main output RELAY:
normal open
AC 250V/3A DC 30V/3A COS¢=1
SSR/LOGIC :24V DC ± 2V/ 20mA
Specifications
RELAY:
normal open
AC 250V/3A DC 30V/3A COS¢=1
SSR/LOGIC:24V DC12V/ 30mA
K 0~999℃/0~1200℃
J 0~999℃ /0~1200℃
T -150~400℃ (Special order)
S 0~1600℃
Rt Pt100 -199~600℃
Cu50 -50~150℃
Alarm
Input
T/C
Withstand voltage strength
1500V Rms
(Between power terminal and the housing)
Min 50M Ω(500V DC)
(Betweenpower terminal and the housing)
Environment temperature
Save temperature
Environment humidity
Weight
0~50℃
-10~60℃
35~85%RH
Insulation resistance
MountingandSizes
+
+
+
↑
D
↑
B
A
↑
↑
E
↑
↑
C
↑
GH
Sizes
Model
TD4
TD6
TD9
TD7
44.5+0.5 45+0.5 65 65 48 48 8 80
43.5+0.5 91+0.5 65 115 48 96 12 80
67.5+0.5 67.5+0.5 95 95 72 72 12 100
91+0.5 91+0.5 115 115 96 96 12 100
A B C D E F G H
Parameter Setting &Autotuning
☆Parameters setting:
A:Indisplay estate,press SET,P/MV lamp on means SV setting,
while off means MV manual output setting,but only on manual
operation & input connect do MV settable. B: Press the
<<
/
Mkey to select the digit you want to modify; C: Press and
key to modify the numerals; D: Press SET key to confirm.
☆In autotuning estate,output value modification is
impossible.
☆Antotuning operation.
In display estate,press SET and <</M key at the same time
until AT/M lamp flahses.Then ithe instrument is under
autotuning estate.Press again to quite.
Power on
↓
↓
Displays temperature unit
↓
Input up limit
3S
3S
3S
Measured displaying
Set displaying
↓
Shift and flashes
Modify
SET
Stop flashing
↓
Confirm
Self-check
All LED on
Input type
≤ 350g
E 0~1000℃
Caution
TD8 91+0.5 43.5+0.5 65 115 96 48 12 80
Input low limit
↓
In Manual operation/Non-autotune estate, press and hold
/ key for more than 3 seconds to enter/quit the below
menu for display range settings.
SET
↓
1
>>
>
>
Low limit value, it is adjustable
by the input signal.
automation systems of mechanism, chemical industrial,
chinaware, light industrial, metallurgy and petroleum chemical
industrial. It is also applied to the production line of foodstuff,
packing, printing, dry machine, metal heat process equipment
to control the temperature.
Up limit value, it is adjustable
by the input signal.
↓SET
AL1 hysteresis setting value.
Range ±90, factory setting 1.0
SET
↓
TD □□ - □□□□
Models Input signals:Default: K,J,T,S,Pt100/mA,lN
OUT2/AL2: R:RELAY S:SSR/Logic
-T:SCR N:Non
OUT1: I:4-20mA R:RELAY
S:SSR/Logic T:SCR
AL1:R:RELAY S:SSR/Logic T:SCR
Power supply:Default:90-260V AC/DC
E:24VDC or 18-30V AC/DC
Sizes: 4:48H ×48W 6:48H ×96W
TA series of temperature controller
7:72H ×72W 8:96H ×48W
9:96H ×96W
>>
>
>
/M
F
+
↑
↑
↑
MYPIN
mV mV 0-75mV
mA mA 4-20mA /0-10V
①. PV / parameter symbols
②. SV / parameters preset value
③. Indication lamps
OUT1: Heating/Main control output lamp
On: Output Off: No output
OUT2/AL2:
Colling/Alarm 2 output lamp
On: Output Off: No output
AT/M: On: manual operation Off: auto operation
Flash: under autotuning estate
P/MV: SV/MV display setting
On: MV manual output Off: SV setting
AL1: Alarm 1 lamp On: Alarm Off: No Alarm
AL2: Alarm 21 lamp On: Alarm Off: No Alarm
④.Set key Parameter Setting/Changing
⑤.Shift/Autotune key Press this key to shift digit of
parameter value setting. Or hold this key for more than 3
seconds can enter/quit autotune estate. When enter
autotune estate, AT lamp on. When quit autotune estate,
AT lamp off.
