OEM OPM223 User manual

BA194e/00/07.09/
71106576
valid as of:
Software-version 2.50
Operating Instructions
OPM223/253
Transmitter for pH and ORP


OPM223/253
3
Table of contents
1 Safety instructions . . . . . . . . . . . . .4
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Installation, commissioning and operation . . 4
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . 4
1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 Notes on safety icons and symbols . . . . . . . 5
2 Identification . . . . . . . . . . . . . . . . . .6
2.1 Device designation . . . . . . . . . . . . . . . . . . . 6
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . 7
2.3 Certificates and approvals . . . . . . . . . . . . . . 7
3 Installation . . . . . . . . . . . . . . . . . . . .8
3.1 Quick installation guide . . . . . . . . . . . . . . . . 8
3.2 Incoming acceptance, transport, storage . . . 9
3.3 Installation conditions . . . . . . . . . . . . . . . . . 9
3.4 Installation instructions . . . . . . . . . . . . . . . 11
3.5 Post-installation check . . . . . . . . . . . . . . . . 14
4 Wiring . . . . . . . . . . . . . . . . . . . . . . .15
4.1 Electrical connection . . . . . . . . . . . . . . . . . 16
4.2 Alarm contact . . . . . . . . . . . . . . . . . . . . . . . 22
4.3 Post-connection check . . . . . . . . . . . . . . . . 22
5 Operation . . . . . . . . . . . . . . . . . . . .23
5.1 Quick operation guide . . . . . . . . . . . . . . . . 23
5.2 Display and operating elements . . . . . . . . 23
5.3 Local Operation . . . . . . . . . . . . . . . . . . . . . 27
5.4 System configuration . . . . . . . . . . . . . . . . . 30
5.5 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . 59
6 Commissioning . . . . . . . . . . . . . . .65
6.1 Things to note when commissioning
ISFET sensors . . . . . . . . . . . . . . . . . . . . . . 65
6.2 Function check . . . . . . . . . . . . . . . . . . . . . . 65
6.3 Switching on . . . . . . . . . . . . . . . . . . . . . . . 65
6.4 Quick start-up . . . . . . . . . . . . . . . . . . . . . . 67
7 Maintenance. . . . . . . . . . . . . . . . . .69
7.1 Maintenance transmitter . . . . . . . . . . . . . . 69
7.2 Maintenance of the entire measuring point 71
7.3 "Optoscope" service tool . . . . . . . . . . . . . . 73
8 Accessories. . . . . . . . . . . . . . . . . . 74
8.1 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 74
8.2 Connection accessories . . . . . . . . . . . . . . 74
8.3 Mounting accessories . . . . . . . . . . . . . . . . 75
8.4 Assemblies . . . . . . . . . . . . . . . . . . . . . . . . 76
8.5 Software and hardware add-ons . . . . . . . 77
8.6 Calibration solutions . . . . . . . . . . . . . . . . . 77
8.7 Optoscope . . . . . . . . . . . . . . . . . . . . . . . . 77
9 Trouble-shooting. . . . . . . . . . . . . . 78
9.1 Trouble-shooting instructions . . . . . . . . . . 78
9.2 System error messages . . . . . . . . . . . . . . 78
9.3 Process specific errors . . . . . . . . . . . . . . . 81
9.4 Instrument specific errors . . . . . . . . . . . . . 84
9.5 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . 86
9.6 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
9.7 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . 91
10 Technical data . . . . . . . . . . . . . . . . 92
10.1 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
10.2 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
10.3 Power supply . . . . . . . . . . . . . . . . . . . . . . 93
10.4 Environment . . . . . . . . . . . . . . . . . . . . . . . 93
10.5 Performance characteristics . . . . . . . . . . . 94
10.6 Mechanical construction . . . . . . . . . . . . . . 94
11 Appendix . . . . . . . . . . . . . . . . . . . . 96
Index. . . . . . . . . . . . . . . . . . . . . . . 101

