Transport
F2050 must be transported and stored vertically.
NOTE
Ensure that the heat pump cannot fall over during
transport.
Check that F2050 has not been damaged during transport.
LIFT FROM THE STREET TO THE SET UP
LOCATION
If the surface allows, the easiest method is to use a pallet
truck to move the heat pump to the installation area.
If the heat pump needs to be transported across soft ground,
such as a lawn, we recommend using a crane truck that can
lift it to the installation location. When the heat pump is lifted
with a crane, the packaging must be intact.
If a crane truck cannot be used, the heat pump can be
transported on an extended sack truck. The heat pump must
be taken hold of from its heaviest side and two people are
required to lift it.
LIFT FROM THE PALLET TO FINAL POSITIONING
Before lifting remove the packaging and the securing strap
to the pallet.
Place lifting straps around each foot. It is recommended
that two people perform the lift from the pallet to the base.
SCRAPPING
When scrapping, remove the heat pump in reverse order. In
this case, lift by the base plate rather than the pallet!
Assembly
•Place the heat pump in a suitable location outdoors to
prevent any risk of the refrigerant flowing in through
ventilation openings, doors or similar openings in the event
of a leak. It must also not constitute a hazard to people or
property in any other way.
•If the heat pump is placed in a location where any refriger-
ant leak could accumulate, for example below ground level
(in a dip or low-lying recess), the installation must satisfy
the same requirements that apply for gas detection and
the ventilation of engineering rooms. Requirements regard-
ing sources of ignition must be applied where appropriate.
•Place F2050 outdoors on a solid level base that can take
the weight, preferably a concrete foundation. If concrete
slabs are used they must rest on asphalt or shingle.
•The lower edge of the evaporator must not be lower than
the level of the average local snow depth, or at least 300
mm above ground level. The base should be at least 70
mm tall.
•F2050 should not be positioned next to noise sensitive
walls, for example, next to a bedroom.
•Also ensure that the placement does not inconvenience
the neighbours.
•F2050 must not be placed so that recirculation of the
outdoor air is possible. Recirculation entails reduced power
and impaired efficiency.
•The evaporator must be sheltered from direct wind / ,
which negatively affects the defrosting function. Place
F2050 protected from wind / against the evaporator.
•Large amounts of condensation, as well as melt water
from defrosting, may be produced. Condensation must
be led off to a drain or similar (see section “Condensation
water").
•Care must be exercised so that the heat pump is not
scratched during installation.
Do not place F2050 directly on the lawn or other non solid
surface.
NIBE F2050Chapter 2 | Delivery and handling8
Delivery and handling