Fan Starter
INSTRUCTION MANUAL
Fan Starter 4
4 kW 400 V 3~(+N) 50 Hz
ART. NO. 512337

Fan Starter 4
2
List of contents Page
CE, Declaration of conformity 3
Safety 4
Technical data 4
Accessories 4
Description 4
Installation 6
Component list 7
Lay out 8
Main circuits diagram 9
Control circuits diagram 10
Interconnection diagram, general 11
Interconnection diagram, OPTION 12
Interconnection diagram, FILTERMAX 13

Fan Starter 4
3
s product is designed to meet the requirements of the relevant EC directives. To maintain this
status all installation, repair and maintenance work must be carried out by qualified personnel
using only original spare parts. Contact your nearest authorised dealer or AB Ph. Nederman
& Co. for advice on technical service or if you require spare parts.
Declaration of conformity
We, AB Ph. Nederman & Co., declare under our sole responsibility that the Nederman
product:
- Fan Starter Art. No 512337
to which this declaration relates, are in conformity with
the following standards or other normative documents:
EN 50 081-1, EN 50 082-2, EN 60 439-1
following the provisions of Directive
89/336/EEC, 92/31/EEC, 73/23/EEC
AB Ph. Nederman & Co.
Sydhamnsgatan 2
S-252 28 Helsingborg Sweden
1999-12-21
________________________________
Magnus Hammarlund, Product Manager
SAFETY
Warning! Only a competent electrician may install the Fan Starter.
Warning! If start signal is activated the fan will automatically start after a
voltage drop out.
Warning! At any work on the installation the main switch must be switched
off and locked.
Warning! A separate safety/maintenance switch shall be installed close to
the fan, if the fan and the Fan Starter are mounted in different
locations.
Warning! Even when the Fan Starter is powered down, there may be
external control voltage at terminal X1.

Fan Starter 4
4
TECHNICAL DATA
Type Direct start
Voltage 400 V 3~(+N) PE 50 Hz
Suitable Motor Max 4 kW 400 V
Input fuse Max 25 A
Control voltage 24 V AC 50 Hz
Transformer 150 VA,
Supply to external 24 V AC, 75 VA
equipment (100 VA available after start of motor.)
230 V AC max 6 A, only if Neutral (N) is
connected
Protection class IP 54
Weight 15 kg
Dimension H x W x D 400 x 400 x 200 mm
Accessories
Safety/Maintenance switch 3 pole 372076
Fan Timer 372077
Running time meter 372081
Voltage separation relay 12 V AC 372148
24 V AC 372149
DESCRIPTION
Fan Starter 4 is a direct starter for Nederman NCF Fans.
The Fan Starter is fitted with a 4-pole main switch interlocked with the door so
that the door can not be opened if the switch is on.
Control voltage is 24 V AC supplied by an internal transformer.
The Fan Starter is prepared for connection with different components in an
extraction system. If Neutral is connected (N) a single-phase supply of 230 V
is available for external equipment, such as FILTERMAX, MAGNA-system or
automatic dampers. Supply with 24 V AC 75 VA, (100 VA after start of motor)
is also available for Fan Timer or other external 24 V AC equipment. The 24 V
AC can be connected continuously (terminal 3-4) or with S1 in pos. "AUTO"
(terminal 111-112, not available when connected to FILTERMAX)

Fan Starter 4
5
The Fan Starter can be started and stopped with the switch on the door, by
turning it to position "1" it starts and by turning back to "0" it stops. Position
"AUTO" is used to start and stop the Fan Starter when connecting external
start/stop signals. Fan Timer or other maintained start/stop signal as well as
remote impulse start and stop can be connected.
If not position "AUTO" shall be used the text "AUTO" can be covered by the
enclosed plastic label.
When connected to FILTERMAX the AUTO-0-1 switch acts as a remote start
switch for the FILTERMAX. The FILTERMAX Fan start-output will then
activate the contactors in the Fan Starter. With FILTERMAX the remote
impulse start and stop can not be connected.
The white indication lamp indicates running fan. The yellow fault indication
lamp indicates basically tripped motor overload protector, with FILTERMAX it
indicates the ALARM signal (service or A-Alarm). Tripped motor overload
protector will be indicated on the FILTERMAX Control panel with a red lamp at
the fan symbol.
The start of a NCF fan is a rather heavy start and repeated starts will trip the
motor overload protector. There is a timer installed then repeated stop could
be expected. With switch S1 is in position ”Auto” when a start signal from
external contacts for example hood or automatic dampers.
External start signal must be a potential free contact. To start from extraction
arms with light a voltage separation relay must be used, see accessories.