⑥.Up key ⑦.Down key
↑
O U T 1 OUT2/ AT/M
AL1
SET
>
>
/M
PV
SV
①
②
③
④
→
→
→↑
↑⑥⑤
→
P / M V A L 2
>
>
>
>
⑦
>>
>
>

Terminal configurations
(If any changed, please refer to the product showing.)
③ Incorrect Control : If the instrument has been used for a long
time, the user find the temperature is hard to rise up to the set
value, meanwhile the outsidesystemrunning well, there must be
something wrong with the parameters of the instrument.
The user need to re-autotuning the instrument. If the instrument
lostcontrol,pleasecheckiftheconnectionofthecontroliscorrect.
If external load is shorted, broken, wrong connection or compo-
nents is damaged, it will cause lost control as well. When it is
necessary, please push out the PCB to check the if the output
terminals is damaged and notavailable.
④Display malfunction : “UUUU”: The input signal exeed
the measured HI range .
ON/OFF control: ▲Set value
←
LO HI
Alarm mode:▲ Set value △ Alarm value AL
LO HI
▲
↑
HYS
▲
OFF
Cooling
0:Deviation HI
alarm ▲ △
↑
OFF ON
HY ←
LO HI
1:Deviatian LO alarm
△ ▲
↑
O N HY
←
LO HI
2:Absolute value HI
alarm ▲ △
↑
HY ←
LO HI
3: Absolute value LO
alarm △ ▲
↑
HY
←
LO HI
4: Section outside alarm △ ▲ △
OFF
HI
5: Section inside alarm
△ ▲ △
ON
HI
Malfunction estimate
① No Display : Check all the connection and wiring if it is all
correct.Speciallypayattention tothe power supplyterminalsand
signal input ternimals.
② Incorrect Didplay: Check if the input signalis conformitywith
the selected symbol.
For TC input, please use the relative compensation cable.
For RTD input, please use low impedence cable. The 3 wires
should at the same length.
If all above mentioned is collect , pleaase use parameter
PVF to modify.
Heating ON OFF
Note:
All the factory setting value of deviation alarm is 1.0.
AL2 hysteresis setting value.
Range ±90, factory setting 1.0
↓
SET
Password setting.
Factory setting 015
Decimal point setting:
0: No decimal 1: One decimal
↓
↓SET
SET
↓SET
↓SET
4
↓SET
↓SET
↓HOLD SET >3 S
SET
↓
↓SET
↓
↓SET
------------------------------------------
AL1 set range: –1999-9999
AL1 mode: 0: Deviation HI alarm 1: Deviatian
LO alarm 2:Absolute value HI alarm
3: Absolute value LO alarm 4: Section outside
alarm 5: Section inside alarm 6: TC broken
alarm ,The factory setting is 2
AL2 mode: The same as AL1.
Range: ±100.Display value
PV = Measured value - PVF
Input signal selection TC: K, J, E, S
RTD: Pt100, Cu50 The factory setting is K
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
Integral time range 0.1-3600. I=OFF means
cancel integral time.
Derivative time range 0.1-3600. D=OFF means
cancel derivative time.
AL2 set range:–1999-9999.
↓
↓SET
↓
SET
↓SET
SET
↓SET
↓SET
SET
SET
Control hysteresis, range: ±100.
It is not available when P ≠OFF
The output control mode ,RELAY=020,
SSR\SCR=001,4-20mA=000.
Control directions: HEAt: heating
COOL: cooling
①
Parameter lock code setting. LcK=000
means unlocked. LcK=010 means locked.
Temperature unit. C means C degree,
F means F degree.
2
TD6/TD8/TD9 are subject to the
drawing on the product.
Only for 4-20mA
=PID,control; =tPV 4-20mA,
transmit;
High analogue output
(when analogue is active)
High analogue output
(when analogue is active)
TD4
RTD~260V/AC
5
4
3
2
1 0
9
8
6
7
1
AL1
1 2
1 1
A
B
B
+
-
TC/mV
←
+
-
SSR
RELAY
+
-
SSR
1 2
1 1
SSR
4
3
0UT1
AL2
←
+
-
4-20mA
TD7
RTD
7
4
3
2
1 3
1 2
1 0
1 1
1
AL1
A
B
B
+
-
TC
RELAY
5
6
OUT1
9
8
1 8
1 7
N C
N0
RELAY
OUT2/AL2
T1
G
▲
7
9
T2
4
3
+
-
SSR
+
-
SSR
87
1 5
1 4
1 6
4-20mA
T1
G
▲
8
6
T2
6
+
-
SSR
7
RTD
90-260V DC/AC
7
6
3
2
1 3
1 2
1 1
9
1 0
1
A
B
B
AL1
4
8
1 5
1 4
5
1 6
NC
N0
2 4
2 3
2 2
2 1
2 0
1 9
1 8
1 7
TC
com
OUT1
6
8
+
-
4-20mA
Application examples
1.Relay output control (forTA9)
Power supply
Heating cord
Heating
equipment
5
4
8
7
6
2
1
16
15
14
12
11
10
17
J-1
FUSE
AL1
OUT1
C
R
J
←
90-260V AC
3
13
←
Pt
N O
N C
918
RTD
ON
OFF
OFF O N
O N OFF
OFF
OFF
O N
O N
▲
↑
↑
Note:
Mamual/Auto Convertion: In display estate,press <</M to
shift. AT/M lamp on means manual operation, while off
means autotuning.
For the very first time, please press SET and <</M key
until AT/M lamp flash to enter autotuning estate.In the
future,if the load/control temp. point changes in small
scale (eg. Running the same equipment, and the preset
value changes within ±30℃), the user no need to let it
autotuning again. Because the instrument has recorded the
previous PID parameters. When the instrument is used for
huge capacity heating equipments, the user should set
autotuning value lower 5%-10% than the normal control
value, in order to decrease the exceed-tuning caused by
control.
Normally, the control cycle of the heating equipment
should be 20-30 seconds. For huge capacity heating
equipments, the value should be 30-120 seconds, in order to
longer the use life of the relay. For non-contact output,
such as SSR control output, the value should be 1-3.
90-260V AC/DC
90

Terminal configurations
(If any changed, please refer to the product showing.)
③ Incorrect Control : If the instrument has been used for a long
time, the user find the temperature is hard to rise up to the set
value, meanwhile the outsidesystemrunning well, there must be
something wrong with the parameters of the instrument.
The user need to re-autotuning the instrument. If the instrument
lostcontrol,pleasecheckiftheconnectionofthecontroliscorrect.
If external load is shorted, broken, wrong connection or compo-
nents is damaged, it will cause lost control as well. When it is
necessary, please push out the PCB to check the if the output
terminals is damaged and notavailable.
④Display malfunction : “UUUU”: The input signal exeed
the measured HI range .
ON/OFF control: ▲Set value
←
LO HI
Alarm mode:▲ Set value △ Alarm value AL
LO HI
▲
↑
HYS
▲
OFF
Cooling
0:Deviation HI
alarm ▲ △
↑
OFF ON
HY ←
LO HI
1:Deviatian LO alarm
△ ▲
↑
O N HY
←
LO HI
2:Absolute value HI
alarm ▲ △
↑
HY ←
LO HI
3: Absolute value LO
alarm △ ▲
↑
HY
←
LO HI
4: Section outside alarm △ ▲ △
OFF
HI
5: Section inside alarm
△ ▲ △
ON
HI
Malfunction estimate
① No Display : Check all the connection and wiring if it is all
correct.Speciallypayattention tothe power supplyterminalsand
signal input ternimals.
② Incorrect Didplay: Check if the input signalis conformitywith
the selected symbol.
For TC input, please use the relative compensation cable.
