- 6 -
RNPP-311M
NOVATEK-ELECTRO
Umax –voltage is higher than the user adjusted value of Umax
The switches SEQ, IMB, Umin, Umin are intended for permission / prohibition of relay operation in
case of emergency.
If the switch is set to the Left position –then the corresponding function is turned ON;
If the switch is set to the Right position –this function is disabled.
RNPP-311M will operate by any one of SEQ, IMB, Umin, Umin emergency if this switch is set to the Left
position (ON).
4. START UP PROCEDURE AND OPERATION
4.1 RNPP-311M is supplied ready to use and doesn’t require any special start up procedures. Due to
the use of microprocessor based scheme all the settings and adjustments are set precisely accurately and
there is no need to check the accuracy of settings with a help of testing voltmeter.
After long time storage period it is recommended to check the functionality of RNPP-311M. There is no
need to perform any routine maintenance if the RNPP-311M is already in use for a long time and being used
in accordance to the operation conditions stated in the present documentation.
ATTENTION! All the terminals connections and operation should be strictly performed according to
safety regulations. It is recommended to adjust all the knobs and select necessary functions when the
RNPP-311M is in the “cold” state (not energized). When testing the device it is allowed to make adjustments
and change the settings on the energized RNPP-311M.
4.2 Start up procedure:
1. Using adjustment knobs set the required values of voltage tripping thresholds Unom±%; tripping time
delay Toff and autoreclosing time delay Ton;
2. Using 5-8 switches on the front panel (Figure 1) at the left or right position.
Left position of the switch - function is enabled;
Right position –function disabled.
3. With the use of the DIP switch 4 ( Figure 1) set the type of the power supply input.
4. Connect RNPP-311M in parallel to the power load - using input terminals 9, 10, 11 (see Figure 1)
and Neutral to terminal 12.
If necessary connect external 24V (AC/DC) power supply source to terminals 7(+) and 8(–);
5. Connect output terminals (1-2(4-5) and 5-6(2-3)) to the control circuit (operational contacts of the
contactor);
6. Give the power supply to input terminals (energize the RNPP-311M)
If on the first start up RNPP-311M doesn’t allow to turn ON the power load and indicates wrong phase
sequence alarm but the user is absolutely sure that the phase sequence is correct –then it is necessary to
exchange the wires connected to terminals 10 and 11.
If RNPP-311M is being used as a maximal voltage protection relay then the break in the magnetic
starter coil power circuit should be connected to terminals 1-2 (4-5) (the reverse logic of switching-on).
The switch Umax should be set to ON position (enabled) and the switches SEQ, IMB and Umin should
be set to the OFF position (disabled).
4.3 RNPP-311M usage examples
a) Minimal voltage relay
- Switch Umin is set to the left position (function is enabled)
- Switches Umax, IMB are set to the right position (function disabled)
If the voltage level is lower than the user adjusted minimal voltage threshold (Unom±%)–then
RNPP-311M will turn OFF the power load with the user preset time delay Toff and red ALARM LED indicator
will turn ON. Corresponding LINE green LED indicator(s) will turn OFF indicating on which line the problem
occurred. If the voltage on any of the lines is lower than 100V –then RNPP-311M will turn OFF the power load
within 0,2 sec.
b) Voltage level monitoring and phase presence control relay
- Switches Umin and Umax are set to the left position
If voltage level is higher than the user adjusted maximal voltage threshold (Unom±%) –then
RNPP-311M will turn OFF the power load with the user preset time delay Toff; in case the minimal voltage
problem detected then the power load will be turned OFF with the fixed time delay of 12 sec (in order to
escape from fault tripping due to startup voltage drops). Red ALARM LED indicator will turn ON.
In case the phase loss detected–then RNPP-311M will turn OFF the power load within 0.2 sec.