Fan Starter 4
6
Installation
Study these installation instructions carefully before proceeding.
Failure to observe the warnings and instructions given may cause a
malfunction or personal hazard.
Warning! Before you begin read "Safety" on page 3.
Dimension the cables and fuses in accordance with the motor current.
Always pay attention to local legislation when sizing the cables and fuses.
Small area in a 24 V system can cause a poor short circuit protection. For
terminals 3 -114 use minimum 1,5 mm2if cable is up to 10 m long and
minimum 2,5 mm2if cable is up to 20 m long. Larger area if cable is longer.
The current value for the motor overload protector has to be set.
For the direct starter set the value to the motor current at 400 V. See the
motor plate.
Connect the motor in accordance with the power circuit diagram.
Check the fan direction.
A separate safety/maintenance switch shall be installed close to the fan, if the
fan and the Fan Starter are mounted in different locations. The control contact
in the safety/maintenance switch shall be connected to the Fan Starter
(terminal 109-110).

Fan Starter 4
35
COMPONENT LIST
ITEM NAME MANUFACTURER TYPE REMARKS
Enclosure
Mounting Plate
Gland Plate
Wall Fixing Brackets
Himel CRN-44/200
MM-44
TSA-CRN/C
PFCR
F2 Electronic overload
relay Allen-Bradley 193-EA1FB 3,7 - 12 A
H1 Pilot Lamp
Incandescent Lamp Allen-Bradley 800EP-PM7D0
800E-N157 Transparent
Ba 9s 24 V 1,4 W
H2 Pilot Lamp
Incandescent Lamp Allen-Bradley 800EP-PM5D0
800E-N157 Yellow
Ba 9s 24 V 1,4 W
K1M Contactor Allen-Bradley 100-C09KJ10
Q1 Main Switch
Fourth Pole
Shaft
Actuator
Allen-Bradley 194E-A25-1753
194E-A25-NP
164L-3393
194L-HE6G-175
Q2 Circuit breaker Terasaki TDD-II 1 S 2-pole, 1 A
Q3 Circuit breaker Terasaki TDD-I 6 S 1-pole, 6A
Q4 Circuit breaker Terasaki TDD-I 6 S 1-pole, 6 A
S1 Selector Switch
Operator
Latch
Contact Block
Allen-Bradley 800EP-SM32
800E-A3L
800E-3X10
T1 Transformer ETV, Åkarp 09703 400/24 V, 150 VA
X1 Terminal Row Allen-Bradley 1492-WG6
1492-WG4
1492-W4
PE (1 pcs.)
(2 pcs.)
(20 pcs.)
XT Terminal AC 24 V Allen-Bradley 1492-WKD3
1492-WG4 Isolating Terminal (1 pcs)
(1 pcs.)
K5T Timer 700-FEB3TU23 Pre-set 10 minutes
P1T Running Time Meter OPTION Art. No 372081
MS Safety/Maintenance
switch OPTION Art. No 372076

Fan Starter 4
36

Fan Starter 4
37

38
Fan Starter 4

Fan Starter 4
39

Fan Starter 4
40
Fan Starter 4
8

Interconnection diagram, FILTERMAX
41
Fan Starter 4

Manufacturer:
AB Ph. Nederman & Co
Sydhamnsgatan 2
SE-252 28 Helsingborg, Sweden
Telephone: Int. +46 42 18 87 00
Fax: Int.+46 42 14 79 71
www.nederman.se