Safety instructions OPM223/253
4
1 Safety instructions
1.1 Designated use
OPM223/253 is a transmitter for determining the pH value and/or ORP.
The transmitter is particularly suited for use in the following areas:
• Chemical industry
• Pharmaceutical industry
• Food industry
• Drinking water treatment
• Condensate treatment
• Municipal sewage treatment plants
• Water treatment
• Electroplating
Any other use than the one described here compromises the safety of persons and the entire
measuring system and is, therefore, not permitted.
The manufacturer is not liable for damage caused by improper or non-designated use.
1.2 Installation, commissioning and operation
Please note the following items:
• Installation, electrical connection, commissioning, operation and maintenance of the
measuring system must only be carried out by trained technical personnel.
The technical personnel must be authorised for the specified activities by the system
operator.
• Technical personnel must have read and understood these Operating Instructions and must
adhere to them.
• Before commissioning the entire measuring point, check all the connections for
correctness. Ensure that electrical cables and hose connections are not damaged.
• Do not operate damaged products and secure them against unintentional
commissioning. Mark the damaged product as being defective.
• Measuring point faults may only be rectified by authorised and specially trained
personnel.
• If faults can not be rectified, the products must be taken out of service and secured against
unintentional commissioning.
• Repairs not described in these Operating Instructions may only be carried out at the
manufacturer’s or by the service organisation.
1.3 Operational safety
The transmitter has been designed and tested according to the state of the art and left the
factory in perfect functioning order.
Relevant regulations and European standards have been met.
As the user, you are responsible for complying with the following safety conditions:
• Installation instructions
• Local prevailing standards and regulations.
Ex systems have an additional Ex documentation which is part of the Operating Instructions
(see also chapter "Scope of delivery").

OPM223/253 Safety instructions
5
EMC
This instrument has been tested for electromagnetic compatibility in industrial use according
to applicable European standards.
Protection against interference as specified above is valid only for an instrument
connected according to the instructions in these Operating Instructions.
1.4 Return
If the transmitter has to be repaired, please return it cleaned to the sales centre responsible.
Please use the original packaging, if possible.
1.5 Notes on safety icons and symbols
Safety icons
Electrical symbols
#
Warning!
This symbol alerts you to hazards. They can cause serious damage to the instrument or
to persons if ignored.
"
Caution!
This symbol alerts you to possible faults which could arise from incorrect operation. They
could cause damage to the instrument if ignored.
!Note!
This symbol indicates important items of information.
%Direct Current (DC)
A terminal at which DC is applied or through which DC flows.
&Alternating Current (AC)
A terminal at which (sine-form) AC is applied or through which AC flows.
)
Ground connecting
A terminal, which, from the user’s point of view, is already grounded using a grounding
system.
*Protective earth terminal
A terminal which must be grounded before other connections may be set up.
bAlarm relay
Input
Output
DC voltage source
Temperature sensor

Identification OPM223/253
6
2 Identification
2.1 Device designation
2.1.1 Product structure
2.1.2 Additional functions of the Plus Package
• Current output table to cover large areas with varying resolution
• Monitoring of sensor and process for safe operation
• Neutralisation controller to keep pH value constant by dosing acid and alkali
• Automatic cleaning function start
Sensor input; software
IS pH (glass/ISFET) / ORP; Plus package
PR pH (glass)/ORP; basic version
PS pH (glass)/ORP; Plus package
Power supply; approval
0 230 V AC
1 115 V AC
2 230 V AC; CSA Gen. Purp.
3 115 V AC; CSA Gen. Purp.
4 230 V AC; ATEX II 3G [EEx nAL] IIC
5 100 V AC
6 24 V AC/DC; ATEX II 3G [EEx nAL] IIC for OPM223, EEx nA[L] IIC T4 for OPM253
7 24 V AC; CSA Gen. Purp.
824VAC/DC
Output
0 1 x 20 mA, pH/ORP
1 2 x 20 mA, pH/ORP + selectable
Additional contacts; analogue input
05 not selected
10 2 x relay (limit/P(ID)/timer)
15 4 x relay (limit/P(ID)/Chemoclean)
16 4 x relay (limit/P(ID)/timer)
20 2 x relay (limit/P(ID)/timer); 20 mA
25 4 x relay (limit/P(ID)/Chemoclean); 20 mA
26 4 x relay (limit/P(ID)/timer); 20 mA
OPM253-
complete order code
OPM223-

OPM223/253 Identification
7
2.2 Scope of delivery
The delivery of the field instrument includes:
• 1 transmitter OPM253
• 1 plug-in screw terminal
• 1 cable gland Pg 7
• 1 cable gland Pg 16 reduced
• 2 cable glands Pg 13.5
• 1 operating instructions BA194e00
• versions with explosion protection for hazardous area zone II (ATEX II 3G):
Safety instructions for use in explosion-hazardous areas, XA194a300
The delivery of the panel mounted instrument includes:
• 1 transmitter OPM223
• 1 set of plug-in screw terminals
• 2 tensioning screws
• 1 BNC-plug (solder-free)
• 1 operating instructions BA194e00
• versions with explosion protection for hazardous area zone II (ATEX II 3G):
Safety instructions for use in explosion-hazardous areas, XA194a300
If you have any questions, please contact your supplier or your sales centre responsible .
2.3 Certificates and approvals
Declaration of conformity
The product meets the legal requirements of the harmonised European standards.
The manufacturer confirms compliance with the standards by affixing the 4symbol.
Explosion protection for Zone 2
OPM253-..6... ATEX II 3G EEx nA[L] IIC T4
OPM253-..4...
OPM223-..4...
OPM223-..6...
ATEX II 3G [EEx nAL] IIC

Installation OPM223/253
8
3 Installation
3.1 Quick installation guide
#Warning!
If the measuring point or parts of the measuring point are in explosion-hazardous areas you
have to follow the "Safety instructions for electrical apparatus certified for use in explosion-
hazardous areas". These instructions (XA194a300) are part of the scope of delivery.
Proceed as follows to completely install the measuring point:
• Install the transmitter (see "Installation instructions" section).
• If the sensor is not yet installed in the measuring point, install it (see Technical Information
of the sensor).
• Connect the sensor to the transmitter as illustrated in the "Electrical connection" section.
• Connect the transmitter as illustrated in the "Electrical connection" section.
• Commission the transmitter as explained in the "Commissioning" section.
3.1.1 Measuring system
A complete measuring systems comprises:
• The transmitter OPM223 or OPM253
• A pH/ORP electrode with or without an integrated temperature sensor
• An immersible, flow or retractable assembly
• A measuring cable(e.g. OPK9)
Options: extension cable, junction box VBA or VBM
C07-OPM2x3xx-14-06-00-xx-001.eps
Fig. 1: Complete measuring system OPM223/253
1
2
3
4
5
Flow assembly OPA250
Junction box VBA
Transmitter OPM253
Measuring cable e.g. OPK9
Transmitter OPM223
6
7
8
9
Retractable assembly OPA450
Electrode, e.g OPS11
Immersion assembly OPA111
Extension cable
CAL REL
REL1
REL1
ALARM
REL2
REL2
E
CAL REL
REL1
REL1
ALARM
REL2
REL2
E
123
4
5
6
7
8
4
9

OPM223/253 Installation
9
3.2 Incoming acceptance, transport, storage
• Make sure the packaging is undamaged!
Inform the supplier about damage to the packaging.
Keep the damaged packaging until the matter has been settled.
• Make sure the contents are undamaged!
Inform the supplier about damage to the delivery contents.
Keep the damaged products until the matter has been settled.
• Check that the scope of delivery is complete and agrees with your order and the
shipping documents.
• The packaging material used to store or to transport the product must provide shock
protection and humidity protection. The original packaging offers the best protection. Also,
keep to the approved ambient conditions (see "Technical data").
• If you have any questions, please contact your supplier or your sales centre responsible.
3.3 Installation conditions
3.3.1 Field instrument
C07-OxM253xx-06-06-00-en-001.EPS
Fig. 2: Field instrument
!Note!
There is a hole in the punching for the cable entry (connection of supply voltage). It serves as
a pressure balance during air freight dispatching. Make sure no moisture penetrates the inside
of the housing before the cable installation. The housing is completely air-tight after the cable
installation.
CAL REL
REL 1
REL 1
ALARM
REL 2
REL 2
E
Pg 7
Pg 16
M 5
11/
0.43
Ø 6 /
Ø 0.24
115 / 4.53
157 / 6.18
247 / 9.72
70 / 2.76
70 / 2.76
154 / 6.06
170 / 6.69
mm / inch
Pg 13.5

Installation OPM223/253
10
3.3.2 Panel-mounted instrument
C07-OxM223xx-06-06-00-en-001.EPS
Fig. 4: Panel-mounted instrument
C07-OxM253xx-11-06-00-xx-001.eps
Fig. 3: View into the field housing
1
2
3
4
Removable electronics box
Partition plate
Terminals
Fuse
1
2
3
4
90 / 3.54
139 / 5.47
96 / 3.78
6 /
0.24
mm / inch
92 / 3.62
149.5 / 5.89

OPM223/253 Installation
11
3.4 Installation instructions
3.4.1 Field instrument
There are several ways of securing the field housing:
• Wall mounting with fixing screws
• Post mounting to cylindrical pipes
• Post mounting to square securing mast
!Note!
When mounting in the open air with unprotected exposure to weather conditions, a weather
protection cover (see Accessories) is required.
Transmitter wall mounting
C07-OxM253-11-06-00-en-002.eps
Fig. 5: Field instrument wall mounting
For wall mounting the transmitter, proceed as follows:
1. Drill the bores as shown in Fig. 5 .
2. Drive the two fixing screws through the securing bores (1) from the front.
3. Mount the transmitter on the wall as shown.
4. Cover the bores with plastic caps (2).
1
2
154 / 6.06
mm / inch
Ø 6 /
Ø 0.24

Installation OPM223/253
12
Transmitter post mounting
!Note!
You require a post mounting kit to secure the field device to horizontal and vertical posts or
pipes (max. Ø 60 mm(2.36")). This can be acquired as an accessory (see "Accessories"
section).
C07-OxM253xx-11-06-00-en-003.eps
Fig. 6: Post mounting field device to cylindrical pipes
For post mounting the transmitter, proceed as follows:
1. Guide the two securing screws (1) of the mounting kit through the openings of the securing
plate (3).
2. Screw the securing plate onto the transmitter using the four fixing screws (2).
3. Secure the retainer with the field device using the clip on the post or pipe.
1
2
3
1
1
3
Ømax. 60 /
2.36

OPM223/253 Installation
13
You can also secure the field device to a square universal post in conjunction with the weather
protection cover. These can be acquired as accessories, see "Accessories" section.
C07-OxM253xx-11-06-00-xx-004.eps
Fig. 7: Mounting field device with universal posts and weather protection cover
For mounting the weather protection cover, proceed as follows:
1. Screw the weather protection cover with 2 screws (bores 1) to the upright post (bores 2).
2. Secure the field device to the weather protection cover. To do so, use the bores (3).
3
1
2
3

Installation OPM223/253
14
3.4.2 Panel-mounted instrument
The panel-mounted instrument is secured with the clamping screws supplied (see Fig. 8).
The necessary installation depth is approx. 165 mm (6.50").
C07-OxM223xx-11-06-00-en-001.eps
Fig. 8: Securing the panel-mounted instrument
1 Wall of the cabinet
2 Seal
3Clampingscrews
* Required installation depth
3.5 Post-installation check
• After installation, check the transmitter for damage.
• Check whether the transmitter is protected against moisture and direct sunlight.
1
2
3
3
3
92 / 3.62
+0.5 +0.02
92 / 3.62
+0.5 +0.02
90 / 3.54
57 / 2.24
33 /
1.30
approx. 25 /
0.98
139 / 5.47
max. 45 /
1.77 6 /
0.24
96 / 3.78
92 /
3.62
approx. 165 / 6.50*

OPM223/253 Wiring
15
4Wiring
#Warning!
• The electrical connection must only be carried out by authorised technical personnel.
• Technical personnel must have read and understood the instructions in this manual and
must adhere to them.
• Ensure that there is no voltage at the power cable before beginning the connection work.

Wiring OPM223/253
16
4.1 Electrical connection
4.1.1 Connection diagram
The wiring diagram depicted in Fig. 9 shows the connections of an instrument equipped with
all the options. Connecting the sensors to the various measuring cables is explained in more
detail in the "Measuring cables and sensor connection" section.
C07-OPM2x3xx-04-06-00-xx-001.eps
Fig. 9: Transmitter electrical connection
A
B
C
D
E
F
G
H
I
Standard sensor
ISFET sensor
Outer screen connection for glass electrodes
Potential matching
Temperature sensor
Signal output 1 pH/ORP
Signal output 2 temperature, pH/ORP or controller
Binary input 1 (Hold)
Binary input 2 (Chemoclean)
J
K
L
M
N
O
P
Q
Auxiliary voltage output
Alarm (contact position currentless)
Relay 1 (contact position currentless)
Relay 2 (contact position currentless)
Relay 3 (contact position currentless)
Relay 4 (contact position currentless)
Current input 4 ... 20 mA
Power supply
pH
Ref.
11
12
13
47
48
49
57
58
59
51
52
53
54
55
56
PA/
PM
15 V
85
86
S
10-50 V
81
93
82
94
10-50 V
L+
L-
L1
N
23 +
24 -
mA
~=
41
42
43
pH
mA
31
32
mA
33
34
A
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
SRC
DRN.
B

