NELSEN WATER NRO ROC2HE-UL User manual

Nelsen NRO ROC2HE-UL
System Controller Documentation
Systems w/CPU-4 Control Board
Manufactured after March 2020
Since 1954


1
Table of Contents
Contents.........................................................................................................................................................................................................................................................................................................................Page #
Specifications, Table 1......................................................................................................................................................................................................................................................................................................2
Schematic, Figure 1..............................................................................................................................................................................................................................................................................................................3
Controller Overview, Figure 2...............................................................................................................................................................................................................................................................................4
Controller Detail: CPU-4..................................................................................................................................................................................................................................................................................................5
Controller Detail: TB-1.......................................................................................................................................................................................................................................................................................................6
Conductivity Probe Installation, Figure 5..........................................................................................................................................................................................................................................7
Installation Instructions...................................................................................................................................................................................................................................................................................................7
Controller Programming: Accessing Hidden Menus, Figure 6....................................................................................................................................................................8
System Start-up w/Permeate Flush..........................................................................................................................................................................................................................................................8
Controller Programming: Program Selections, Table 2.............................................................................................................................................................................................9
Controller Programming: Menu Navigation, Figure 7............................................................................................................................................................................................. 10
Controller Fault Displays................................................................................................................................................................................................................................................................................ 11-12
Warranty.............................................................................................................................................................................................................................................................................................................................................. 13

2
Table 1 - Specifications
Inputs
Tank level switches (2) Normally-Closed. Can be used with a single level switch.
Inlet pressure switch Normally-Open.
Pretreat lockout switch Normally-Open.
The Tank, Low Pressure and Pretreat inputs are 50% duty cycle square wave,
10VDC peak @ 10mA max.
The switch inputs are dry contacts only. Applying voltage to these terminals
will damage the controller.
Controller Power 110-120/208-240 VAC, 60/50Hz (Range: 110-240 VAC)
Permeate Conductivity 0-3000 PPM, 0-6000 μs (standard sensor, CP-1, K=.75)
Feed Conductivity (opt) 0-3000 PPM, 0-6000 μs (standard sensor, CP-1, K=.75)
Output Circuit Ratings
Feed Solenoid 1A. Voltage is the same as motor/supply voltage.
Flush Solenoid 1A. Voltage is the same as motor/supply voltage.
Motor 1.0 HP/110-120V, 2.0 HP/208-240V.
Circuit Protection
Relay Fuse F1 5x20mm - 2 Amp - BelFuse 5ST 2-R
Note: The fuses shown above are for supplemental protection only. Branch
circuit protection and disconnect means must be provided externally.
See Field Wiring Diagram for Branch Circuit protection requirements.
Other
Dimensions 7" tall, 7" wide, 4" deep. Nema 4X Polycarbonate Hinged Enclosure.
Weight 2.6 lb. (Basic Configuration, not including optional wire harness, etc.)
Environment 0-50°C, 10-90%RH (non-condensing)
Note: After our modifications the enclosure rating is Nema 1.

3
Figure 1 - Simplified Schematic

4
Figure 2 - Controller Overview
Terminal Board (TB-1 Re-E)CPU Board (CPU-4)
Conductivity Probe
Connections
Display
(4 line, 20 character)
Clear, concise feedback
on the RO’s status.
Alarm
Display backlight
flashes along with
audible beeper to
indicate alarm condition.
Keypad
System ON/OFF,
Up Arrow
Down Arrow
Manual Run,
Manual Flush

5
Typical Configuration
Permeate Conductivity Probe
Shield
White
Black
Cable to
Terminal Board
Figure 3 - Controller Detail: CPU-4
Typical Configuration