For RTD input, please use low impedence cable. The 3 wires
should at the same length.
If all above mentioned is collect , pleaase use parameter
PVF to modify.
Heating ON OFF
Note:
All the factory setting value of deviation alarm is 1.0.
AL2 hysteresis setting value.
Range ±90, factory setting 1.0
↓
SET
Password setting.
Factory setting 015
Decimal point setting:
0: No decimal 1: One decimal
↓
↓SET
SET
↓SET
↓SET
4
↓SET
↓SET
↓HOLD SET >3 S
SET
↓
↓SET
↓
↓SET
------------------------------------------
AL1 set range: –1999-9999
AL1 mode: 0: Deviation HI alarm 1: Deviatian
LO alarm 2:Absolute value HI alarm
3: Absolute value LO alarm 4: Section outside
alarm 5: Section inside alarm 6: TC broken
alarm ,The factory setting is 2
AL2 mode: The same as AL1.
Range: ±100.Display value
PV = Measured value - PVF
Input signal selection TC: K, J, E, S
RTD: Pt100, Cu50 The factory setting is K
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
Integral time range 0.1-3600. I=OFF means
cancel integral time.
Derivative time range 0.1-3600. D=OFF means
cancel derivative time.
AL2 set range:–1999-9999.
↓
↓SET
↓
SET
↓SET
SET
↓SET
↓SET
SET
SET
Control hysteresis, range: ±100.
It is not available when P ≠OFF
The output control mode ,RELAY=020,
SSR\SCR=001,4-20mA=000.
Control directions: HEAt: heating
COOL: cooling
①
Parameter lock code setting. LcK=000
means unlocked. LcK=010 means locked.
Temperature unit. C means C degree,
F means F degree.
2
TD6/TD8/TD9 are subject to the
drawing on the product.
Only for 4-20mA
=PID,control; =tPV 4-20mA,
transmit;
High analogue output
(when analogue is active)
High analogue output
(when analogue is active)
TD4
RTD~260V/AC
5
4
3
2
1 0
9
8
6
7
1
AL1
1 2
1 1
A
B
B
+
-
TC/mV
←
+
-
SSR
RELAY
+
-
SSR
1 2
1 1
SSR
4
3
0UT1
AL2
←
+
-
4-20mA
TD7
RTD
7
4
3
2
1 3
1 2
1 0
1 1
1
AL1
A
B
B
+
-
TC
RELAY
5
6
OUT1
9
8
1 8
1 7
N C
N0
RELAY
OUT2/AL2
T1
G
▲
7
9
T2
4
3
+
-
SSR
+
-
SSR
87
1 5
1 4
1 6
4-20mA
T1
G
▲
8
6
T2
6
+
-
SSR
7
RTD
90-260V DC/AC
7
6
3
2
1 3
1 2
1 1
9
1 0
1
A
B
B
AL1
4
8
1 5
1 4
5
1 6
NC
N0
2 4
2 3
2 2
2 1
2 0
1 9
1 8
1 7
TC
com
OUT1
6
8
+
-
4-20mA
Application examples
1.Relay output control (forTA9)
Power supply
Heating cord
Heating
equipment
5
4
8
7
6
2
1
16
15
14
12
11
10
17
J-1
FUSE
AL1
OUT1
C
R
J
←
90-260V AC
3
13
←
Pt
N O
N C
918
RTD
ON
OFF
OFF O N
O N OFF
OFF
OFF
O N
O N
▲
↑
↑
Note:
Mamual/Auto Convertion: In display estate,press <</M to
shift. AT/M lamp on means manual operation, while off
means autotuning.
For the very first time, please press SET and <</M key
until AT/M lamp flash to enter autotuning estate.In the
future,if the load/control temp. point changes in small
scale (eg. Running the same equipment, and the preset
value changes within ±30℃), the user no need to let it
autotuning again. Because the instrument has recorded the
previous PID parameters. When the instrument is used for
huge capacity heating equipments, the user should set
autotuning value lower 5%-10% than the normal control
value, in order to decrease the exceed-tuning caused by
control.
