
-5 -
NOVATEK-ELECTRO
TR-100
If entered password is correct, then LED indicator “ALARM” (pic.1 pt.2) will ON and first parameter of Table 3
will appear on the digital display.
If entered password is NOT correct, then TR-100 will return to initial mode.
If is set as “000”, then password checking will NOT affected, LED indicator “ALARM” (pic.1 pt.2) will
ON and first parameter of Table 3 will appear on digital display.
Scrolling of parameters due buttons, to enter in menu item, press
button, to change value use
button, to confirm adjusted parameters and to return to menu press
button. Exit from menu without sa-
ving due
button. If any buttons are in inaction for more than 20 seconds, TR-100 will return to initial mode.
2.2.2 Restore factory defaults.
There are two ways to restore factory defaults:
Set parameter as 1 when device is in change parameters mode, and press
button whereupon
TR-100 will be restarted with factory defaults. In this case, password WON’T be restored.
Hold both buttons as pressed and Turn the supply power ON. Keep button holding for more than 2 s,
whereupon will appear on the digital display, release buttons. Cut off power. Factory defaults will be restored
as well as password (password disable).
2.2.3 Testing ТR-100.
2.2.3.1 Testing of LED indication.
Press
button, all LED indicators will ON for 2 sec. If at least one of them does NOT light, TR-100 is
considered faulty and requires under repair. During test of LED indication TR-100 continue normal operation.
2.2.3.2 Testing of output relays.
In TR-100 testing all relays together is provided and each relay separately, for this it is necessary:
In change parameters mode, set value of parameter according with Table 3 and press
button,
thus on the digital display will be showed (it means testing relay stays in normally open (OFF) conditional)
and all LED indicators will be OFF.
Condition of testing relay change due single press
button:
- Relay stays in normally open (OFF) condition;
- Relay stays in normally close (ON) condition.
Press
button to return in menu. If any buttons are in inaction for more than 20 seconds, TR-100 will return
to initial mode.
2.2.4 Usage ventilation.
TR-100 is able to control of switching on and cutting off of cooling fan, for this it is necessary to set value of
parameter as different from 0 (see Table 3):
Mode 1 –In this mode, temperature is detected due THREE sensors 1, 2 and 3. As soon as temperature of
one of sensors exceed of temperature of adjusted threshold of switching on of ventilation , ventilation relay
will ON with corresponding indication (flashing of LED indicator 4 pic.1). Cutting off of ventilation relay will occur, if
temperatures of all sensors drop below than - .
Mode 2 –The same as Mode 1, but temperature is detected due FOUR sensors 1, 2, 3 and 4.
Mode 3 –If channel 4 is ON ( = 1, see Table 3). In this mode temperature is detected due 4th sensor.
As soon as temperature of sensor exceeds temperature of adjusted threshold of switching on of ventilation ,
relay will ON with corresponding indication (flashing of LED indication 4 pic.1). Cutting off of ventilation relay will
occur, if temperature of sensor drops below than - .
NOTE: LED 4 (pic.1) is ON, when control of ventilation is ON and LED 4 is flashing, when temperature of one
of sensors exceeds temperature of adjusted threshold (see Table 3).
2.2.5 Viewing of maximal reached temperature.
In TR-100 storage of maximal reached temperature of channel is provided. To display of maximal temperature it
is necessary: