Notifier AUTOPULSE IQ-318 User manual

AUTOPULSE
®
IQ-318/E/C ANALOG
ADDRESSABLE CONTROL SYSTEM
Fire Alarm Control Panel Installation Manual
(Meets the Requirements of UL 864 9th Edition)
J3
P/N 52864:J3 ECN 15-230
Document 52864
9/29/15 Rev:

2IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property
insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel (FACP) with
remote notification capability—can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
An emergency communication system—typically made up
of an automatic fire alarm system (as described above) and a
life safety communication system that may include an autono-
mous control unit (ACU), local operating console (LOC), voice
communication, and other various interoperable communica-
tion methods—can broadcast a mass notification message.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire or life
safety event.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premises
following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use of
System Smoke Detectors, which is made available at no
charge to all installing dealers. This document can be found at
http://www.systemsensor.com/appguides/. A study by the
Federal Emergency Management Agency (an agency of the
United States government) indicated that smoke detectors
may not go off in as many as 35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A fire
alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-
floor or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls,
chimneys, even wet or humid areas may inhibit particle or
smoke flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predeter-
mined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro-
tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system,
compromising its ability to report a fire.
Audible warning devices such as bells, horns, strobes,
speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or
are located on another floor of a building. Any warning device
may fail to alert people with a disability or those who have
recently consumed drugs, alcohol, or medication. Please note
that:
• An emergency communication system may take priority
over a fire alarm system in the event of a life safety emer-
gency.
• Voice messaging systems must be designed to meet intelli-
gibility requirements as defined by NFPA, local codes, and
Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly
disseminated on any local displays.
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond to or comprehend
the meaning of the signal. Audible devices, such as horns
and bells, can have different tonal patterns and frequen-
cies. It is the property owner's responsibility to conduct fire
drills and other training exercises to make people aware of
fire alarm signals and instruct them on the proper reaction
to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically com-
patible with the control panel. It is essential to use only equip-
ment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premises to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.
The most common cause of life safety system malfunction is
inadequate maintenance. To keep the entire life safety system

IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ-
ated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro-
gramming operation or change in site-specific software. Re-
acceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All compo-
nents, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (non-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic com-
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi-
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Ser-
vices Department if any problems are anticipated or encoun-
tered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-
tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han-
dling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interfer-
ence, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi-
oelectriques depassant les limites applicables aux appa-
reils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
HARSH™ and NIS™ are trademarks; and Acclimate®, FAAST®, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFire®, and
VIEW® are all registered trademarks of Honeywell International Inc. AUTOPULSE™ is a trademark of Tyco Fire Products LP. Echelon® is a registered
trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and
Windows® are registered trademarks of the Microsoft Corporation.
©Monday, November 23, 2015. All rights reserved. Unauthorized use of this document is strictly prohibited.

4IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for
a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.T[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.

AP Placeholder — P/N LSxxxxx-00xAP-E:APRev mm/dd/yyyy 5
Table of Contents
Section 1: About This Manual.................................................................................................. 6
1.1: Standards and Other Documents....................................................................................................................6
1.2: UL 864 Compliance.......................................................................................................................................7
1.3: Related Documents........................................................................................................................................7
1.4: Cautions and Warnings ..................................................................................................................................8
Section 2: System Overview.................................................................................................... 9
2.1: System Description........................................................................................................................................9
2.2: System Components ....................................................................................................................................10
2.3: Compatible Equipment ...............................................................................................................................15
Section 3: Installation............................................................................................................. 17
3.1: Preparing for Installation .............................................................................................................................17
3.2: Installation Checklist ...................................................................................................................................18
3.3: Mounting a Cabinet .....................................................................................................................................19
3.4: Installing Option Boards..............................................................................................................................19
3.5: Connecting the Power Cables......................................................................................................................21
3.6: NAC Connections and Releasing Circuits...................................................................................................24
3.7: Output Relay Connections...........................................................................................................................25
3.8: Backup-Alarm Switches .............................................................................................................................26
3.9: UL Power-limited Wiring Requirements.....................................................................................................27
3.10: Installing EIA-485 Devices .......................................................................................................................28
3.11: Installing Remote Printers and/or CRT......................................................................................................28
3.12: Wiring a Signaling Line Circuit (SLC)......................................................................................................33
3.13: Connecting a PC for Off-Line Programming ...........................................................................................34
Section 4: Applications .......................................................................................................... 35
4.1: Overview......................................................................................................................................................35
4.2: Devices Requiring External Power Supervision..........................................................................................35
4.3: NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit)..................................36
4.4: Central Station Fire Alarm System Canadian Requirements.......................................................................38
4.5: NFPA 72 Proprietary Fire Alarm Systems...................................................................................................38
4.6: Fire/Security Applications ..........................................................................................................................39
4.7: Releasing Applications ................................................................................................................................41
Section 5: Testing the System .............................................................................................. 48
5.1: Acceptance Test ...........................................................................................................................................48
5.2: Periodic Testing and Service........................................................................................................................48
5.3: Operational Checks......................................................................................................................................48
5.4: Battery Checks and Maintenance ................................................................................................................49
6.1: Calculating AC Branch Circuit Current ......................................................................................................50
6.2: Calculating the System Current Draws .......................................................................................................50
6.3: Calculating the Battery Requirements .........................................................................................................54
7.1: Electrical Specifications ..............................................................................................................................56
7.2: Wire Requirements ......................................................................................................................................58
Index......................................................................................................................................... 60

6IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15
Section 1: About This Manual
1.1 Standards and Other Documents
This Fire Alarm Control Panel complies with the following NFPA standards:
•NFPA12CO
2Extinguishing Systems
• NFPA 12A Halon 1301 Extinguishing Systems
• NFPA 13 Sprinkler Systems
• NFPA 15 Water Spray Systems
• NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems
• NFPA 17 Dry Chemical Extinguishing Systems
• NFPA 17A Wet Chemical Extinguishing Systems
• NFPA 72 Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected
Premises Unit (requires UDACT/UDACT-2).
• NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm
Systems.
• NFPA 72 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems (requires TM-4).
• NFPA 72 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems
• NFPA 72 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems (Protected
Premises Unit).
• NFPA 2001 Clean Agent Fire Extinguishing Systems
• NFPA 2010 Fixed Aerosol Fire Extinguishing Systems
The installer should be familiar with the following documents and standards:
• NFPA 72 Initiating Devices for Fire Alarm Systems
• NFPA 72 Inspection, Testing and Maintenance for Fire Alarm Systems
• NFPA 72 Notification Appliances for Fire Alarm Systems
Underwriters Laboratories
• UL 38 Manually Actuated Signaling Boxes
• UL 217 Smoke Detectors, Single and Multiple Station
• UL 228 Door Closers - Holders for Fire Protective Signaling Systems
• UL 268 Smoke Detectors for Fire Protective Signaling Systems
• UL 268A Smoke Detectors for Duct Applications
• UL 346 Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 Audible Signaling Appliances
• UL 521 Heat Detectors for Fire Protective Signaling Systems
• UL 864 Standard for Control Units for Fire Protective Signaling Systems
• UL 1481 Power Supplies for Fire Protective Signaling Systems
• UL 1971 Visual Signaling Appliances
• UL 1076 Proprietary Burglar Alarm Systems
• UL 2017 Standard for General-Purpose Signaling Devices and Systems
• UL 2572 Standard for Mass Notification Systems
• UL 60950 Safety of Information Technology Equipment
Underwriters Laboratories of Canada (ULC)
• Standard CAN/ULC-S527-M99
• CAN/ULC-S524-M91 Standard for the Installation of Fire Alarm Systems
Other
• EIA-485 and EIA-232 Serial Interface Standards
• NEC Article 300 Wiring Methods
• NEC Article 760 Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction

IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15 7
UL 864 Compliance About This Manual
• C22.1-98 The Canadian Electrical Code, Part 1
1.2 UL 864 Compliance
1.2.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864 9th Edition.
The following products have not received UL 864 9th Edition certification and may only be used in
retrofit applications. Operation of the IQ-318/E with products not tested for UL 864 9th Edition has
not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These
applications will require the approval of the local Authority Having Jurisdiction (AHJ).
• For a complete list of all peripherals that can be used with this fire alarm control panel (FACP),
and which of those peripherals have not received UL 864, 9th Edition certification and may
only be used in retrofit applications, see Section 2.3, “Compatible Equipment”, on page 15.
1.3 Related Documents
Table 1.1 below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-ANS) provides the current
document revision. A copy of this document is included in every shipment.
Compatible Conventional Devices (Non-addressable) Document Number
(Part no. if applicable)
Device Compatibility Document 50054
Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number
(Part no. if applicable)
IQ-318/E Installation, Operations, and Programming Manuals
IQ-318C Canadian Applications Addendum
52864, 52865, 52866
52864CDN
AutoPulse SLC Wiring Manual 52184 (432780)
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming Utility Document Number
(Part no. if applicable)
VeriFire® Tools CD help file AP-TCD
Power Supplies, Auxiliary Power Supplies & Battery Chargers Document Number
(Part no. if applicable)
ACPS-2406 Installation Manual 51304
ACPS-610 Instruction Manual 53018
APS-6R Instruction Manual 50702
APS2-6R Instruction Manual 53232
CHG-120 Battery Charger Manual 50641
FCPS-24S6/FCPS-24S8 Field Charger/Power Supply Manual 51977
AUTOPULSE-NCA-2 Network Control Annunciator Manual 52857
ANSUL-NCA Network Control Annunciator Manual 52185 (432781)
Table 1.1 Reference Documentation (1 of 2)

8IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15
About This Manual Cautions and Warnings
1.4 Cautions and Warnings
This manual contains cautions and warnings to alert the reader as follows:
1.4.1 Typographic Conventions
System Components Document Number
(Part no. if applicable)
Annunciator Control System Manual 15842
ACM-8R Annunciator Control Module Manual 15342
FDU-80G Remote Annunciator Manual 52707
LCD-80 Liquid Crystal Display Annunciator 15037
LCD2-80 Liquid Crystal Display Annunciator 53242
LDM Series Lamp Driver Annunciator Manual 15885
SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712
DPI-232 Direct Panel Interface Manual 51499
TM-4 Installation Document (Reverse Polarity Transmitter) 51490
UDACT Manual (Universal Digital Alarm Communicator/Transmitter) 50050
UDACT-2 Manual (Universal Digital Alarm Communicator/Transmitter) 54089
RA100Z Remote LED Annunciator Installation Document I56-0508
Table 1.1 Reference Documentation (2 of 2)
!
CAUTION:
Information about procedures that could cause programming errors, runtime errors, or equipment
damage.
!
WARNING:
Indicates information about procedures that could cause irreversible damage to the control panel,
irreversible loss of programming data or personal injury.
NOTE: The term IQ-318 is used in this manual to refer to the IQ-318, and the IQ-318E and the
IQ-318C unless otherwise noted.

IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15 9
Section 2: System Overview
2.1 System Description
The IQ-318/E control panel is a modular, intelligent fire alarm control panel (FACP) with an
extensive list of powerful features. The control panel uses the CPS-24/E integral power supply with
battery charger. This is mounted in its cabinet to create a complete fire alarm control system. The
panel supports FlashScan® and CLIP mode; the board provides an integral signaling line circuit
(SLC) that can support up to 318 addressable points (159 detectors and 159 monitor/control
modules).
Modular devices mount in the cabinet or in auxiliary backboxes to provide additional circuits. This
system is available in either a 120 VAC or 240 VAC configuration. Cabinetry can be ordered in
black or in red. The IQ-318/E chassis is removable, allowing work to be done outside the cabinet.
2.1.1 Standard Features
• Uses the VIEW® early warning fire detection and the FlashScan® or Classic Loop Interface
Protocol (CLIP) families of detectors and modules
• Integral power supply with battery charger
• Four standard Notification Appliance Circuits (NAC), Class A or B
• Alarm, Trouble, Supervisory and Security relays
• Support for 32 annunciator addresses, with 10 special annunciator groups
• Supports Style 4, Style 6, Style 7 SLC loops
• Releasing service using on-board NACs or FCM-1 modules
• Logic Equations
• Display scroll selection
• Alarm verification supervisory indication (NYC)
• Supervisory duct detectors
• Supports Intelligent Sensing algorithms
• Battery charger supports 18 to 200 amp hour sealed lead-acid batteries
• EIA-485 connections for wiring ACS annunciators (including LDM custom graphic
annunciators), TM-4 transmitter
• EIA-232 connections for printer, CRT or printer/CRT
• VeriFire Tools® off-line programming utility
• Autoprogram feature for faster device programming
• The control panel provides 6 amps of usable output power in an alarm condition; it provides
3 amps of usable output power in normal or continuous operating conditions
• Diagnostic LEDs and switches
• Ground fault detection (0 ohm impedance)
• Battery and battery-charger supervision, voltage-monitoring, and current-monitoring
• Disconnect of deeply-discharged battery (low battery disconnect)
• Programmable for strobe synchronization
• QWERTY silicone-rubber keypad with a 2x40 LCD display and eight indicator LEDs
• Mass Notification System compatible

