Ohio Medical 263748-C User manual

12.1” Touchscreen Master Alarm
Service Manual
®

2550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
Table of Contents
1.0 Responsibilities ............................................................................................................... 3
1.1 Installer Responsibilities.........................................................................................................3
1.2 User Responsibilities .............................................................................................................3
2.0 Alarm System Description & Functions ............................................................................. 3
2.1 Description of Basic Alarm & Functions...................................................................................3
2.2 Normal, Alarm & Maintenance Mode Condition Views ...............................................................4
2.3 Alarm Banners & Silence Alarm Conditions ..............................................................................5
2.4 Testing The Alarm .................................................................................................................5
3.0 Installation ...................................................................................................................... 6
3.1 Box Assembly .......................................................................................................................6
3.2 Internal View of Master Alarm .................................................................................................6
3.3 Installation Instructions Prior To Drywall Plaster .......................................................................7
3.4 Box Wiring & Drywall/Plaster Preparation ................................................................................8
3.5 Instructions After Drywall & Plaster.........................................................................................9
3.6 Sensor Connections To Master Alarm Input Terminal(s)...........................................................10
3.7 Master Alarm Outputs..........................................................................................................12
4.0 Set-Up & Programming.................................................................................................. 13
4.1 Important Electrical Safety Notice Prior To Set-Up..................................................................13
4.2 Initial Set-Up........................................................................................................................14
4.3 Programming, Conguration & Setting Up Alarm Points..........................................................15
Alarm Event Log
View All Events & History
View Single AP Log
Information
Test Alarms Points
Other Settings (Display, Factory Reset, Scroll Time)
5.0 Specications................................................................................................................ 19
6.0 Dimensions ................................................................................................................... 20
7.0 Part Numbers................................................................................................................ 20
8.0 Battery Replacement..................................................................................................... 21
9.0 Troubleshooting............................................................................................................. 22
10.0 Wiring Diagram ........................................................................................................... 23

3
550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
1.0 Responsibilities
Information contained in this Installation and Operation Maintenance Manual pertains to the Ohio Medical Color LCD Touch
Screen Master Alarm (MA) System. The Master Alarm System will operate as described in this manual when operated and
serviced in compliance with the instructions.
1.1 Installer Responsibilities
The alarm should be handled, installed, and tested per the recommended practice as described within this manual.
Should any repair or replacement become necessary, contact Ohio Medical Customer Service (800-448-0770) for original
equipment, replacement parts.
1.2 User Responsibilities
The alarm should be tested and examined periodically according to facility codes. Any parts which are found to be
damaged, corroded, contaminated, etc. should be replaced.
2.0 Alarm System Description & Function
PLEASE NOTE THE FOLLOWING DEFAULT PASSWORD (PW) = “1111”
Note: The unit’s password may be changed anytime. Please contact Ohio Medical Customer Service if your password is forgotten. A Factory
Reset will need to be performed. Upon a Factory Reset, ALL user-customized information/settings will need to be re-entered. Given this,
please store your password in a secure location.
2.1 Description of Basic Alarm & Functions
The alarm is designed to monitor and display the status of up to 30 Alarm Points (APs). When an alarm condition occurs,
a signal is sent to the MA and is displayed on the Liquid Crystal Display (LCD). The unit is capable of relaying alarm
conditions to a Building Management System (BMS) via Dry Contacts, Modbus (or BACnet) or, via Ethernet connection.
Custom alarm labels may be created or chosen in the preprogrammed menu. Examples of alarm conditions include: High/
Low Gas Pressure, Low Vacuum, Manifold Reserve Tank In-Use, High Temperature Shutdown, Reserve Pump Running.
Alarm Events may be viewed/cleared per an individual alarm condition or, collectively as a group. The unit is also
equipped with a Maintenance Mode to permanently silence the audible portion of the alarm until the condition(s) causing
the alarm are xed. Visual Indicators always remain.
Other Key Functions Include:
Universal 100V-240V AC Power Input with Circuit Breaker Protection
Normally Open (N.O.) or Normally Closed (N.C.) alarm point set-up
Alarm Condition Communications (to BMS): Via BACnet, Modbus, Ethernet or Dry Contacts
Up-To 30 Dry Contact Outputs
12.1” Full Color LED Screen; Password Protection
Adjustable Screen-Scroll and Audible Alarm Silence Options
2.2 Normal Alarm & Maintenance Mode Condition Views
PLEASE READ THIS MANUAL IN ITS ENTIRETY BEFORE PROCEEDING
HAZARD OF ELECTRICAL SHOCK OR BURN. TURN OFF POWER
BEFORE WORKING ON THIS EQUIPMENT.
WARNING! SOME EDGES MAY BE SHARP, HANDLE WITH
CAUTION.

