NanoSense LoRa EP5000L User manual

123 rue de Bellevue, 92100 Boulogne Billancourt
France
Tél : 33-(0) 1 41 41 00 02 - www.nano-sense.com
page 1/8
EP5000L air quality probe Installation manual
Ver
Date
Modification / Update
V1
16/12/2019
Initial Version
V2
23/04/2021
Update
V3
09/07/2021
Disassembling the front panel
V4
10/10/2021
Add recommendations and warranty

Installation Guide Modbus E5000 IAQ probe
page 2/8
Summary
1. SECURITY................................................................................................................................................................................. 3
2. POSITIONING .......................................................................................................................................................................... 3
3. DISASSEMBLING THE FRONT PANEL ........................................................................................................................................ 5
4. FLUSH MOUNTING .................................................................................................................................................................. 5
5. SURFACE BOX MOUNTING (RENOVATION).............................................................................................................................. 5
6. WIRING ................................................................................................................................................................................... 5
7. INSTALLATION......................................................................................................................................................................... 6
8. CONNECTIONS......................................................................................................................................................................... 6
9. POWER ON.............................................................................................................................................................................. 6
10. NFC ......................................................................................................................................................................................... 7
11. REMOVING THE FRONT PANEL OF AN INSTALLED PROBE........................................................................................................ 7
12. DISCONNECTION ..................................................................................................................................................................... 8
13. RECOMMENDATIONS.............................................................................................................................................................. 8
14. WARRANTY ............................................................................................................................................................................. 8

Installation Guide Modbus E5000 IAQ probe
page 3/8
1. Security
WARNING
Danger of death, risk of electric shock and fire!
The installation should only be undertaken by a qualified electrician!
To apply for correct bus and power cables and to activate the device, comply with the state of the art
and standards.
Any intervention or modification to the device will invalidate any warranty claim.
• Do not use this probe in environments with regular exposure to silicon vapors (HMDS) because this
gradually alters the sensitivity of the VOC sensor.
• Do not use the sensors for measuring gas content relating to safety!
• Use the probe only with secured low voltages!
2. Positioning
The position of the probe is crucial vis-à-vis efficiency and energy savings for
ventilation, heating and cooling.
• The probe is designed to ensure air quality; it must be placed in the area of
occupancy of the premise served by outlet vents, on a wall at eyes level
(breathing human level, between 1.5 and 1.8m).
• Avoid drafts (near openings, blowing air, doors, outlet vents) and dead zones
(niche, shelves and curtains).
• Avoid orthogonal walls (corners of room in particular)
• Avoid heat sources and the proximity of occupants (radius of 1 m from
workstation).
• Position the probe vertically on a wall or partition.
This device is not intended for installation in duct or ceilings.
• Avoid direct exposure to sunlight. Consider all seasons sun positions
• The measurement of luminous intensity is mainly intended for the measurement of scattered light. This
is what corresponds to the perception of our eyes. The positioning of the probe must take into account
the quality of the desired measurement.

Installation Guide Modbus E5000 IAQ probe
page 4/8
The following graph shows how the different contributions of natural light combine without even taking
into account the generally zenithal artificial lighting:
Consideration should also be given to the receptivity of the light sensor which is mounted vertically
similar to our eyes:
Any work not in accordance with this documentation or
changes to the device will invalidate all warranty claims.

Installation Guide Modbus E5000 IAQ probe
page 5/8
3. Disassembling the front panel
The front panel is clipped on the apparatus.
Put the probe on a table, the front glass facing the table
(connector up)
With your fingernails or your finger move away one clip of the
front panel peripheral from the apparatus and pull the apparatus
up.
Do not spread the outline too far and do not exert pressure on the
glass with your hand or other means as this may disassemble the
front panel.
4. Flush mounting
Use the multi material backbox provided or an airtight insulated backbox with a
waterproofing membrane through which the sheath passes. If the backbox passes
through the sealing plane, seal between the backbox and the partition with a
specific VOC free and silicone free sealant. If ordering the backbox separately:
Make sure that the backbox doesn’t contain Silicone.
The internal depth of the case must be at least 50mm.
The internal diameter (about 64mm) shall have a 40x40mm space free up to
the bottom)
The space between screws shall be 60mm
The height of the screws heads shall be 2mm max)
5.Surface box mounting (renovation)
Use the specific wall surface box (To be ordered separately).
This box has 4 pre-cut cable passages (one on each side) for wiring
under trunking.
In case of a recessed cable, the bottom of the box has a pre-cut central
pad.
Fix the box to the wall with four screws, checking
the direction (arrow inside the box indicating the
"UP" side)
Fix the probe into the box
6. Wiring
Be careful, wiring must be sealed. Incoming air, even slight, would seriously jam the
temperature, humidity and air quality measures.
When the switchboard is located in the heated volume: caulk arrivals between cables and
ducts at the switchboard level.
When the switchboard is out of the heated volume, caulk between cables and ducts
before entering the heated volume. A sealing plug must also be placed between
duct and cable reaching the EP5000 probe to prevent air entry.
When the sealing of the duct is not possible, use a specific sealant without silicone
and VOC.
In case of use of electrical backbox, select an airtight case with sealing membrane
Ø 67/68

