6002 addressable control and indicating equipment
User Manual
2
31-0019-r04_2018-08
© 2017, 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information were current at the date of publication and subject to change without notice.
STATUS
FIRE Indicates the Alarm Condition. The LED will flash with un-acknowledged alarms
and be on steady when acknowledged.
Alarm zone information will be displayed on the ZONE indicators. Alarm device
information will be displayed on the LCD.
FAULT Indicates the Fault Condition. The LED will flash with un-acknowledged faults and
be on steady when acknowledged.
Fault information will be displayed on the LCD, and depending on the source of
the fault, in the FAULTS area of the control and indicating equipment.
PRE-ALARM Indicates a device is reaching the alarm threshold level. The LED will flash with
un-acknowledged alarms and be on steady when acknowledged.
Pre-alarm information will be displayed on the LCD.
TEST Indicates the Test Condition. The LED illuminates during the Test Condition.
DISABLE Indicates at least one device is disabled.
SUPPLY Indicates power is connected to the control and indicating equipment.
FAULTS
SUPPLY Indicates the mains supply is unavailable. The LED will flash with un-
acknowledged mains supply faults and be on steady when acknowledged.
BATTERY Indicates the standby battery supply or battery charger is faulty. The LED will flash
with un-acknowledged battery faults and be on steady when acknowledged.
SYSTEM Indicates a fault in the central processing unit. The LED will illuminate when a
processing fault or memory fault is detected.
ALARM Indicates when either an alarm zone circuit fault or an addressable audio/visual
alarm device fault is detected. The LED will flash with un-acknowledged alarm
faults and be on steady when acknowledged.
EARTH Indicates an earth fault is detected in the alarm zone transmission path wiring.
The LED will flash with un-acknowledged earth faults and be on steady when
acknowledged.
ZONES
Indicates the Alarm, Fault, Disable and Test Conditions for a specific detection
zone.
NAVIGATION
KEYPAD
Navigation controls, used in conjunction with other functions and LCD.
Increases the selection or number. Used for menu scrolling.
Decreases the selection or number. Used for menu scrolling.
Moves the cursor on the LCD.
Moves the cursor on the LCD.
Confirms the current entry.
Reverses/aborts the current entry or display.