Normally, the control cycle of the heating equipment
should be 20-30 seconds. For huge capacity heating
equipments, the value should be 30-120 seconds, in order to
longer the use life of the relay. For non-contact output,
such as SSR control output, the value should be 1-3.
90-260V AC/DC
90

Terminal configurations
(If any changed, please refer to the product showing.)
③ Incorrect Control : If the instrument has been used for a long
time, the user find the temperature is hard to rise up to the set
value, meanwhile the outsidesystemrunning well, there must be
something wrong with the parameters of the instrument.
The user need to re-autotuning the instrument. If the instrument
lostcontrol,pleasecheckiftheconnectionofthecontroliscorrect.
If external load is shorted, broken, wrong connection or compo-
nents is damaged, it will cause lost control as well. When it is
necessary, please push out the PCB to check the if the output
terminals is damaged and notavailable.
④Display malfunction : “UUUU”: The input signal exeed
the measured HI range .
ON/OFF control: ▲Set value
←
LO HI
Alarm mode:▲ Set value △ Alarm value AL
LO HI
▲
↑
HYS
▲
OFF
Cooling
0:Deviation HI
alarm ▲ △
↑
OFF ON
HY ←
LO HI
1:Deviatian LO alarm
△ ▲
↑
O N HY
←
LO HI
2:Absolute value HI
alarm ▲ △
↑
HY ←
LO HI
3: Absolute value LO
alarm △ ▲
↑
HY
←
LO HI
4: Section outside alarm △ ▲ △
OFF
HI
5: Section inside alarm
△ ▲ △
ON
HI
Malfunction estimate
① No Display : Check all the connection and wiring if it is all
correct.Speciallypayattention tothe power supplyterminalsand
signal input ternimals.
② Incorrect Didplay: Check if the input signalis conformitywith
the selected symbol.
For TC input, please use the relative compensation cable.
For RTD input, please use low impedence cable. The 3 wires
should at the same length.
If all above mentioned is collect , pleaase use parameter
PVF to modify.
Heating ON OFF
Note:
All the factory setting value of deviation alarm is 1.0.
AL2 hysteresis setting value.
Range ±90, factory setting 1.0
↓
SET
Password setting.
Factory setting 015
Decimal point setting:
0: No decimal 1: One decimal
↓
↓SET
SET
↓SET
↓SET
4
↓SET
↓SET
↓HOLD SET >3 S
SET
↓
↓SET
↓
↓SET
------------------------------------------
AL1 set range: –1999-9999
AL1 mode: 0: Deviation HI alarm 1: Deviatian
LO alarm 2:Absolute value HI alarm
3: Absolute value LO alarm 4: Section outside
alarm 5: Section inside alarm 6: TC broken
alarm ,The factory setting is 2
AL2 mode: The same as AL1.
Range: ±100.Display value
PV = Measured value - PVF
Input signal selection TC: K, J, E, S
RTD: Pt100, Cu50 The factory setting is K
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
Integral time range 0.1-3600. I=OFF means
cancel integral time.
Derivative time range 0.1-3600. D=OFF means
cancel derivative time.
AL2 set range:–1999-9999.
↓
↓SET
↓
SET
↓SET
SET
↓SET
↓SET
SET
SET
Control hysteresis, range: ±100.
It is not available when P ≠OFF
The output control mode ,RELAY=020,
SSR\SCR=001,4-20mA=000.
Control directions: HEAt: heating
COOL: cooling
①
Parameter lock code setting. LcK=000
means unlocked. LcK=010 means locked.
Temperature unit. C means C degree,
F means F degree.
2
TD6/TD8/TD9 are subject to the
drawing on the product.
