manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Novus
  6. •
  7. Industrial Equipment
  8. •
  9. Novus TxIsoLoop-1 User manual

Novus TxIsoLoop-1 User manual

This manual suits for next models

1

Popular Industrial Equipment manuals by other brands

ABB +Q957 user manual

ABB

ABB +Q957 user manual

G.B.C BASIC EDGE 50 instruction manual

G.B.C

G.B.C BASIC EDGE 50 instruction manual

Tronair Batpak 11-6602-1000 Operation & service manual

Tronair

Tronair Batpak 11-6602-1000 Operation & service manual

Pilz PNOZ mi2p Operation manual

Pilz

Pilz PNOZ mi2p Operation manual

Clemco Zero BNP 6012 manual

Clemco

Clemco Zero BNP 6012 manual

Erskine Attachments V-Plow Operator's manual

Erskine Attachments

Erskine Attachments V-Plow Operator's manual

ABB HT610965 Operation manual

ABB

ABB HT610965 Operation manual

Morra MH 540 user manual

Morra

Morra MH 540 user manual

Eaton S090ST manual

Eaton

Eaton S090ST manual

GRIGGIO G 240 P4 instructions

GRIGGIO

GRIGGIO G 240 P4 instructions

Nexen AIR CHAMP HT45 user manual

Nexen

Nexen AIR CHAMP HT45 user manual

WTE V5 installation manual

WTE

WTE V5 installation manual

ABB HT845232 Operation manual

ABB

ABB HT845232 Operation manual

SMC Networks CJP Series Operation manual

SMC Networks

SMC Networks CJP Series Operation manual

JohnDow Industries JDI-AFT58 Operator's manual

JohnDow Industries

JohnDow Industries JDI-AFT58 Operator's manual

IMB MB9016A instruction manual

IMB

IMB MB9016A instruction manual

Clarke CUMB1 Assembly & operating instructions

Clarke

Clarke CUMB1 Assembly & operating instructions

amiad Arkal Spin Klin 2 user guide

amiad

amiad Arkal Spin Klin 2 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

NOVUS AUTOMATION 1/2
TxIsoLoop-1 / TxIsoLoop-2
LOOP-POWERED ISOLATORS – USER GUIDE V1.0x
1. INTRODUCTION
TxIsoLoop-1 and TxIsoLoop-2 galvanic isolators are devices used
for electrical isolation of 0(4)-20 mA current signals. Its purpose is to
avoid measurement errors typically found in installations that have
problems with electrical potential difference and ground loops.
These isolators do NOT require an electrical power supply. The
energy obtained by passing the electric current through the insulator
input actively generates the output current.
2. FEATURES
•Galvanic isolation between input and output.
•Models with one or two input/output channels.
•The device does not require a power supply.
•High accuracy.
3. SPECIFICATIONS
•Input signal: 0(4) to 20 mA (Check minimum current for proper
operation)
•Voltage drop − Input/output without protection (Vdrop): < 3 Vdc
•Voltage drop − Input/output with protection (Vdrop): < 5 Vdc
•Output signal: 0(4) to 20 mA
•Max. load (RL): 1450 R
•Total accuracy: 0.2 % @ 0 to 60 °C / RL = 250 R
0,3 % @ -20 to 75 °C / RL = 250 R
•Minimum operating current: > 0.1 mA
•Maximum input current: < 40 mA
•Response time: 2 ms @ RL= 250 R
•Current limit: 31 mA
•Electrical isolation: 3000 Vac / 10 seconds
240 Vac continuous
•EMC: EN 61326-1 (without performance degradation)
•Work environment: Temperature: -20 to 75 °C
Relative humidity: 20 to 90 %
•Housing: ABS (60 %) + PC (40 %)
•Protection index: IP40
•Wire gauge for connections: 0.14 to 1.5 mm²
•Recommended torque: 0.8 Nm
•Polyamide terminal enclosure.
4. ELECTRICAL INSTALLATION
To ensure perfect operation of the TxIsoLoop isolator, the circuit
where the isolator input is connected must provide a minimum
electrical voltage (V1).
You can supply the electrical voltage in two ways:
1. The device that generates the current signal is of the active type
(source), where it provides the necessary electrical voltage
itself.
Figure 1 –TxIsoLoop connections with source type device
With type source devices (transmitters, controllers, etc.), this voltage
is provided by the device itself).
The minimum voltage value to be supplied by the generator can be
calculated using the formula below:
V1= Vin Where: Vin = Vdrop + ( Iout(max) x RL)
I
in
= I
out
2. With sink type devices (2-wire transmitters), the energy is
provided by an external power supply in series in the loop, as
shown in Figure 2.
Figure 2 –Connections on the TxIsoLoop with sink type devices
In this option, the inserted source must provide enough voltage to
meet the needs of the current generating device (generator,
transmitter, controller, etc.) and the isolator.
The minimum voltage value to be supplied by the power supply can
be calculated using the formula below:
V1= Vb+
Vin
Where: V1= Voltage from the source inserted
into the circuit
Vb= Minimum voltage of the generator
Vin = Vdrop + ( Iout(max) x RL)
I
in
= I
out
NOVUS AUTOMATION 2/2
4.1 ELECTRICAL CONNECTIONS
To configure TxIsoLoop-1, use the following wiring diagram:
Figure 3 –TxIsoLoop-1 Connections
To configure TxIsoLoop-2, use the following wiring diagram:
Figure 4 –TxIsoLoop-2 Connections
4.2 TXISOLOOP-2 – SIGNAL SPLITTER FUNCTION
If needed, TxIsoLoop-2 can be used as a 4-20 mA signal splitter, as shown
in the figures below:
ACTIVE CURRENT SIGNAL
Figure 5 –Active current signal
PASSIVE CURRENT SIGNAL
Figure 6 –Passive current signal
4.3 INSTALLATION RECOMMENDATIONS
•Input signal conductors must run through the plant separately
from the supply and output conductors. If possible, in grounded
conduits.
•The power supply for the electronic instruments must come from
a proper instrumentation network.
•In control applications, it is essential to consider what can
happen when any part of the system fails.
•It is recommended to use RC FILTERS (noise suppressors) at
contactor coils, solenoids, etc.
5. MECHANICAL INSTALLATION
The transmitter is intended for a 35 mm DIN rail mounting.
Figure 7 –Isolator dimensions
6. WARRANTY
Warranty conditions are available on our website
www.novusautomation.com/warranty.