Installation Guide Modbus E5000 IAQ probe
page 6/8
from which the duct passes through. If the case crosses through the sealing plane
(plasterboard), seal between the casing and panel with a special sealant without
silicone and VOC.
Connectors are specified for rigid cable 18 to 24 AWG (1 to 0.5mm dia.) or twisted
20 to 22 AWG (0.8 to 0.65mm dia.)
The connectors accept two 0.8mm cables on the same terminal in order to chain
several sensors. Beware of line losses, a 0.8mm cable has a resistance of 21Ω
per Km.
7. Installation
It is recommended to install the probe at the end of the work (after painting and using
silicone-based products).
Connect the 24V DC Power Supply cables on the terminal block on the back of the
product. Pay attention to marking: Modbus A & B and power supply polarity. Indeed,
the LoRa version can also have an operational Modbus connection.
Just push the stripped ends (flexible or rigid) into the connector. In case of a multi-
strand cable, make sure to well twist them before inserting them. In case of
difficulty, push the release tab. Respect the polarity (non-destructive).
Make sure to respect the Up marking otherwise the temperature and humidity
measurement will be jammed.
Screw the plate on the backbox.
Plug the front panel onto the plate. Pay attention to the position of the connector in
the back of the front plate.
If well mounted, the transparent window of the light sensor shall be on top middle.
8. Connections
The power supply must be continuous (DC) and between 12 and 32V (24V nominal).
9. Power on
Few seconds after power-up, all LEDs will be activated individually for a visual
test. At the end of the cycle, failure message made of blink between orange and red
LED may appear during few seconds, the time to interrogate all sensors
Then, the blue LED shall "breathes" if the air quality is good enough.
The start-up cycle includes built in tests and visual checks of LEDs.
The cycle lasts about one minute in total.
LEDs indicate faults as follows:

Installation Guide Modbus E5000 IAQ probe
page 7/8
LED code on the front panel
Identification #
Defective FRU
No LED active
NA
Power supply failure suspected or
probe power supply board
Red LED on for 5 seconds
Followed by a yellow flash
1
Front panel board.
Followed by 2 yellow flashes
2
Single band CO2 sensor module.
Followed by 3 yellow flashes
3
Dual band CO2 sensor module
Followed by 4 yellow flashes
4
VOC sensor module
Followed by 5 yellow flashes
5
Motherboard
Followed by 6 yellow flashes
6
Interconnection board
Followed by 7 yellow flashes
7
Particle sensor board
Followed by 8 yellow flashes
8
Power supply board
Red LED blinking
9
Multiple failures
Alternation Red Blue
10
Perishable sensor reaching the end
of life.
All LEDs blinking
11
No communication between front
panel and probe. (after 30 seconds)
10.NFC
Used to recover and register LoRaWAN keys (See commissioning manual and smartphone application)
11.Removing the front panel of an installed probe
There are 4 side recess.
Insert a small screwdriver head horizontally by 1mm into one recess avoiding to
damage the wall.
Pull the front panel 2mm from the wall and push the screw driver deeper. (between 2
plastic parts)
Move the screwdriver towards the middle of the side until the front panel unclips from
the device.
Be careful not to fall the panel down as the tempered glass may break apart.

Installation Guide Modbus E5000 IAQ probe
page 8/8
12.Disconnection
13.Recommendations
The EP50000 probe guarantees you precise measurements for years to come, provided you give it some
attention ...
•Do not install your probe near sources of alcohol, gasoline, fuel oil, lubricants, paint or chemicals.
The VOC sensor would be contaminated.
•Do not spill aerosol products such as deodorants, perfumes, paints, lubricants, etc. near the probe.
•Avoid contact or proximity with silicone-based materials.
•Do not use detergent or solvent to clean the probe, chemicals can cause sensor failure by
contaminating or damaging it temporarily or permanently.
•Do not immerse or spray any liquid in the openings, this could permanently damage the probe.
•Do not attempt to expect an accurate VOC measurement immediately after exposure to high
concentration, the sensor requires time to recover and perform to its full potential.
14.Warranty
This probe was manufactured to high quality standards. However, it can happen that it presents a defect
or a failure despite the numerous tests to which it has been subjected. This device is guaranteed against
any manufacturing or material defect within the limits of the following provisions:
•The warranty is strictly limited to the exchange or repair in the factory of parts recognized as
defective, after examination and control, to the exclusion of any other compensation.
•The warranty period, offered by the manufacturer, is one year and begins to run from the date of
purchase.
•It is only effective if the device has been used in accordance with the installation instructions,
recommendations and good practice.
•Are excluded from the guarantee:
-Damage resulting from abnormal conditions of use.
-Damage caused by shocks or excessive mechanical forces,
-Damage or accidents resulting from negligence or resulting from a transformation or -
transformation attempted of the device.
-Damage due to disassembly and improper reassembly of the probe.
•The warranty is only valid for devices that are returned to the manufacturer's address.
•Interventions under the guarantee cannot have the effect of extending the duration of the
guarantee.
•The provisions of this guarantee are not exclusive of the benefit, for the benefit of the purchaser,
of the legal guarantee for defects and latent defects which applies in any event.
Table of contents
Other NanoSense Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Elma
Elma CENTER 390 instruction manual

Nikon
Nikon Coolshot 40i instruction manual

Hanna Instruments
Hanna Instruments HI 8424NEW instruction manual

Sony
Sony DVW-250 Maintenance manual

Agilent Technologies
Agilent Technologies OmniBER 720 user guide

Endress+Hauser
Endress+Hauser Micropilot FMR67B technical information