6
Figure 4 - Controller Detail: Terminal Board, TB-1 (See Fig. 1 for schematic)

7
Figure 5 - Conductivity Probe Installation
1 Drill the enclosure as needed and install liquid-
tight fittings for the wiring.
NOTE: The Controller can be ordered
pre-drilled or with fittings installed, or with
fittings and wiring installed. Contact Nelsen
Corporation for details.
2 Mount the enclosure in the desired location on
the RO system.
3 Bring the wires from the peripheral devices
into the enclosure and connect them to the
appropriate terminals. (See Figure 1, Figure 3 and
Figure 4.)
4 Install the conductivity cell in the permeate line.
(See Figure 5 for conductivity cell installation
instructions.)
7 Connect the conductivity cell to the terminals on
the CPU Board. (See Figure 3)
8 Provide power to the RO system.
9 Press the System On/Off switch to turn the
system ON.
10 Program Mode 2 is default (See Table 2) which is
a general purpose setting, without a flush valve.
NOTE: The Program Settings can be
customized to suit the specific needs
of an OEM and pre-programmed at the
factory with your settings. Contact Nelsen
Corporation for details.
11 Make any other changes you want to the
settings. Press System On/Off to save your
changes.
12 The controller is now ready for service.
NOTE: YOU MUST REMOVE THE JUMPER
WIRE FROM E23 TO E24 if using a single
point High Level RO water shut off float
switch control and connect the float switch
wires to terminals E23 and E24 (See Fig. 4).
If you are using a piggyback float plug leave
the jumper wire in place.
Installation
Install the Conductivity Probe in the “Run”
of a Tee or equivalent location. Orient the
probe so that air can not become trapped in
the area near the probe.
FLOW
FLOW
Conductivity
Probe

8
Figure 6 - Controller Programming: Accessing the Hidden Menus
System Start-up w/Permeate Flush
1 With the System ON, Press and
Hold the Up and Down Arrows.
2 With the Up and Down Arrows
depressed, Press the System On/Off
button. The menu will switch to the
RO Presets menu shown in Figure 7.
For systems equipped with a Permeate Flush, you must follow the procedure below for proper system start-
up. When there is no Permeate Water in the tank the RO will not start.
1. With the system on, Press and Hold the Up and Down Arrows
2. With the Up and Down Arrows depressed, Press the System On/Off button. This will switch to the
Hidden Menus as shown above.
3. If not already on the RO Presets Program, Press the Up or Down Arrows until you reach this screen.
4. Once on the RO Presets Program Screen, Press Manual to Edit this Screen.
5. Press the Up or Down Arrow to change to Program 2
6. Once on Program 2, Press Manual to Exit the screen.
7. Press System On/Off to save the changes and return to the Home Page.
Once your Permeate Tank has filled enough to do a proper permeate flush, follow the steps again
changing from Program 2 back to Program 3.

9
The controller has 4 separate, user-selectable sets of settings for configuring the RO. The factory default
settings are shown below. The settings are identical except for variations in the flush behavior.
• Program 1, High Pressure flush
• Program 2, No Flush
• Program 3, Permeate Flush, (low pressure, inlet valve closed)
• Program 4, Low Pressure, feed water flush
See the previous page for instructions on how to access the menu for selecting these programs.
See Appendix A for a detailed explanation of the Parameters and their affect on the RO’s operation.
Table 2 - Controller Programming: ROC2HE Program Selections
Parameter Value Program 1 Program 2 Program 3 Program 4
Tank Level Switch delay
(actuation and de-actuation) Seconds 2 2 2 2
Pressure Switch delay (actuation and de-actuation) Seconds 2 2 2 2
Pretreat Switch delay (actuation and de-actuation) Seconds 2 2 2 2
Pump start delay Seconds 10 10 10 10
Inlet Solenid stop delay Seconds 1 1 1 1
Pump start retry interval (restart delay after LP fault) Seconds 60 60 60 60
Low pressure fault shutdown, # of faults Faults 5 5 5 5
Low pressure fault shutdown, time period to count faults Minutes 10 10 10 10
Low pressure fault shutdown, reset after shutdown Minutes 60 60 60 60
Low pressure time out fault Seconds 60 60 60 60
Flush Behavior High Pressure No Flush Perm Flush Low Pres Flush
Startup Flush: Minutes from last ush Minutes 0 0 0 0
Startup Flush: Duration Seconds 0 0 0 30
Periodic Flush: Interval Minutes 60 0 0 0
Periodic Flush: Duration Seconds 30 0 0 0
Shutdown Flush: Time from last ush Minutes 10 0 0 0
Shutdown Flush: Minumum operation Minutes 30 0 0 0
Shutdown Flush: Duration Seconds 60 0 60 60
Idle Flush: Interval * Minutes 0 0 0 0
Idle Flush: Duration * Seconds 0 0 0 0
Timed Manual Run Minutes 5 5 5 5
Timed Manual Flush Seconds 5 0 5 5
* These features are disabled by default due to the potential for confusion on the part of end-users in the field.
They can be enabled when needed via the OEM PC programming interface which allows changes to all of
the values shown above.