Only for 4-20mA
=PID,control; =tPV 4-20mA,
transmit;
High analogue output
(when analogue is active)
High analogue output
(when analogue is active)
TD4
RTD~260V/AC
5
4
3
2
1 0
9
8
6
7
1
AL1
1 2
1 1
A
B
B
+
-
TC/mV
←
+
-
SSR
RELAY
+
-
SSR
1 2
1 1
SSR
4
3
0UT1
AL2
←
+
-
4-20mA
TD7
RTD
7
4
3
2
1 3
1 2
1 0
1 1
1
AL1
A
B
B
+
-
TC
RELAY
5
6
OUT1
9
8
1 8
1 7
N C
N0
RELAY
OUT2/AL2
T1
G
▲
7
9
T2
4
3
+
-
SSR
+
-
SSR
87
1 5
1 4
1 6
4-20mA
T1
G
▲
8
6
T2
6
+
-
SSR
7
RTD
90-260V DC/AC
7
6
3
2
1 3
1 2
1 1
9
1 0
1
A
B
B
AL1
4
8
1 5
1 4
5
1 6
NC
N0
2 4
2 3
2 2
2 1
2 0
1 9
1 8
1 7
TC
com
OUT1
6
8
+
-
4-20mA
Application examples
1.Relay output control (forTA9)
Power supply
Heating cord
Heating
equipment
5
4
8
7
6
2
1
16
15
14
12
11
10
17
J-1
FUSE
AL1
OUT1
C
R
J
←
90-260V AC
3
13
←
Pt
N O
N C
918
RTD
ON
OFF
OFF O N
O N OFF
OFF
OFF
O N
O N
▲
↑
↑
Note:
Mamual/Auto Convertion: In display estate,press <</M to
shift. AT/M lamp on means manual operation, while off
means autotuning.
For the very first time, please press SET and <</M key
until AT/M lamp flash to enter autotuning estate.In the
future,if the load/control temp. point changes in small
scale (eg. Running the same equipment, and the preset
value changes within ±30℃), the user no need to let it
autotuning again. Because the instrument has recorded the
previous PID parameters. When the instrument is used for
huge capacity heating equipments, the user should set
autotuning value lower 5%-10% than the normal control
value, in order to decrease the exceed-tuning caused by
control.
Normally, the control cycle of the heating equipment
should be 20-30 seconds. For huge capacity heating
equipments, the value should be 30-120 seconds, in order to
longer the use life of the relay. For non-contact output,
such as SSR control output, the value should be 1-3.
90-260V AC/DC
90

Terminal configurations
(If any changed, please refer to the product showing.)
③ Incorrect Control : If the instrument has been used for a long
time, the user find the temperature is hard to rise up to the set
value, meanwhile the outsidesystemrunning well, there must be
something wrong with the parameters of the instrument.
The user need to re-autotuning the instrument. If the instrument
lostcontrol,pleasecheckiftheconnectionofthecontroliscorrect.
If external load is shorted, broken, wrong connection or compo-
nents is damaged, it will cause lost control as well. When it is
necessary, please push out the PCB to check the if the output
terminals is damaged and notavailable.
④Display malfunction : “UUUU”: The input signal exeed
the measured HI range .
ON/OFF control: ▲Set value
←
LO HI
Alarm mode:▲ Set value △ Alarm value AL
LO HI
▲
↑
HYS
▲
OFF
Cooling
0:Deviation HI
alarm ▲ △
↑
OFF ON
HY ←
LO HI
1:Deviatian LO alarm
△ ▲
↑
O N HY
←
LO HI
2:Absolute value HI
alarm ▲ △
↑
HY ←
LO HI
3: Absolute value LO
alarm △ ▲
↑
HY
←
LO HI
4: Section outside alarm △ ▲ △
OFF
HI
5: Section inside alarm
△ ▲ △
ON
HI
Malfunction estimate
① No Display : Check all the connection and wiring if it is all
correct.Speciallypayattention tothe power supplyterminalsand
signal input ternimals.
② Incorrect Didplay: Check if the input signalis conformitywith
the selected symbol.
For TC input, please use the relative compensation cable.
For RTD input, please use low impedence cable. The 3 wires
should at the same length.
If all above mentioned is collect , pleaase use parameter
PVF to modify.
Heating ON OFF
Note:
All the factory setting value of deviation alarm is 1.0.
AL2 hysteresis setting value.
Range ±90, factory setting 1.0
↓
SET
Password setting.
