
Technical Manual: 0000015 EVC-P (Changes are subject to DCN)
5
• Ref No: NISM/EVC-P/04 • Date: 23.01.19 • Issue: 4
• evolution • EVC-P • Conventional Photoelectric Smoke Detector
Section 5 - INSTALLATION
In normal use, the EVC-P detector will be installed at ceiling level.
Pass the field wiring through the cable hole in the centre and from the
rear of the base. Offer up and affix the base to the ceiling or conduit
fitting with screws via the base mounting holes. Connect the field
wiring to the base terminals, as detailed on page 6 making sure the
wiring does not obstruct fitting of the detector head. Fit the detector
head by inserting it into the base and turning clockwise until the notch
in the detector rim aligns with base locking screw.
The OMNIVIEW™ 360º indicator permits visibility from any angle.
Fit the plastic dust cover supplied over the detector to keep out dust
etc, until the system is commissioned. If the dust cover is not fitted and
the environment is slightly dusty, such as when building work is being
completed, for example, problems of false alarms are likely to occur
after commissioning unless cleaning of the detector is undertaken.
At commissioning, the dust cover should be removed and discarded.
NOTE: THE PLASTIC DUST COVER MUST BE RE- MOVED
FROM THE DETECTOR IN ORDER FOR THE DETECTOR TO
FUNCTION CORRECTLY.
Section 6 - MAINTENANCE
AND CLEANING
Maintenance:
The EVC-P detector is a high quality product engineered for
reliability. In order to obtain optimum performance, periodic
maintenance is required. If proper preventative maintenance is not
carried out, there is a likelihood of malfunction, as a dirty detector is
more likely to cause a false alarm.
Servicing:
Servicing of the system should be carried out in accordance with the
requirements of BS 5839 Part 1, Fire Detection and Alarm Systems
for Buildings: Code of Practice for System Design, Installation and
Servicing.