10
Figure 7 - Controller Programming: Menu Navigation

11
Controller Fault Condition Displays
Below are examples and explanations of the displays which accompany the fault conditions possible on the
CPU-4. Fault conditions always indicate a problem of some sort which requires corrective action. the displays
provide sufficient information to recognize the source of the fault and the required corrective action.
Low Pressure Fault: (System is responding to low pressure condition per system settings)
Line 1 “Service Fault”
Line 2 “Low Feed Pressure”
Line 3
Line 4 “Restart in MM:SS”
Pre Treat Fault: (Pretreat Switch is closed indicating problem with pretreat system).
Line 1 “Service Fault”
Line 2 “Pretreat”
Line 3
Line 4 “Check Pretreat Sys.”
Permeate Conductivity Fault: (Permeate conductivity is higher than the alarm set-point.)
Line 1 “Service Fault”
Line 2 “Permeate TDS xxx ppm” or “Permeate Cond xxx uS”
Line 3 “Alarm SP xxx ppm” or “Alarm SP xxx uS”
Line 4 “To Reset Push OFF/ON”
Feed Conductivity Fault: (Feed conductivity is higher than the alarm set-point.)
Line 1 “Service Fault”
Line 2 “Feed TDS xxx ppm” or “Feed Cond xxx uS”
Line 3 “Alarm SP xxx ppm” or “Alarm SP xxx uS”
Line 4 “To Reset Push OFF/ON”
Conductivity Probe Error messages:
Line 2 “Inteference” - Noise detected by conductivity circuit, valid measurement not possible.
Line 2 “Over-range” - Measurement is out of range for the circuit, probe may also be shorted
Line 2 “Probe shorted” - Short circuit detected on temperature sensor in probe
Line 2 “Probe not detected” - Open circuit detected on temperature sensor in probe (white & unshielded wire)
Line 2 “Probe Startup 1” - Internal reference voltage too high to make valid measurement
Line 2 “Probe Startup 2” - Internal reference voltage too low to make valid measurement
Line 2 “Probe Startup 3” - Internal excitation voltage too high to make valid measurement
Line 2 “Probe Startup 4” - Internal excitation voltage too low to make valid measurement

12
Controller Fault Condition Displays
If RO Not Working and Display Shows “Tank Full” or “Tank Full Draw Down”
1. If using a single point high level float switch, the jumper in the wiring instructions must be installed. This
needs to be checked to make sure it is not loose and or disconnected, which would cause a failure and
one of the displays above. ie. Remove jumper and reinstall, making sure of a good connection. Re-check
display and operation.
2. Check the switch in the tank to make sure it is operating correctly. Check the switch with a multi-meter for
correct “on-off” operation. Replace switch or level control if faulty.
3. If someone connected 110v to the terminal strip connection for the high level shut off, they could have
fried the “opto-isolator”.
4. Also, if there were major lightning strikes and power outages with surges, it is possible that you may have
had a power surge that sent electric current to the dry contacts and possibly fried the “opto-isolator”.
This will prevent the system from turning on, and the display will show Tank Full messages.
5. If the jumper is verified to be in place with good connections, and if the high level cut off switch in the
storage tank is verified to be operational, then the board might need to be replaced due to number 3 or 4.

13
Nelsen Corporation (“Nelsen”) provides this limited warranty as described below (the “Limited Warranty”).
Limited Warranty
Subject to the terms of this Limited Warranty, Nelsen warrants to the original buyer (“Buyer”) of this Water Conditioner
product (the “Product”) solely from a Nelsen authorized dealer that the Product will be free from defects in material or
workmanship for a period of one (1) year after the date of original installation. This Limited Warranty shall apply only if
the Product is installed, operated and maintained in strict accordance with Nelsen’s or the manufacturer’s guidelines
and other legal requirements. The Product is sold with the understanding that Buyer has independently determined
the suitability and compatibility of such Product for Buyer’s purposes. Any statements, technical information or
recommendations concerning the Product or any parts therein by Nelsen are based upon data provided to Nelsen by its
suppliers and believed to be accurate, but do not constitute a guarantee or warranty. This Limited Warranty shall not
cover and shall be null and void if, in Nelsen’s discretion, the Product, or any parts therein, are: (a) manufactured by a
third party manufacturer; (b) modified after sale or use of replacement parts not specified by manufacturer requirements;
(c) improperly installed, stored, used, operated, handled or maintained; or (d) abused, misused or otherwise damaged
for any reason, including due to negligence, weather, fire, lightning, power surges or other acts of God or exposure to
freezing or hot water or the effects of normal wear and tear.
Third Party Warranties
In lieu of the above Limited Warranty, the Product, or any parts therein, may be covered by a third-party manufacturer’s
warranty. Nelsen’s authorized dealer will provide Buyer with a copy of any third-party manufacturer warranty prior to
purchase. Nelsen shall transfer and assign to Buyer any and all third-party manufacturer’s warranties on the Product,
or any parts therein, subject to the conditions and exclusions in the manufacturer’s warranty. Buyer’s exclusive remedy
under such third-party manufacturer’s warranty shall be against such third-party manufacturer and not Nelsen. Buyer
may need to register the Product with a third party manufacturer in order to obtain its warranty.
Additional Conditions
• This Limited Warranty does not cover any membranes or filters.
• This Limited Warranty shall not cover the Product if operated at water pressures or water temperatures or with
water contaminants that exceed manufacturer’s guidelines.
• The Product may include interconnecting piping that may have leaks, even if tested at the time of manufacture,
due to pipe vibrations and handling. The installer of the goods is responsible for checking the system for leaks upon
start-up and making any repairs if necessary.
• This Limited Warranty does not cover damage or failure of the Product, or any part therein, caused by friction, wear,
chemical attack or debris build-up on wear parts. For purposes hereof, “wear parts” shall include, without limitation,
end cap quad rings and parts requiring replacement under recommended maintenance procedures, including,
without limitation, o-rings and gaskets.
Warranty Claims
All claims under this Limited Warranty shall be submitted by Buyer to the authorized Nelsen dealer who sold the
Product in writing and shall include the Buyer’s name, address, telephone number, date of purchase of the Product,
receipt evidencing proof of purchase and a copy of this Limited Warranty. Nelsen or its authorized dealer will investigate
the claim. Buyer must fully cooperate in investigating and evaluating the claim, including, without limitation, providing
additional information upon request. TO BE ELIGIBLE FOR COVERAGE UNDER THIS LIMITED WARRANTY, BUYER
MUST SUBMIT A CLAIM WITHIN SIXTY (60) DAYS OF THE DATE THAT THE ALLEGEDLY DEFECTIVE PRODUCT OR
PART IS FIRST DISCOVERED BY BUYER AND, IN NO EVENT, LATER THAN SIXTY (60) DAYS AFTER THE WARRANTY
PERIOD HEREIN.
Continued on next page.
Appendix C - Controller Limited Warranty