4550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
An AP will be displayed in three different ways:
1. Normal Alarm Condition: An AP will display with a green background and white text (as shown below) if
conditions on the source equipment are operating within normal operating parameters.
2. Alarm Condition: An AP in an alarm condition will display with a red background and white text (as shown
below) if conditions on the source equipment are operating outside normal operation.
3. Maintenance Mode: An AP in maintenance mode will display with a yellow background with black text (as
shown below) …. When the AP is manually placed in Maintenance Mode.
Figure 2.2 Below represents a 30 alarm points (APs) set-up. Two APs are in an alarm condition (red), one is in
maintenance mode (yellow) – with the rest seen as operating normally (green).
[FIGURE 2.2]
3. Maintenance Mode
Alarm Point Inputs, such
as INPUT P2
1. Normal Alarm
Condition
Alarm Point Inputs, such
as INPUT P3 thru INPUT
P29
2. Alarm Condition
Alarm Point Inputs, such
as O2 Changeover and
INPUT P30
{
Figure 2.2 Showing Master Alarm Front LCD Touch Screen
Note: Alarm Point Input titles (i.e. O2 Changeover) are customizable by the user.
2.4 Testing the Alarm Points (APs) [Visual & Audible]
The MAIN MENU screen contains a Test Alarms button. Press and hold the button for approximately ve seconds. The
alarm will sound for 10 seconds along with red and white ashing visual indicators for all Inputs. See Figure 3.C
[FIG 2B]
[FIG 2.4]

5
550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
2.3 Alarm Banners & Silence of Audible Alarm Conditions
The audible alarm will sound under any of the following key conditions:
1. An alarm condition exists for one or more APs.
2. The user adjustable Silence Duration time elapsed and any alarm condition is still present.
3. An alarm input on the MA is congured as Normally Open (N.O.) and the dry contacts for the AP (associated with
the Source Equipment) are congured as Normally Closed (N.C.).
4. An AP is congured, but no actual physical connection to the source equipment is made.
Silencing the Alarm
The Audible Alarm may be silenced in three ways. If the originating cause is not corrected, the following options will not x
the alarm condition.
1. Silencing Button: The audible alarm may be temporarily silenced at any time by pressing
the Master Alarm Silencing Button (right) in the lower right portion of
the screen, regardless of the screen. Each time the alarm is silenced,
the user selected silence duration time will restart.
2. Silencing Duration: The default silencing duration time is 5 minutes. The silence duration can
be user set to a maximum of 59 minutes & 59 seconds. Silencing duration
must be set greater than 0.
3. Maintenance Mode: Any AP can be manually placed into maintenance mode. This will silence the audible alarm.
Visual alarm indicators remain.
2.4 Testing the Alarm Points (APs) [Visual & Audible]
The MAIN MENU screen contains a Test Alarms button. Press and hold the button for approximately ve seconds. The
alarm will sound for 10 seconds along with red and white ashing visual indicators for all Inputs. See Figure 3.C
[FIG 2B]
[FIG 2.4]
Bafes fully open for
loudest alarm
Bafes fully closed for
softest alarm
[FIGURE 2.B]
Figure 2.B The volume of the alarm may be adjusted by rotating
the volume control located in the lower right corner of the box
(Reference Figure 3.2).
Master Alarm
Silencing Button
[FIGURE 3.C]
Master Alarm
Silencing Button

6550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
3.0 Installation
The alarm is shipped fully wired, tested and calibrated. For ease of assembly in walls, the alarm is shipped in two sections;
the Box and Front Panel assemblies. The box is installed in the drywall, then the front panel is attached. Finally, box wiring
and sensor inputs/outputs are congured.
Primary Power Supply
Circuit Breaker
IO for Alarm Outputs
Expansion
Adapter
Volume
Control
1. Input Terminal Blocks
3.2 Internal View of Master Alarm
Primary components integrated within the Box Assembly include what is shown in Figure 3.2 below.
[FIGURE 3.2]
BACnet
Module
Optional
Depending on model
Depending on model
2. Output Terminal Blocks
3.1 Box Assembly
All sides of the enclosure have knock outs for the power supply
wiring and the input/output terminal blocks. Use a hammer and at
headed screwdriver to punch through the knockouts as shown in
Figure 3.1.
[FIGURE 3.1]