OPM223/253 Wiring
17
!Note!
• The device is approved for protection class II and is generally operated without a protective
earth connection.
• To guarantee measuring stability and functional safety, you have to ground the outer screen
of the sensor cable:
– Glass electrodes (PR/PS device version): terminal "S"
– ISFET sensors (IS device version): PE distributor rail
This is on the cover frame for panel-mounted instruments and in the connection
compartment for field devices.
• Ground the PE distributor rail or the ground terminal.
Field instrument connection
Guide the measuring cables through the PG glands into the housing. Connect the measuring
cables in accordance with the terminal assignment (→Fig. 10).
C07-OPM253xx-04-06-00-xx-002.eps
Fig. 10: Field instrument connection compartment sticker
1 PE distributor rail for IS device version
Panel-mounted instrument connection
C07-OPM223xx-04-06-00-xx-003.eps
Fig. 11: Panel-mounted instrument connection sticker
1 Ground terminal for IS device version
pH / Redox (Glas)
42
+++++-----
434154 55 56
NC
SRC
DRN
31
11
12
32
13
PA/PM
3433
S
REF (Glas/IsFET)
(IsFET)
(IsFET)
NC 938685 94 81 82 NC
51 52 53 57 58 59 47 48 49
pH
Redox
Temp.
(opt.)
+15V
10mA
YE
WHRD
GN
BN
REL 4SENSOR REL 3 REL 2 REL 1
NC
Mains
Hilfsenergie
131094-4G
Digital 2
Digital 1
11 13
12
L1
+
N
-
(AC)
(DC)
Contacts:
max. 2A
AC: 250V/500VA
DC: 30V/60W
+-
23 24
4..20mA
1
BNC: pH/Redox + REF
31 +
Sensor
32 -
33 +
34 -
85 +
86 -
93 +
94 - 42
81 + 43
82 - 41
pH
Redox
Temp.
(opt.)
+15V
10mA
Digital 2
Digital 1
NC
NC
NC
131081-4E
S
REF
PA/PM
12
13
11
YE
WH
GN
RD
BN
SRC (IsFET)
(Glass)
IsFET
Glass
()
DRN
Mains Contacts: max. 2A, AC:250V/500VA, DC:30V/60W
L1 +
AC DC
N-
REL1
REL2
REL3
REL4
4..20mA
24
23
49
COM
COM
COM
COM
-
+
59
54
55
56
52
51
53
58
57
48
47
131084-4C
BNC: pH/Redox + REF
31 +
Sensor
32 -
33 +
34 -
85 +
86 -
93 +
94 - 42
81 + 43
82 - 41
pH
Redox
Temp.
(opt.)
+15V
10mA
Digital 2
Digital 1
NC
NC
NC
131081-4E
S
REF
PA/PM
12
13
11
YE
WH
GN
RD
BN
SRC (IsFET)
(Glass)
IsFET
Glass
()
DRN
Mains Contacts: max. 2A, AC:250V/500VA, DC:30V/60W
L1 +
AC DC
N-
REL1
REL2
REL3
REL4
4..20mA
24
23
49
COM
COM
COM
COM
-
+
59
54
55
56
52
51
53
58
57
48
47
131084-4C
1

Wiring OPM223/253
18
"Caution!
• Terminals marked NC may not be wired.
• Unmarked terminals may not be wired.
!Note!
Please label the sensor terminal block with the sticker provided.
4.1.2 Measuring cable and sensor connection
You require screened special measuring cables to connect pH and ORP electrodes to the
transmitter. The following multi-core and ready-to-use cable types can be used:
Structure and termination of the measuring cables
C07-OPM2x3xx-04-06-00-en-004.eps
Fig. 12: Structure of the special measuring cables
!Note!
For further information on the cables and junction boxes, please refer to the "Accessories"
section.
Sensor type Cable Extension
Electrode without temperature sensor OPK1 VBA / VBM box + OYK71 cable
Electrode with temperature sensor Pt 100
and TOP 68 plug-in head
OPK9 VBA / VBM box + OYK71 cable
ISFET sensor with temperature sensor
Pt 100 / Pt 1000 and TOP 68 plug-in head
OPK12 VBA / VBM box + OYK12 cable
pH individual electrode with separate
reference electrode and separate
temperature sensor
OPK2 VBA / VBM box + PMK cable
OPK1
OPK2
OPK9
OPK12
PM
pH / Redox
PM
pH or Redox
Ref. or Redox
Pt 100
PM
pH + Pt 100 / Pt 1000
PM
pH + Pt 100 / Pt 1000
Coax Ref.
pH or Redox
BN PM
BN PM
pH or Redox
RD Redox or Ref.
BU Ref.
GN Temp.
YE Temp.
WH Temp.
Coax BK Ref.
inner pH
GN Temp.
WH Temp.
YE Temp.
BN PM
Coax BK
inner
GN Temp.
WH Temp.
YE Temp.
RD DRN
BN PM
Ref
SRC IsFET

