
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
20 ClimateMaster Water-Source Heat Pumps
Tranquility 16 (TC) Series
Rev.: 24 January, 2023
Open Loop - Ground Water Systems
Typical open loop piping is shown in Figure 14. Shut off
valves should be included for ease of servicing. Boiler
drains or other valves should be “tee’d” into the lines
to allow acid ushing of the heat exchanger. Shut off
valves should be positioned to allow ow through the
coax via the boiler drains without allowing ow into
the piping system. P/T plugs should be used so that
pressure drop and temperature can be measured.
A monitoring plan should be implemented in these
probable scaling situations. Other water quality issues
such as iron fouling, corrosion prevention and erosion
and clogging should be referenced in Table 3.
Expansion Tank and Pump
Use a closed, bladder-type expansion tank to minimize
mineral formation due to air exposure. The expansion
tank should be sized to provide at least one minute
continuous run time of the pump using its drawdown
capacity rating to prevent pump short cycling. Discharge
water from the unit is not contaminated in any manner
and can be disposed of in various ways, depending on
local building codes (e.g. recharge well, storm sewer,
drain eld, adjacent stream or pond, etc.). Most local
codes forbid the use of sanitary sewer for disposal.
Consult your local building and zoning department to
assure compliance in your area.
Water Control Valve
Note the placement of the water control valve in
Figure 14. Always maintain water pressure in the
heat exchanger by placing the water control valve(s)
on the discharge line to prevent mineral precipitation
during the off-cycle. Pilot operated slow closing
valves are recommended to reduce water hammer.
If water hammer persists, a mini-expansion tank can
be mounted on the piping to help absorb the excess
hammer shock. Ensure that the total ‘VA’ draw of the
valve can be supplied by the unit transformer. For
instance, a slow closing valve can draw up to 35VA.
This can overload smaller 40 or 50 VA transformers
depending on the other controls in the circuit. A typical
pilot operated solenoid valve draws approximately
15VA (see Figure 21). NOTE: the special wiring
diagrams for slow closing valves (Figures 22 & 23).
Flow Regulation
Flow regulation can be accomplished by two methods.
One method of ow regulation involves simply adjusting
the ball valve or water control valve on the discharge
line. Measure the pressure drop through the unit heat
exchanger, and determine ow rate from Tables 8a
through 8e. Since the pressure is constantly varying,
two pressure gauges may be needed. Adjust the
valve until the desired ow of 2.0 to 2.6 l/m per kW is
achieved. A second method of ow control requires a
ow control device mounted on the outlet of the water
control valve. The device is typically a brass tting with
an orice of rubber or plastic material that is designed
to allow a specied ow rate. On occasion, ow control
devices may produce velocity noise that can be reduced
by applying some back pressure from the ball valve
located on the discharge line. Slightly closing the
valve will spread the pressure drop over both devices,
lessening the velocity noise. NOTE: When EWT is
below 10°C, 2.6 l/m per kW is required.
WARNING! Polyolester Oil, commonly known as POE
oil, is a synthetic oil used in many refrigeration systems
including those with HFC-410A refrigerant. POE oil, if it
ever comes in contact with PVC or CPVC piping, may
cause failure of the PVC/CPVC. PVC/CPVC piping should
never be used as supply or return water piping with water
source heat pump products containing HFC-410A as
system failures and property damage may result.
⚠
WARNING!
⚠
Water quantity should be plentiful and of good quality.
Consult table 3 for water quality guidelines. The unit can
be ordered with either a copper or cupro-nickel water
heat exchanger. Consult Table 3 for recommendations.
Copper is recommended for closed loop systems and
open loop ground water systems that are not high
in mineral content or corrosiveness. In conditions
anticipating heavy scale formation or in brackish water,
a cupro-nickel heat exchanger is recommended. In
ground water situations where scaling could be heavy
or where biological growth such as iron bacteria will
be present, an open loop system is not recommended.
Heat exchanger coils may over time lose heat exchange
capabilities due to build up of mineral deposits. Heat
exchangers must only be serviced by a qualied
technician, as acid and special pumping equipment
is required. Desuperheater coils can likewise become
scaled and possibly plugged. In areas with extremely
hard water, the owner should be informed that the
heat exchanger may require occasional acid ushing.
In some cases, the desuperheater option should not
be recommended due to hard water conditions and
additional maintenance required.
Water Quality Standards
Table 3 should be consulted for water quality
requirements. Scaling potential should be assessed
using the pH/Calcium hardness method. If the pH
<7.5 and the calcium hardness is less than 100 ppm,
scaling potential is low. If this method yields numbers
out of range of those listed, the Ryznar Stability and
Langelier Saturation indecies should be calculated.
Use the appropriate scaling surface temperature for
the application, 66°C for direct use (well water/open
loop) and DHW (desuperheater); 32°C for indirect use.
Ground-Water Heat Pump Applications