7
550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
3.3 Installation Instructions Prior to Drywall Plaster
It is important to mount the box between the wall studs at the required height for its intended use. Check all federal, local,
and building codes prior to installation. Adjustable wall-mounted brackets are provided to accommodate for wall thickness
after dry walling, plastering, or other means of wall nishing.
Figure 3.3.1 Remove the metal alarm box assembly from the carton.
Figure 3.3.2 Remove the cardboard dust cover from the metal box via the two screws (X). Re-insert the screws into the
box; they will be used later to hold the cardboard cover in place during drywalling/plastering, and ultimately
used for the front panel hinge assembly.
Figure 3.3.3 Remove the metal wall brackets and hardware from the box located inside the primary box the unit has
shipped in.
Figure 3.3.4 Install the brackets to the left and right sides of the box.
3.3.5 Adjust the brackets so that the front edge of the box assembly
[as shown without the hinged cover] is ush with the nished wall.
3.3.6 Once positioned & square, tighten the hardware securing the
mounting brackets to the alarm box assembly and wall supports.
Do not FULLY tighten hardware at this time.
Keep lightly snug to adjust to wall conditions.
[FIGURE 3.3.1]
[FIGURE 3.3.2]
[FIGURE 3.3.3]
[FIGURE 3.3.4]
X
Reinsert screws

8550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
3.4 Box Wiring & Drywall/Plaster Preparation
For safety, the circuit breaker must be in the OFF position prior to electrical connections.
ON Position
pushed and locked in
OFF Position
fully extended out
Strip ½” of insulation and connect the ground wire to the green ground terminal block.
Ground Lead Location
Strip ½” of insulation, connect the neutral lead wire to the power supply terminal labeled “N”.
Neutral Lead Location
Live Lead Location
Strip the insulation and connect the live lead wire to the circuit breaker.
If not already removed, remove the two screws from the enclosure and set aside.
Note: For clarity, the product is shown removed from the wall.
Remove the Two Screws

9
550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
Figure 3.4.5 Take the cardboard dust cover and remove the two sides at the perforations.
Note: If a dust cover is not provided or lost, a piece of cardboard may be cut to cover the alarm box during the drywalling or plastering.
Figure 3.4.6 Gently slide the cardboard in the slits between the inner and outer faces of the alarm box. The two holes
in the cardboard should align with the two holes on the bottom of the alarm box. Assemble the two screws
to complete the process.
Installation Note: The cardboard may also be temporarily taped.
Perforations
Screws
Slits
3.5 Instructions After Drywall & Plaster
Once the drywalling/plastering is complete, remove the cardboard dust cover by unscrewing the two bottom screws. Set
the screws aside and discard the cardboard.
Figure 3.5 Carefully remove the front panel assembly from the bottom of the shipping box and set it aside (with the HMI
touch screen facing upwards).
[FIGURE 3.4.5]
[FIGURE 3.4.6]
[FIGURE 3.5]

10 550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
Figure 3.5.3 Mount the front panel hinge assembly to the box assembly using the two screws that held the cardboard
dust cover on during the drywalling/plastering procedures.
Hinge & Screws
Figure 3.5.4 To attach the restraining lanyard (black plastic cable) from the front panel to the box, remove the nut from
the stud inside the right side of the box assembly. Take care not to remove the bushing, then install the
restraining lanyard over the bushing on the stud. Re-install the nut and hand tighten.
Nut/Bushing Restraining Lanyard
3.6 Sensor Connection(s) to Master Alarm Input Terminal(s)
Figure 3.6 Connect the power wire harness and PLC adapter cable from the expansion adapter to the HMI.
A designated INPUT terminal strip (See Figure 3.6A) is provided to connect up to 30 paired wires from APs (located at the
Source Equipment) to the MA (Master Alarm). Connect the Positive (+) wire leads to the left side of the Input terminal strip
labeled MA # +. Connect the Negative (-) wire leads to the right side of the Input terminal strip labeled MA # -.
PLC Adapter Cable
Power Wire Harness
[FIGURE 3.6]
[FIGURE 3.5.3]
[FIGURE 3.5.4]