OPM223/253 Wiring
19
Field instrument measuring cable connection
Proceed as follows to connect a pH-electrode to the field instrument:
1. Open the housing cover to access the terminal block in the connection compartment.
2. Break the punching of a cable gland from the housing, mount a PG gland and guide the
cable through this Pg gland.
3. Connect the cable in accordance with the terminal assignment .
4. Tighten the Pg gland.
"Caution!
Make sure to protect the connectors, cable ends and terminals against moisture as this could
result in incorrect measurement!
Panel-mounted instrument measuring cable connection
To connect a pH electrode to the panel-mounted instrument, connect the cable in accordance
with the terminal assignment to the terminals on the rear of the device.
If you are using glass electrodes with the panel-mounted instrument, you have to terminate the
measuring cable with a BNC connector. A solder-free BNC connector is supplied with the
device.
Proceed as follows:
1. Cut off end sleeves 2 and 3 of the coaxial
cable (Fig. 13).
C07-OPM223xx-04-06-00-xx-013.eps
Fig. 13: Cable OPK1: device connection
1 Coaxial cable
2 Inner screen BK (ref.)
3 Inner coax (pH / mV)
4 Strand BN (PM)
2. Push the cable gland 5 and the washer 6
onto the coaxial cable.
3. Remove the insulation (13 mm(0.51"))
and screw the clamping ring 7 onto the
insulation.
!Note!
Parts 5 to 7 are supplied with the BNC
connector for cable diameters 3.2 mm
(0.13") and 5 mm (0.20").
4. Fold the braided screen 8 of the screen
over the clamping ring and cut off the
excess material.
5. There is a semi-conductor layer 14
(conductive foil) between the inner
insulation and the braided screen 8. Strip
this semi-conductor layer to the braided
screen.
C07-OPM223xx-04-06-00-en-014.eps
Fig. 14: Terminating the pH connecting cable for
mounting the BNC elbow plug
3
4
1
2
56
56 7
8
14
13 / 0.51
16 / 0.63

Wiring OPM223/253
20
Examples for connecting pH and ORP sensors
The following diagrams show the connection of various pH and ORP sensors.
C07-OPM2x3xx-04-06-00-xx-010.eps
Fig. 17: Connecting glass electrode OPS11 with OPK9 (left) and ISFET sensor OPS471 with OPK12
A Panel-mounted instrument
B Field instrument
C Potential matching PM for symmetrical connection
6. Remove the inner insulation (4 mm
(0.16")).
7. Position end sleeve 13 onto the stripped
inner conductor and secure the end
sleeve with a crimping pliers. C07-OPM223xx-04-06-00-en-015.eps
Fig. 15: Terminating the pH connecting cable for
mounting the BNC elbow plug
8. Push the BNC connector housing 9 over
the cable. The inner conductor must be
located at clamping surface 10 of the
connector.
9. Tighten the cable gland 5.
10.Insert the clamp element 11 and screw in
the connector cover 12. This creates a
safe connection between the inner
conductor and the connector pin. C07-OPM223xx-04-06-00-xx-016.eps
Fig. 16: Mounting the pH connecting cable in the
BNC elbow plug
13
4 /
0.16
59
10
11
12
J
SS
DRN
PA/
PM
PA/
PM
OPK9 OPK12
OPS11 OPS471
B
CC
B
S
GN WH YE BN
Schirm /
Screen
11 12 13
11 12 13
BN BN
BNC
BK
BK
BK
innen /
internal
innen /
internal
SRC
Ref
SRC
Ref
Ref
pH/
Redox
GN WH YE RD BN
PE
PE
AA
)
This manual suits for next models
1
Table of contents