10 IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15
System Overview System Components
2.1.2 Options
Refer to Section 2.2 “System Components” for descriptions of the various optional modules.
• Optional devices include:
UDACT/UDACT-2 Universal Digital
Alarm Communicator/Transmitter, and
ACM-8R remote relay module to increase
point capacity.
• Optional annunciators connected through
the EIA-485 interface allow remote
system monitoring.
2.1.3 System Limitations
System expansion must take into consideration the following:
1. The physical limitations of the cabinet configuration.
2. The electrical limitations of the system power supply.
3. The capacity of the secondary power source (standby batteries). (Note that batteries larger than
26 AH will require a separate battery backbox.)
2.2 System Components
2.2.1 Standard Equipment
The standard, factory-assembled IQ-318/E system includes the following components:
• The control panel with integral power supply, and cabinet. IQ318 (120V operation) or IQ318E
(220-240V operation), and CPS-24/E. IQ318/E is the “control panel” itself and the heart of the
system; it ships with a grounding cable, battery interconnect cables, and document kit. CPS-
24/E mounts directly on the control panel. The system ships pre-installed in its cabinet.
NOTE: The CPS-24/E is an integral part of the IQ318 and is not available separately.
• A primary display KDM-R2 keypad/display.
Batteries are ordered separately; refer to Appendix 6.3 “Calculating the Battery Requirements” for
system current-draw calculations.
Up to two option boards can be installed within the FACP’s cabinet; additional optional peripherals
can be mounted in auxiliary backboxes. Refer to Section 2.3, “Compatible Equipment” for
equipment listed for use with this FACP.
2.2.2 Control Panel Circuit Board
The control panel electronics are contained in IQ318 and its built-in power supply. The printed
circuit board incorporates a signaling line circuit (SLC) and the central processing unit; the power
supply has an integral battery charger. A keypad/display unit is installed over the power supply as
shown Figure 2.1. Wiring is shown in Figure 2.2, “IQ318 and Power-Supply: Wiring Connections”
and Figure 2.3, “IQ318 and Power-Supply: Jumpers, LEDs and Switches”.

IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15 11
System Components System Overview
Figure 2.1 IQ-318/E System, Shown with
Door Open
2.2.3 Main Power Supply CPS-24/E
The main power supply is an integral part of the IQ-318/E and mounts directly over the control
panel’s circuit board. It provides a total of 3.9 A (7.4 A in alarm) and contains an integral battery
charger. This can be used for many functions including:
• Powering the IQ-318/E
• Powering a variety of UL-listed 24 VDC
notification appliances from four built-in
NAC outputs
• Providing up to 1.25 A of resettable power
for four-wire smoke detectors
• Providing up to 1.25 A of non-resettable
power for external devices such as the
TM-4 Transmitter Module
• Providing auxiliary 24 VDC power @ 0.5
A and 5 VDC power @ 0.15 A
• Fuse: 8 amps, 250 V, 5 x 20 mm, Fast
Acting, ceramic, p/n 12117
See Figure 2.2, “IQ318 and Power-Supply: Wiring Connections” and Figure 2.3, “IQ318 and
Power-Supply: Jumpers, LEDs and Switches” for details.
320door_open.wmf

12 IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15
System Overview System Components
2.2.4 Circuit Board Components
The following three figures illustrate the location of the various connections, switches, jumpers and
LEDs on the IQ318 and its power supply. Figure 2.2 shows wiring connections; Figure 2.3 shows
jumpers, LEDs and switches. See Section 3 “Installation” for larger images and more details.
(Larger images are referenced on these drawings.)
TB13 - SLC Loop #1
(supervised, power-
limited)
(Figure 3.18)
TB11 - EIA-485 ACS Mode Connection (supervised)
TB11 - EIA-485 Terminal Mode Connection (supervised)
(Figure 3.14 on page 28)
TB10 - DC Power
(24 VDC power-limited)
Resettable
Non-resettable
(See Figure 3.6 on page 22) TB12 - EIA-232 Printer Connection (Figure 3.15 on page 33)
TB12 - EIA-232 PC/Terminal Connection (CRT)
(Figure 3.16 on page 31)
J1 - Network/Service Connection (NUP)
(power-limited, supervised)
J2 - USB A VeriFire Tools Connection
J3 - USB B VeriFire Tools Connection
TB8 - NAC#2
All NAC Circuits: power-
limited, supervised
(Figure 3.9 on page 24)
TB9 - NAC#1
TB7 - NAC#3
TB6 - NAC#4
Output Relays - power-limited only if connected to a power-limited
source. (See Figure 3.11 on page 25 for details.)
TB5 -
Supervisory Relay
Security Relay
TB4 -
Alarm Relay
Trouble Relay
J5 - Security Tamper Switch
J6 - Auxiliary Trouble Input
J7 - KDM-R2
Connection
CPU320-KAPS-
Figure 2.2 IQ318 and Power-Supply: Wiring Connections
TB3 - Battery Connection
(over-current protected, non-power-limited)
TB1 - AC Power Connection (non-
power-limited)
Hot
Neutral
Earth
Ground
(+) (-)
TB2 - Secondary Power Auxiliary Outputs
(power-limited)

IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15 13
System Components System Overview
NAC
LEDs
Disable - Enable Switches
for Backup Alarm
(Figure 3.12 on page 26)
LED10 – SLC Loop
Ground Fault LED
LED5 - Supervisory LED
LED7 - Pre-Alarm LED
LED6 - Security LED
LED3 - Point Disabled LED
LED2 - Signals Silenced LED
LED4 - System Trouble LED
LED8 - Fire Alarm LED
LED1 - Power-on LED (AC or battery)
System Switches - ‘No
Keyboard Operation’
SW5 - Acknowledge
SW6 - Silence
SW7 - Reset
CPU320-KAPS-291809.wmf, CPU2-640-
JP1 - SLC Ground
Fault Jumper
SW1 - Ground Fault Detection Enable/Disable
LED3 - Earth Fault LED (general board ground fault)
Figure 2.3 IQ318 and Power-Supply: Jumpers, LEDs and Switches
LED5 - +24V Aux LED
LED6 - +5V Aux LED
LED6 - +5V Aux LEDLED1 - Logic Power LED
LED2 - Trouble LED
LED4 - AC Power LED
F4- AC Fuse

14 IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15
System Overview System Components
2.2.5 System Cabinet
The control panel is factory installed in its backbox. The lockable door is hinged on the left and
opens a full 180 degrees. Mounting methods include surface-mounting or semi-flush mounting on a
wall between 16 inch (40.64 cm) on-center studs. A trim ring option is available for semi-flush
mounting.
External measurements:
• Backbox: 18.12 in. (46.025 cm) width;
18.12 in. (46.025 cm) height;
5.81 in. (14.76 cm) depth.
• Door: 18.187 in. (46.195 cm) width;
18.40 in. (46.736 cm) height;
0.75 in. (1.905 cm) depth.
When using trim ring TR-320, mount backbox with at least 1 inch (2.54 cm) between wall surface
and front of backbox, to allow door to open fully past the trim ring. The TR-320 molding width is
0.905 in. (2.299 cm).
Additional Options
The IQ-318/E control panel provides space for one or two additional option boards to be installed,
as shown in Figure 3.3 on page 20. The IQ-318C fulfills ULC annunciation requirements; see IQ-
318C Canadian Applications Addendum for details. A variety of compatible annunciators are
available with their own backboxes; see Section 2.3, “Compatible Equipment”.

IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15 15
Compatible Equipment System Overview
2.3 Compatible Equipment
These are the most common devices at time of publishing; the most complete list of compatible
intelligent SLC loop devices is provided in the SLC Wiring Manual; for conventional non-
addressable equipment see the Device Compatibility Document. These devices are UL and ULC
listed unless marked otherwise (in parentheses next to the product). For products documented
separately, see Section 1.3 “Related Documents”.
AutoPulse and Notifier Compatible Equipment
NOTE: Products marked with a checkmark “” have not received UL 864 9th Edition
certification and may only be used in retrofit applications (see Section 1.2, “UL 864 Compliance”,
on page 7)
Electronic Equipment
ACM-24AT Annunciator Control Module
ACM-48A Annunciator Control Module
ACM-8R Annunciator Control Module
ACPS-610 Addressable Charger/Power Supply
APS2-6R Auxiliary Power Supply
AEM-24AT Annunciator Expander Module
AEM-48A Annunciator Expander Module
AKS-1 Annunciator Key Switch
BAT-12120 Battery 12-volt, 12 amp-hour
BAT-12180 Battery 12-volt, 18 amp-hour
BAT-12250 Battery 12-volt, 25 amp-hour
BAT-12260 Battery 12-volt, 26 amp-hour
BAT-12550 Battery 12-volt, 55 amp-hour
BAT-12600 Battery 12-volt, 60 amp-hour
BX-501 Intelligent Detectors/Sensors Base
B501 Intelligent base
B501BH Sounder base
B501BH-2 Sounder base, steady tone
B501BHT-2 Sounder base, temporal tone
B710LP/B210LP Intelligent detector base
CCM-1 Communication Converter Module
CMX-1 Addressable Control Module
CMX-2 Addressable Control Module
CPU-320/E Control Panel Circuit Board
CPX-551 Ionization Smoke Detector
CPX-751 Intelligent Ionization Smoke Detector
CRT-2 Video Display Monitor with Keyboard
DPI-232 Direct Panel Interface
FCM-1 NAC Module
FCM-1-REL Control Module
FCPS-24S6/S8 Field Charger Power Supply
FDX-551 Intelligent Thermal Sensor
FDU-80, FDU-80G Remote Fire Annunciator
FMM-1 Monitor Module
FMM-101 Mini Monitor Module
SB-200S Single-ended beam smoke detector with sensitivity
testing
FSB-200 Single-ended beam smoke detector.
FSD-751P Photoelectric Duct Detector
FSD-751RP Photoelectric Duct Detector with alarm relay
FSD-751PL Low-flow Duct Detector
FSP-851R/DNR Remote Test Capable Photoelectric Smoke
Detector
FSD-751RPL Low-flow Duct Detector with alarm relay
DHX-501, DHX-502 Duct Detectors
FSI-751, FSI-851 Ion Detector
Acclimate ™ FAPT-751, FAPT-851 Combination
Photoelectric/Heat Detector
FSH-751 HARSH™ Smoke Detector
HPX-751 Intelligent HARSH™ Detector
FSL-751 VIEW® Low Profile Laser Detector
FSM-101 Pull Station Monitor Module
FRM-1 Relay Module
FSP-751, FSP-851 Photo Detector
FDRM-1 Dual Monitor/Dual Relay
FSP-751T, FSP-851T Photo/Thermal Detector
DNR/W Intelligent Non-Relay Photoelectric Duct Detector
FST-751, FST-851 Thermal Detector
FST-751R, FST-851R Thermal Detector (rate of rise)
FST-851H High Temperature Detector
FZM-1 Monitor and Zone Interface Module
FDM-1 Dual Monitor Module
ISO-X Loop Fault Isolator Module
FSA-5000FSA-8000KDM-R2 Keypad/Display Unit
LCD-80 Liquid Crystal Display Annunciator
LCD2-80 Liquid Crystal Display Annunciator
LDM-32 Lamp Driver Module
LDM-E32 Lamp Driver Module
LDM-R32 Lamp Driver Module
LPX-751 VIEW® Low Profile Laser Detector (CLIP)
MMX-1 Addressable Monitor Module
MMX-2 Addressable Monitor Module
MMX-101 Addressable Mini Monitor Module
AP-NBG-12LR/NBG-12LRA Agent Release-Abort Station
NBG-12 Series Manual Pull Station
NBG-12LX Addressable Manual Pull Station
AP-NCA-2 Network Control Annunciator
N-ELR Assortment ELR Pack with Mounting Plate
PRN-6 80-Column Printer
PRN-7 80-Column Printer
R-120 120 Ohm End-of-Line Resistor
R-2.2K 2.2K End-of-Line Resistor
R-27K 27K End-of-Line Resistor
R-470 470 End-of-Line Resistor
R-47K 47K End-of-Line Resistor
A77-716B End-of-Line Resistor Assembly
RPT-485F EIA-485 Repeater (Fiber)
RPT-485W EIA-485 Repeater (Wire)
RPT-485WF EIA-485 Repeater (Wire/Fiber)
SCS-8, SCE-8 Smoke Control Station
SCS-8L, SCE-8L Smoke Control Lamp Driver
SDX-551 Intelligent Photoelectric Detector
SDX-751 Intelligent Photoelectric Detector
SLC-IM Signaling Line Control Integration Module
STS-200 Security Tamper Switch
TM-4 Transmitter Module
UDACT Universal Digital Alarm Communicator Transmitter
UDACT-2 Universal Digital Alarm Communicator/Transmitter
XP6-C Supervised Control Module
XP6-R Six Relay Control Module
XP6-MA Six Zone Interface Module
XP10-M Ten Input Monitor Module
!
WARNING: UL 9th Edition Compliance
This product has been certified to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of the IQ-318/E/C with products
not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or
the latest edition of UL 864. These applications will require the approval of the local Authority Having
Jurisdiction (AHJ).
Peripheral devices in the second list were listed under UL 8th Edition and may only be used in retrofit
applications (see Section 1.2, “UL 864 Compliance”, on page 7).