11
550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
A corresponding OUTPUT terminal strip is provided to send AP conditions to the Building Management System (BMS).
Figure 3.6A Master Alarm [Labeled] Input & Output Terminal Blocks
Note: Wiring to be 18-22 gauge, shielded, twisted and supplied by the installer. Length may be up to 5,000 feet (1,524 meters) and to be in a
good repair with properly stripped ends (to avoid shorts).
MA INPUTS
M1 to M30
MA OUTPUTS
M1 to M30
Push a small athead screwdriver into the square release hole on the terminal strip to make connections. Be sure the bare
wire ends are not exposed after wire insertion. See Figure 3.6B below.
[FIGURE 3.6A]
[FIGURE 3.6B]

12 550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
3.7 Master Alarm OUTPUTS
If using dry contacts to connect the APs to a BMS, use the same wiring method/logic as with the INPUTS. It is important
that the wiring for each alarm point OUTPUT correlates to the wiring for the alarm point INPUT. See Figure 3.7 below.
Example: MA 1 INPUT connection corresponds to INPUT P1 on the display. MA 1 OUTPUT connection to the BMS would be wired to the MA 1
Output Terminals.
Corresponds to
INPUT P1
3.7.1 Alarm Outputs via Modbus
For installations that require Alarm Communications via Modbus, the process below should be used in order to
communicate AP information between the Master Alarm and the BMS.
Using communication cable/connector type RJ-11 plug into Serial Port #2 on the HMI/PLC (See Figure 3.7.1). Plug
the other end of the cable into the device that will be monitoring the APs. Reference page 14 for Modbus Net ID screen
conguration.
PORT 2 Master Alarm HMI/PLC Modbus Connection
Use Port 2 for Remote AP Communications. Port 2 is clearly
marked on the unit – please be sure to connect properly.
[FIGURE 3.7]
[FIGURE 3.7.1]
MA INPUT #1 (+/–)
terminal connection points
MA OUTPUT #1 (+/–)
terminal connection points

13
550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
3.7.2 Setting Up Modbus Net ID
4.0 Set-Up & Programming
Important: Ensure all steps in the installation section have been completed properly prior to turning the alarm on.
4.1 Important Electrical Safety Notice Prior To Set-Up
Power-Up the Alarm
The alarm must be properly wired to a reliable power supply prior to energizing the circuit breaker. The circuit breakers
ON and OFF positions are achieved by depressing the 2-Amp circuit breaker button until a distinct click is heard - and then
releasing.
3.7.3 Alarm Outputs via BACnet
• Protocol: BACnet/MSTP
• Network: RS485, 2-wire, 76800 Baud
• MAC ID: 2
• Instance: 32000
• Alarm Output: via Ethernet
Note: Please reference the RTA User Guide for BACnet set-up to BMS.
[FIGURE 3.7.2]
• From the Main Screen Press Menu
• Press Settings
• Enter Password and Enter
• Press Communications Options
• Press Congure Network Settings
• Next to MODBUS Net ID enter 2
Note: The BMS conguration will need to match this setting.
[FIGURE 3.7.3]
[FIGURE 4.1]
ON Position
pushed and locked in
OFF Position
fully extended out
3.7.4 Alarm Outputs via Ethernet
• Protocol: Ethernet via TCP/IP
• Comm Cable: Use CAT5 STP (shielded twisted pair) cable
• RJ45 Connector, BaudRate 9600
• Network ID: 2
• Drop Line Length: up to 100 meters
[FIGURE 3.7.4]

14 550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
4.2 Initial Set-Up
Note: The following steps/photos are for reference only. Set-up may not correlate with the pictures below.
1Turn on the alarm and verify that the Select Language Screen is displayed.
Press the English button and press the arrow to move to the next screen
(bottom right of screen).
2Press the Date button, enter today’s date and press Enter.
Press the Time button, enter the time (24-hour format) and press Enter.
Press right arrow.
3Press the Monitored Zone Name button (blue box), enter “XXXX”
(maximum characters list noted on Screen Header) press Enter.
Press right arrow. You will now be in the FACILITY NAME screen.
4Press the Name button, enter “XXX”, and press Enter.
Press the City button, enter “XXX”, and press Enter.
Press State/Providence button, enter “XXX”, and press Enter.
Press the Country button, enter “XXX”, and press Enter.
Press right arrow. You will be in DEALER INFORMATION screen.
5Input dealer/distributor information as required.
When done, press right arrow. You will be at the Main Menu.
6Password Change (if required)
Press the Settings button, Enter 1111.
Press Systems Setting button
Press the Change Password Button
Enter 1111 or current password
If you wish to change the password, do so here
Press ESC
7Change the SILENCE DURATION time (if required), which will silence the
alarm for a maximum of 59 minutes and 59 seconds before sounding again.
Setting the silence duration to 00:00 will disable the silence feature.
Settings > System Settings [Enter PW] > Silence Duration

