
3
2.0 Gas Valve and Burner Setup
Failure to perform the Gas Valve and Burner Setup correctly may result in incorrect
operation, component failure, property damage, serious injury or death.
Operating Sequence
Prior to commencing the Gas Valve and Burner Setup, perform the following operating sequence check:
1. Turn the supply of gas to the boiler off.
2. Set the thermostat to the highest setting.
3. Ensure the combustion fan pre-purges for at least 30 seconds prior to activating the igniter.
4. Ensure the combustion fan post-purges for at least 60 seconds prior to reactivating the igniter.
5. Set the thermostat to the lowest setting and continue with the Gas Valve and Burner Setup procedure outlined
below.
Gas Line Pressure
The boiler gas valve is equipped with a line pressure test port; see Figure 1-1. Use the following procedure to
measure the gas line pressure to the boiler to ensure if falls within the range given in Table 2-1:
1. Turn the supply of gas to the boiler off.
2. A bleed screw is located on the inlet flange of the gas valve; open it approximately 1-1/2 turns. See Line
Pressure Test Port in Figure 1-1.
3. Slide the gas pressure manometer tubing over the bleed screw fitting located on the inlet flange of the gas valve;
connect the other end of the tubing to the gas pressure manometer. Ensure both ends of the tubing make a tight
connection.
4. Open the supply of gas to the boiler and check for gas leaks.
5. Observe the line pressure under static conditions and compare it to Table 2-1. The pressure will be greatest under
static conditions.
6. With all other gas appliances in the application running, operate the burner to the maximum firing rate (see Table
2-2) and compare the observed line pressure with Table 2-1. The pressure will be lowest during the maximum
flow of gas.
7. Adjust the gas line pressure to ensure the parameters in Table 2-1 are attained under all conditions (see NOTICE
below). If possible, adjust the line pressure to the "Nominal/Desired" value listed in Table 2-1, while the unit is
operating at the maximum modulation rate, see Table 2-2.
8. Continue observing the gas line pressure until the completion of the combustion analyses, in case adjustments
need to be made.
9. Upon completion of the line pressure testing, turn the gas supply off and close the bleed screw. Turn gas on and
check for leaks.
The line pressure is a function of the gas supply and is affected solely by field provided
parameters such as line size and regulator settings. Under no circumstances can the boiler gas
valve influence or be used to adjust the gas line pressure.
Failure to properly close the Line Pressure Test Port bleed screw will cause severe leakage
of gas, resulting in a fire or explosion causing property damage, serious injury or death.
Table 2-1 Line Pressure and Combustion Parameters
Line Pressure (inches w.c.)
Offset Pressure
(inches w.c. / [Pa])4
-0.04 to -0.03 / [-10 to -8]
Notes:
1Combustion calibration must only be performed with the burner operating at maximum modulation rate.
2Combustion values listed are for burner operation at maximum modulation rate; CO2 and CO values will be lower at
minimum modulation rate.
3When tested at minimum modulation rate, the CO2must be 0.5-1.0% lower than CO2at maximum modulation rate.
4The Offset Pressure for models FTG 2000-2400 converted to Propane, must be checked, and if necessary adjusted, in
accordance with the procedure detailed in Figure 2-2.