Factory setting 015
Decimal point setting:
0: No decimal 1: One decimal
↓
↓SET
SET
↓SET
↓SET
4
↓SET
↓SET
↓HOLD SET >3 S
SET
↓
↓SET
↓
↓SET
------------------------------------------
AL1 set range: –1999-9999
AL1 mode: 0: Deviation HI alarm 1: Deviatian
LO alarm 2:Absolute value HI alarm
3: Absolute value LO alarm 4: Section outside
alarm 5: Section inside alarm 6: TC broken
alarm ,The factory setting is 2
AL2 mode: The same as AL1.
Range: ±100.Display value
PV = Measured value - PVF
Input signal selection TC: K, J, E, S
RTD: Pt100, Cu50 The factory setting is K
Proportional band (%) range 0.1-3600.
If P=OFF, it means ON/OFF control
Integral time range 0.1-3600. I=OFF means
cancel integral time.
Derivative time range 0.1-3600. D=OFF means
cancel derivative time.
AL2 set range:–1999-9999.
↓
↓SET
↓
SET
↓SET
SET
↓SET
↓SET
SET
SET
Control hysteresis, range: ±100.
It is not available when P ≠OFF
The output control mode ,RELAY=020,
SSR\SCR=001,4-20mA=000.
Control directions: HEAt: heating
COOL: cooling
①
Parameter lock code setting. LcK=000
means unlocked. LcK=010 means locked.
Temperature unit. C means C degree,
F means F degree.
2
TD6/TD8/TD9 are subject to the
drawing on the product.
Only for 4-20mA
=PID,control; =tPV 4-20mA,
transmit;
High analogue output
(when analogue is active)
High analogue output
(when analogue is active)
TD4
RTD~260V/AC
5
4
3
2
1 0
9
8
6
7
1
AL1
1 2
1 1
A
B
B
+
-
TC/mV
←
+
-
SSR
RELAY
+
-
SSR
1 2
1 1
SSR
4
3
0UT1
AL2
←
+
-
4-20mA
TD7
RTD
7
4
3
2
1 3
1 2
1 0
1 1
1
AL1
A
B
B
+
-
TC
RELAY
5
6
OUT1
9
8
1 8
1 7
N C
N0
RELAY
OUT2/AL2
T1
G
▲
7
9
T2
4
3
+
-
SSR
+
-
SSR
87
1 5
1 4
1 6
4-20mA
T1
G
▲
8
6
T2
6
+
-
SSR
7
RTD
90-260V DC/AC
7
6
3
2
1 3
1 2
1 1
9
1 0
1
A
B
B
AL1
4
8
1 5
1 4
5
1 6
NC
N0
2 4
2 3
2 2
2 1
2 0
1 9
1 8
1 7
TC
com
OUT1
6
8
+
-
4-20mA
Application examples
1.Relay output control (forTA9)
Power supply
Heating cord
Heating
equipment
5
4
8
7
6
2
1
16
15
14
12
11
10
17
J-1
FUSE
AL1
OUT1
C
R
J
←
90-260V AC
3
13
←
Pt
N O
N C
918
RTD
ON
OFF
OFF O N
O N OFF
OFF
OFF
O N
O N
▲
↑
↑
Note:
Mamual/Auto Convertion: In display estate,press <</M to
shift. AT/M lamp on means manual operation, while off
means autotuning.
For the very first time, please press SET and <</M key
until AT/M lamp flash to enter autotuning estate.In the
future,if the load/control temp. point changes in small
scale (eg. Running the same equipment, and the preset
value changes within ±30℃), the user no need to let it
autotuning again. Because the instrument has recorded the
previous PID parameters. When the instrument is used for
huge capacity heating equipments, the user should set
autotuning value lower 5%-10% than the normal control
value, in order to decrease the exceed-tuning caused by
control.
Normally, the control cycle of the heating equipment
should be 20-30 seconds. For huge capacity heating
equipments, the value should be 30-120 seconds, in order to
longer the use life of the relay. For non-contact output,
such as SSR control output, the value should be 1-3.