15
550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
4.3 Programming, Conguration & Setting-Up Alarm Points
a) Press the Menu button. Press the Settings button. Enter the Password then Enter. Press the Congure Alarm
Points button.
b) Press the blue box to the right of the Number of Alarms to set or change the total number of APs to be displayed
(See Figure 4.3) on the screen (may enter 1 – 30 APs). The alarm may sound (the main screen will come up at this
point). Press the silence button at the lower right portion of the HMI to silence the alarm.
Enter the number of APs to be displayed on the screen. The
alarm may sound after Enter is pressed. Press the ashing
audio symbol in the lower right portion of the HMI to silence.
To change the name and status of an AP, press CONFIGURE
button next to the AP you wish to change.
To Set the Alarm Point Name
Press the blue EDIT SIGNAL TEXT button to change ASSIGN the name of the alarm point. A Preprogrammed Label from
the list of names may be chosen by tapping the ASSIGN button or choose Create Custom Label – to create a custom label.
The two options are discussed below.
Note: A preprogrammed label may be chosen (from an NFPA Recommended List of AP names) or edited to conform to local requirements. To
choose a preprogrammed label, simply scroll through the label names and tap the blue Assign button when the desired label is seen. To create
a custom label – see next page.
Custom
{
Preprogrammed
[FIGURE 4.3]
[FIGURE 4.3A]

16 550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
Creating a Custom AP Label
A custom label may be created from scratch by pressing the blue ASSIGN button next to Create Custom Label at the top of
each list of preprogrammed label options. Creating a custom label may require a different name length for 10, 20 and 30
Alarm Point Screen-Viewing.
Note: Up to forty (40) characters may be entered for 10 alarms view per screen, twenty-four (24) characters for 20 alarms view per screen,
and sixteen (16) characters for 30 alarms per screen. An example display for each option is shown on the left. An example of the views per
screen shown in Figure 4.3B.
Alarm Active State Setting (N.O. or N.C.)
To set one AP at a time:
The Alarm Active State setting allows any AP to be set to a
Normally Open [ N.O.] or Normally Closed [N.C.] position.
To set all APs the same:
Instead of individually selecting N.O./N.C. for each and every AP. The Set All Points
button sets all points to the same state. To perform this, select N.O. or N.C. for one AP
and then Press and hold the blue button on the right for four (4) seconds.
[FIGURE 4.3B]
[FIGURE 4.3C]
[FIGURE 4.3D]

17
550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
How to Place an AP into Maintenance Mode
The Maintenance Mode option allows maintenance to be performed on selected APs - canceling the audible alarm for a
particular AP.
An alarm point placed into Maintenance Mode is displayed on the Main Screen in black lettering with a yellow background.
Once the root cause is xed – the alarm point may manually be taken out of Maintenance Mode.
Alarm Event Log
Pressing the Event Log button from the MAIN MENU screen allows viewing of the alarm points EVENT LOG. In this screen,
the history of ALL APs or individual APs may be viewed or cleared. To view activity of all APs, press on the blue VIEW ALL
EVENTS button in the upper middle portion of the HMI. To view activity of individual points, press the small blue VIEW LOG
to the left of the associated AP.
View ALL AP Log
Pressing on the VIEW ALL EVENTS button shows the event history of all APs in chronological order. For each event, the (1)
status and (2) timestamp is shown.
[FIGURE 4.3E]

18 550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
Clear Log for ALL APs
To clear the history of ALL the APs, press the blue Clear Log button in the upper right hand of the HMI. This clears all
history, and the history for individual points will no longer be available
View Single AP Log
Pressing the VIEW LOG button to the left of INPUT point name will show the event history of that individual AP. The screen
will look identical to the VIEW ALL EVENTS option, but will only show the single point alarm/event history.
Clear Log for a Single AP
To clear the history, press the Clear Log button in the upper right hand of the HMI.
This will only clear the history for the individual AP selected. The other points’ histories may still be viewed within their
individual View Log or within the VIEW ALL EVENTS option.
INFORMATION – Test APs: Required for Certication
Test APs
The Test Alarms button tests the audible and visual cues of an alarm condition. To test the alarm, press and hold the Test
Alarm button for approximately 4-5 seconds. The alarm should sound, accompanied by displacing red/white ashing visual
Indicators for ALL Inputs, and an audio symbol in the lower right-hand portion of the HMI. To silence the alarm, press the
ashing audio symbol in the lower right portion of the screen. In approximately ten (10) seconds after the alarm begins,
the monitor will resume previous conditions.
Master Alarm
Silence Button

19
550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
Scroll Time
From the Main Menu press Settings [Enter PW] > Press Enter > Display Settings. At the bottom of the screen, press the
blue box adjacent to Scroll Time to enable the pop up keyboard. The scroll time must be entered in the proper minutes/
seconds format. The maximum value that may be entered into the box is 59:59. The default scroll time is 15 seconds.
Note: If any input sustains an alarm condition, the scroll feature will be disabled. Screens will only be allowed to scroll if all alarm conditions are
corrected, or if all alarm inputs in an alarm condition are placed in Maintenance Mode.
Factory Reset: Please contact Ohio Medical for Factory Reset.
5.0 Specications
General
12.1” Liquid crystal display (LCD)
Supply power: 100v-240v AC
2A circuit breaker protected
Alarm point inputs: up to 30pts
Dry contacts: 30 (optional)
Remote alarm communications: Modbus (standard); BACnet (optional); Ethernet (optional)
Fully complies with NFPA®99
Manufactured in an iso 9001 and 13485 environment
Enclosure materials constructed of heavy duty steel
Alarm conditions shall be identied via audible alarms and visual indicators
Audible alarm-point silence button provided to silence the alarm (eld adjustable duration)
Adjustable audible alarm horn
Audible alarm is to remain in an alarm state until the condition that initiated the alarm condition is corrected
Visual alarm-point indicators shall illuminate and/or ash even if the audible alarm is silenced and, to remain in an
alarm state until the condition initiating the alarm is corrected
Other Settings
Congure Display
From the Main Menu (Settings [Enter PW] > Display Settings > Congure Display) press the blue Congure Display button.
Select the desired Alarms Per Screen in conjunction with the Screen Appearance setting. An example of every display
option is shown below. The display option has no effect on the monitor’s performance.
10pt view 20pt view 30pt view

20 550731 (Rev. 2.1) 11/19
Master Alarm Service Manual
Panel settings (completely eld adjustable and password protected)
All settings accomplished via front screen panel
Selectable English or Spanish instructions
Password protected (with customer chosen passwords) at general, set-up and maintenance levels
Field adjustable 0-30pt alarm set-up/viewing
Adjustable N.O./N.C. Input selection with set-all feature
Adjustable 10pt, 20pt or 30pt; per-screen-viewing
Defaults to all points view in an alarm condition
Pre-congured or customizable alarm point names
Auto scroll with manual scroll options for non-alarm condition viewing
Alarm point events are logged and may be viewed/cleared as individual or all alarm events
Maintenance mode for set-up and alarm point maintenance
6.0 Dimensions
7.0 Part Numbers & Spare Part Numbers
Front View
14.5”
36.83 cm
14.5”
36.83 cm
Top View
14”
35.56 cm
Left Side View
4.9”
12.45 cm
Right Side View
4”
10.16 cm
14”
35.56 cm
Part Number Part Number Description
263748 Alarm, Master, HMI 30 Point
263748-C Alarm, Master, HMI 30 Point with
Dry Contacts
263748-B Alarm, Master, HMI 30 Point with
BACnet
263748-E Alarm, Master, HMI 30 Point with
Ethernet
263748-CE Alarm, Master, HMI 30 Point with
Dry Contacts & Ethernet
263748-CB Alarm, Master, HMI 30 Point with
Dry Contacts & BACnet
Spare Part Number Spare Part Number Description
263643 I/O Module, Remote 16 Relay Output
263651 HMI/PLC, 12.1” Color Touchscreen
263652 Ethernet Card
263654 I/O Module, Snap-In 3V Digital
263660 Adapter, I/O Expansion Module
263668 Battery, Lithium, Button Cell, 3V
263669 Buzzer, Panel Mount 22mm
263670 Power Supply, 240Vac/24Vdc
263671 Fuse Modular Terminal Block, Circuit Breaker
263672 Thermal Device Circuit Breaker
263687 BACnet Ms/Tp Gateway
263662 Communication Cable, PLC To I/O Expansion
Module Adapter, 1 Meter
This manual suits for next models
5
Table of contents