- 4-
If RN-111M was initially deenergized or the power load was OFF due to the wrong voltage para-
meters – then after correct voltage appear on the input terminals and after the time delay Ton con-
tacts 1,3(4) will open and contacts 3(4),6will close.
If input voltage get lower than minimal voltage threshold for more than 12 seconds RN-111M be-
comes to Alarm mode – contacts 1,3(4) close and contacts 3(4), 6open and thus the power load
should be turned OFF.
If input voltage gets 60V lower than the minimal voltage tripping threshold – RN-111M turns OFF
the power load within 0,1 sec (accelerated tripping time). After the recovery of the voltage parameters
to the value of hysteresis (4-5V) – RN-111M turns ON the power load with the user adjusted time
delay Ton.
If input voltage gets higher than the maximal tripping voltage threshold for more than 1 s or
accelerated tripping time of 0,1 sec is applied if the voltage is 30V higher than the maximal tripping
threshold – then the RN-111M comes to Alarm mode – contacts 3(4), 6open and contacts 1,3(6)
close. When voltage level decrease lower than the maximal tripping voltage threshold to the hyste-
resis value (4-5V) – RN-111M turns ON the power load with the user adjusted time delay Ton.
3.2. Minimal voltage protection relay
This mode is active when toggle switch Umin is set to the Left position and Umax is set to the right
position. RN-111M will turn OFF the power load if voltage level will get lower than the Minimal voltage
threshold preset buy the user (Figure 1; item - 4).
Power load (contactor coil) should be connected to the output terminals 3(4), 6.
If RN-111M was initially deenergized or the power load was OFF due to the wrong voltage para-
meters – then after correct voltage appear on the input terminals and after the time delay Ton con-
tacts 1,3(4) will open and contacts 3(4),6will close.
If input voltage get lower than minimal voltage threshold for more than 12 seconds RN-111M be-
comes to Alarm mode – contacts 1,3(4) close and contacts 3(4), 6open and thus the power load
should be turned OFF.
If input voltage gets 60V lower than the minimal voltage tripping threshold – RN-111M turns OFF
the power load within 0,1 sec (accelerated tripping time). After the recovery of the voltage parameters
to the value of hysteresis (4-5V) – RN-111M turns ON the power load with the user adjusted time
delay Ton.
3.3. Maximal voltage protection relay
This mode is active when toggle switch Umax is set to the Left position and Umin is set to the right
position. RN-111M will turn OFF the power load if voltage level will get higher than the Maximal vol-
tage threshold preset buy the user (Figure 1; item - 3).
Power load (contactor coil) should be connected to the output terminals 1, 3(4).
When normal voltage applied to the input terminals of RN-111M – the state of the output relay
doesn’t change so the RN-111M stay in the “cold” state: contacts 1,3(4) are closed and contacts
3(4),6are opened.
If input voltage gets higher than the maximal tripping voltage threshold for more than 1 s or
accelerated tripping time of 0,1 s is applied if the voltage is 30V higher than the maximal tripping
threshold – then the RN-111M comes to Alarm mode – contacts 1, 3(4) open and contacts 3(4),6
close. When voltage level decrease lower than the maximal tripping voltage threshold to the
hysteresis value (4-5V) – RN-111M turns ON the power load with the user adjusted time delay Ton.
3.4. Turn ON time delay relay
This mode is active when both toggle switches (Umin, Umax) are set to the Right position. In this
mode voltage parameters are not controlled and RN-111M will turn ON the power load with the user
preset time delay (Ton) if the input voltage parameters are within the operation voltage range.
Power load (contactor coil) should be connected to the output terminals 3(4), 6.
If the input voltage is more than 160V RN-111M will turn ON the power load after the delay time
will finish. If the voltage will get lower than 120V RN-111M will go to Alarm mode – contacts 1,3(4)
close and contacts 3(4), 6open and thus the power load should be turned OFF.
ATTENTION!!! At first start-up or after the RN-111M was completely deenergized additional time