16 IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15
System Overview Compatible Equipment
Backboxes, Chassis, Dress Panels, etc.
ABF-1B Annunciator Flush Box
ABF-1DB Annunciator Flush Box with Door
ABF-2B Annunciator Flush Box
ABF-2DB Annunciator Flush Box with Door
ABF-4B Annunciator Flush Box
ABM-16AT Annunciator Blank Module
ABM-32A Annunciator Module Blank
ABS-1TB Annunciator Surface Box
ABS-1B Annunciator Surface Box
ABS-2B Annunciator Surface Box
ABS-4D Annunciator Surface Box
ABS-8RB Annunciator Backbox for ACM-8R
NFS-LBBR Red Battery Box
VP-2B 2” Filler Dress Plate
System Sensor Equipment
A2143-00 End of Line Resistor Assembly
EOLR-1 End-of-Line Resistor Assembly
FSB-200, FSB-200S Beam Detectors
Retrofit Equipment: Compatible Notifier Equipment Listed Under Previous Editions
of UL 864
NOTE: The products in this list have not received UL 864 9th
Edition certification and may only be used in retrofit applications.
ACM-16AT Annunciator Control Module
ACM-32A Annunciator Control Module
ACPS-2406 Auxiliary Charger/Power Supply
AEM-16AT Annunciator Expander Module
AEM-32A Annunciator Expander Module
APS-6R Auxiliary Power Supply
BGX-101L Addressable Manual Pull Station
CHG-120 Battery Charger
FCPS-24 Field Charger Power Supply
IPX-751 Advanced Multi-Sensor Intelligent Detector
ANSUL-NCA Network Control Annunciator
P-40 Keltron Printer
P40-KITB Dress plate for Keltron Printer
PRN-4, PRN-5, PRN-6 80-Column Printers
RA400 Remote Annunciator
RA400Z Remote Annunciator with diode
XP5-C Transponder Control Module
XP5-M Transponder Monitor Module
XPC-8 Transponder Control Module
XPDP Transponder Dress Panel
XPM-8 Transponder Monitor Module
XPM-8L Transponder Monitor Module
XPP-1 Transponder Processor
XPR-8 Transponder Relay Module

IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15 17
Section 3: Installation
3.1 Preparing for Installation
Choose a location for the fire alarm system that is clean, dry, and vibration-free with moderate
temperature. The area should be readily accessible with sufficient room to easily install and
maintain it. There should be sufficient space for cabinet door(s) to open completely.
Carefully unpack the system and inspect for shipping damage. Count the number of conductors
needed for all devices and find the appropriate knockouts. (Refer to Section 3.9 “UL Power-limited
Wiring Requirements” for selection guidelines.)
Before installing the fire alarm system, read the following:
• Review the installation precautions at the front of this manual, including temperature and
humidity limits for the system (Page 3).
• All wiring must comply with the National and Local codes for fire alarm systems.
• Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a
separate battery cabinet; this space is for internal battery installation.
• Review installation instructions in Section 3.2 “Installation Checklist”.
3.1.1 Standards and Codes
In addition, installers should be familiar with the following standards and codes:
• NEC Article 300 Wiring Methods.
• NEC Article 760 Fire Protective Signaling Systems.
• Applicable Local and State Building Codes.
• Requirements of the Local Authority Having Jurisdiction.
• C22.1-98 The Canadian Electrical Code, Part 1.
• CAN/ULC-S5524-01 Standard for the Installation of Fire Alarm Systems.
!
CAUTION:
Make sure to install system components in the sequence listed below. Failure to do so can damage
the control panel and other system components.
!
WARNING:
This system contains static-sensitive components. Always ground yourself with a proper wrist strap
before handling any circuits. Use static-suppressive packaging to protect electronic assemblies
removed from the unit.

18 IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15
Installation Installation Checklist
3.2 Installation Checklist
Table 3.1 provides an installation checklist for installing, wiring, and testing the IQ-318/E system.
It has references to installation information included in manuals listed in Section 1.3 “Related
Documents”.
Seq Task Refer to
1. Mount the cabinet backbox to the wall. Section 3.3 “Mounting a Cabinet”
2. If adding option boards such as such as TM-4:
• Remove keypad.
• Install option boards
• Replace keypad
Section 3.4 “Installing Option Boards”,
Section 1. “Remove and re-install KDM-R2 as shown in
Figure 3.2. It may be convenient to do some basic field-
wiring before reinstalling KDM-R2.”, and Section 3.4
“Installing Option Boards”
Also see option board documentation for board-specific
details.
3. Optional: Install auxiliary power supply and/or external
battery charger; set backup-alarm switches.
Auxiliary power manuals, Section 3.8 “Backup-Alarm
Switches”
4. Connect AC wiring, place batteries into backbox without
connecting them, and run cable to optional power supplies,
DC power outputs, NACs, and relays.
CAUTION: Do not apply AC or DC power at this time.
Section 3.5 “Connecting the Power Cables”
5. Optional: Install output devices such as a printer, or CRT
terminal.
Section 3.11 “Installing Remote Printers and/or CRT”
6. Wire annunciators. Relevant product manuals
7. Wire the Signaling Line Circuits. Section 3.12 “Wiring a Signaling Line Circuit (SLC)”
8. Terminate wire shielding as instructed. SLC Wiring Manual
9. Apply AC power to the control panel by placing the external circuit breaker to the ON position.
Do NOT connect batteries.
10. Check AC power. Table 3.2 in Section 3.5 “Connecting the Power Cables”
11. Connect the batteries using interconnect cable, P/N 75560 and 75561.
12. Program the control panel. IQ-318/E Programming Manual and VeriFire Tools Online
Help.
13. Field test the system. Section 5 “Testing the System”
Table 3.1 Installation Checklist
Location for 1 or 2
option boards
Figure 3.1 IQ-318/E in Cabinet
Top two
mounting holes
Two lower
mounting holes
are behind
batteries.

IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15 19
Mounting a Cabinet Installation
3.3 Mounting a Cabinet
This section provides instructions for mounting the IQ-318/E backbox to a wall. The IQ-318/E is
assembled with a removable chassis that can be removed to provide easier access to the backbox’s
mounting holes, or to allow the electronics to be worked on outside the cabinet.
Follow these guidelines when mounting the backbox:
• Locate the backbox so that the top edge is 66 inches (1.6764 m) above the surface of the
finished floor.
• Access to the cabinet shall be provided in accordance with NFPA 90, article 110.33.
• Allow sufficient clearance around cabinet for door to swing freely. (See Section 2.2.5 “System
Cabinet”.)
• Use the four holes in the back surface of the backbox to provide secure mounting. (See
Figure 3.1 on page 39.)
• Mount the backbox on a surface that is in a clean, dry, vibration-free area.
Follow the instructions below:
1. Mark and pre-drill holes for the top two keyhole mounting bolts (0.25 inch, 0.635 cm). Use
mounting hardware appropriate for the mounting surfaces; see UL 2017 Pull-Test
Requirements.
2. Select and punch open the appropriate knock-outs. (For selection guidelines, see Section 3.9
“UL Power-limited Wiring Requirements”.)
3. Using the keyholes, mount the backbox over the two screws.
4. Mark the location for the two lower holes, remove the backbox and drill the mounting holes.
5. Mount the backbox over the top two screws, then install the remaining fasteners. Tighten all
fasteners securely.
6. Feed wires through appropriate knockouts.
3.4 Installing Option Boards
The IQ-318/E ships fully assembled with in its cabinet. One or two option boards can be mounted
inside the IQ-318 cabinet, under the keypad, as shown in Figure 3.3. Option boards that can be
installed internally include the TM-4 and UDACT or UDACT-2. See Section 2.3, “Compatible
Equipment” for a complete list. When installing option boards, temporarily remove the KDM-R2
keypad/display unit to provide full access to hardware connections. It may be convenient to do
some basic field-wiring before reinstalling KDM-R2.
!
CAUTION:
Unless you are familiar with the placement of components within this backbox, only use the knockout
locations provided for conduit entry.
NOTE: UDACT or UDACT-2 only:
If using UDACT or UDACT-2 inside the cabinet, do not install a second option board.
See the UDACT Manual or UDACT-2 Manual for instructions on using the mounting bracket.

20 IQ-318/E/C Installation Manual — P/N 52864:J3 9/29/15
Installation Installing Option Boards
1. Remove and re-install
KDM-R2 as shown in
Figure 3.2. It may be
convenient to do some
basic field-wiring before
reinstalling KDM-R2.
2. Lay the first option board
over the four stand-offs
already installed on the
CPU, so that the holes and
stand-offs align.
3. If attaching a second
option board, use its standoffs to
secure the first option board, then lay
the second option board over the
standoffs. Two sizes of standoffs are
shipped with the option boards; select
standoffs that allow sufficient
clearance for electronics on the lower
option board.
4. Secure the top option board with four
#4-40 screws (supplied).
5. Re-attach KDM-R2.
Installing a Transmitter Module TM-4
TM-4 is power-limited. Connections are on TB10 nonresettable output and TB11 EIA-485 ACS
Mode. Refer to the Transmitter Module TM-4 installation document for installation details.
Figure 3.2 Removing and Reinstalling KDM-R2
320_assembly_tech_pubs_5-2.wmf
Figure 3.3 Installing Option Boards
320_assembly_tech_pubs_3-2.wmf
!
CAUTION:
It is critical that all mounting holes of the IQ-318/E are secured with a screw or standoff to insure
continuity of Earth Ground.
NOTE: It may be convenient to field-wire the SLC loop before installing any option boards, and
to make wiring connections on the first option board before installing a second option board in
front of it.
This manual suits for next models
2
Table of contents
Other Notifier Control System manuals
Popular Control System manuals by other brands

Distech Controls
Distech Controls Allure ECW-Sensor Series installation guide

LINK ELECTRIC & SAFETY CONTROL COMPANY
LINK ELECTRIC & SAFETY CONTROL COMPANY OmniLink II operating manual

Airzone
Airzone ZS6 user manual

Faulhaber
Faulhaber 3564K024B CS instruction manual

Small Box
Small Box Chameleon 2.0 installation guide

Burkert
Burkert NAMUR 6517 operating instructions