14
© Nelsen Corporation Part # NRO-ROC2-MAN — RevE 0322
Repair or Replacement/Credit
Subject to the conditions and limitations herein, if Nelsen determines that the Product, or any part therein, does not
conform to this Limited Warranty, Nelsen will repair or replace the defective Product or part therein. Non-conforming
Products or parts therein must be returned to Nelsen’s authorized dealer at Buyer’s cost. Any replaced Products, or any
parts therein, shall be retained by and become the property of Nelsen. If Nelsen determines that the repair or replacement
of the Product or part therein is not commercially practicable, Nelsen will issue a credit in favor of Buyer in an amount
not to exceed the purchase price of the Product. Notwithstanding anything to the contrary herein, this Limited Warranty
does not cover any cost or labor associated with the removal or re-installation of the replacement Product or part
therein or any shipping costs associated with the returned Product or part therein, which remains the sole cost, risk and
responsibility of Buyer, unless otherwise agreed in writing by Nelsen.
Eligibility/Non-Transferable
This Limited Warranty applies only to Buyer if the Product is purchased from a Nelsen authorized dealer. This Limited
Warranty is personal to Buyer and may not be assigned or otherwise transferred by Buyer. Any attempt to transfer this
Limited Warranty shall be null and void and not recognized by Nelsen.
Disclaimer of Other Warranties/Limitation on Liability
EXCEPT AS PROVIDED ABOVE AND TO THE EXTENT PERMITTED BY LAW, THERE ARE NO OTHER REPRESENTATIONS
OR WARRANTIES WITH RESPECT TO THE PRODUCT, EITHER EXPRESS OR IMPLIED, WRITTEN OR ORAL, OR ARISING
UNDER CUSTOM OF TRADE, INCLUDING, WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE. NO REPRESENTATIONS OR WARRANTIES AT ANY TIME MADE BY ANY
EMPLOYEE, AGENT OR REPRESENTATIVE OF NELSEN SHALL BE EFFECTIVE TO VARY OR EXPAND ANY WRITTEN
WARRANTY OR THE TERMS HEREOF. TO THE EXTENT A WAIVER OF IMPLIED WARRANTIES IS PROHIBITED BY
LAW, ANY IMPLIED WARRANTIES SHALL BE LIMITED TO THE DURATION OF ANY WRITTEN WARRANTY PROVIDED
BY NELSEN. IN NO EVENT SHALL NELSEN BE LIABLE TO BUYER OR TO ANY THIRD PARTY FOR CONSEQUENTIAL,
INCIDENTAL, SPECIAL OR PUNITIVE DAMAGES, OR FOR LOST PROFITS OR LOSS OF USE, RESULTING FROM OR IN ANY
MANNER RELATED TO THE PRODUCT, ITS DELIVERY, NON-DELIVERY, USE, OR INABILITY TO USE THE SAME, WHETHER
SUCH DAMAGES BE CLAIMED UNDER CONTRACT, TORT OR ANY OTHER LEGAL THEORY. NELSEN’S TOTAL LIABILITY
UNDER THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, IS LIMITED TO REPAIR OR REPLACEMENT OF, OR
CREDIT FOR, THE PRODUCT OR ANY PART, AS STATED HEREIN.
Waiver of Class Action
ANY AND ALL CLAIMS ASSERTED BY BUYER OR ANY OTHER PERSON OR ENTITY SHALL BE RAISED IN AN INDIVIDUAL
CAPACITY AND NOT AS A PLAINTIFF OR CLASS MEMBER IN ANY PURPORTED CLASS OR REPRESENTATIVE
PROCEEDING, WHICH ARE HEREBY WAIVED.
Applicable Law
This Limited Warranty shall be interpreted and governed under the laws of the State of Ohio without giving effect to the
choice of law rules thereof. Nelsen and Buyer irrevocably consent and submit to the exclusive jurisdiction and venue
within the courts of Summit County, Ohio and/or the United States District Court for the Northern District of Ohio in
connection with any litigation arising out of, or in any way relating to, this Limited Warranty or the Product, including, but
not limited to, any and all claims for breach of warranty or products liability, and Nelsen and Buyer expressly waive any
objection to the jurisdiction and/or venue of such courts.
Appendix C - Controller Limited Warranty - continued
Table of contents
Popular Control System manuals by other brands

Shuangri Electric
Shuangri Electric SR618C1 Installation and operating manual

OSCOR
OSCOR OSC 5000 owner's guide

Rockford Fosgate
Rockford Fosgate SSC-500 installation manual

Chauvet
Chauvet Obey 3 user manual

Air Lift Performance
Air Lift Performance 3H user guide

Roger
Roger MC16-PAC-2-KIT installation manual

baltur
baltur ETAMATIC OEM Quick start up guide

Franke
Franke DVS SH07-020 Installation & operating instructions

CIAT
CIAT AQUACIAT POWER LD 602R-3500R instruction manual

SEW-Eurodrive
SEW-Eurodrive IPOS plus manual

Siemens
Siemens SIMATIC HMI ITC1500 V3 PRO Quick install guide

Techtrol
Techtrol VLC Installation & operational manual