Olympia POWER LIGHT Series User manual

Thank you for purchasing this product of
Olympia Electronics. A European manufacturer.
GENERAL
o
These luminaires are used indoors (ta 40 C)
where emergency light is needed. Each
luminaire must be permanently connected to
mains power supply. In normal operation the
power and the charge indicators light to show
that the batteries are in charging condition. In
case of a mains power supply failure the
power and the charge indicators turns off and
the luminaire will light the spot lamps
automatically in emergency mode. When the
mains power supply is restored the device
turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 2.
OPERATION
When the device is powered from the mains,
the charge and power indicators should light.
The charge indicator confirms the charging of
the batteries. If it does not light, probably, the
batteries are disconnected. If it does not light
and the batteries are connected, then contact
the technician. As long as the charge indicator
blinks, the batteries of the luminaire are
charging and in this period, any autonomy test
must be avoided. When the charging circle is
complete, the indicator lights continuously (it
can be used as an indication of a power
interruption). The batteries charging is done by
an 3 stages technological advanced procedure,
to ensure the appropriate and full charging of
the batteries.
The power indicator confirms the proper
connection to the mains. The TEST button, has
a dual use. If pressed instantlly while the device
is connected to the mains, the device simulates
the power interruption, by lighting the lamps for
3''. In this way, we can control the driver circuit
of the lamps and the lamps as indicated in
paragraph 3 in the text below .
When the voltage is interrupted, with
corresponding pressings of the button, we can
choose the operation of 2,1 or no lamps, either to
increase the autonomy time or not to consume the
battery power unnecessarily. This option is
canceled when the network is restored.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel
only.
2. The device must be connected to the mains
power supply thru a fuse dependent by the total
amount of the line’s power load.
3. It is sugested to check every month the
indication LED for battery charging, and by
pushing instantly the TEST button to check the
emergency cirquit and the lamps. If the
luminaire does not light contact the installer.
4. It is sugested to check every 6 months the
Page 1 from 2
``POWER LIGHT`` SERIES FOR NON-MAINTAINED EMERGENCY LUMINAIRES
Bayblend FR3010, transparent polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Pb)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
24h
Power indicator, battery charge indicator, TEST button
From overcharge and deep discharge
IP 42
o
0 to 40 C
Up to 95%
3 years (1 year for the lamps and the battery)
90 min 60 min 3h
580lm 1620lm 580lm
2x20W (halogen) 2x20W (halogen) 2x55W (halogen)
3330gr. 5300gr.
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
302 x 94 x 330 mm 302 x 94 x 330 mm
GR-21GR-29GR-21/Η
220-240V AC/50-60Hz
12V/7Ah
14VA 24VA
2x12V/7Ah
923029000_23_023
High Quality European based Manufacturers
325 x 120 x 380 mm
7290gr.

Page 2 from 2
INSTALLATION INSTRUCTIONS
1. Install the included mounting accessories to hook the
device from the mounting holes (fig. 1).
2. Unfasten the 4 mounting screws to remove the front plastic
cover (fig. 1).
3. Make sure that the battery’s cables are connected to the
respective poles. Black cable to (-) pole and red cable to (+)
pole.
4. Install the included
cable gland or the
rubber o-ring. Pass
thru the mains cable
and stabilize it by
fastening the cable
gland.
Connect the wires to
the terminal blocks L
for live wire and Ν for
neutral.
5. Refit with care the
front plastic cover, by
fastening the 4
mounting screws
(tightening torque 1Nm).
m i n i m u m a u t o n o n o u s d u r a t i o n b y
disconnecting the mains power supply. Count
the time that the
lamps light and in case of less time than the
minimum autonomous duration the batteries
must be replaced. If the measured time is
c o n s i d e r a b l y l e s s t h a n t h e m i n i m u m
autonomous duration contact the installer.
The replacement of the battery and the light
source must be done using parts of the same
type, by the manufacturer or by a competent
person.
5. In case of inactive use for a period greater
than 2 months, disconnect the battery by
pulling out the battery’s connector.
6. I s not allowed to discard batteries in to t i
common trash bins, they must be
discarded only in battery recycling
points. Do not incinerate.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
0: Non-maintained (*)
A: Including test device
*60: 1 hour duration
*90: 1,5 hour duration
180: 3 hour duration
(*) Non-Maintained operation: The luminaire
lights its illumination source, only in power
supply’s failure.
Maintained operation: The luminaire lights its
illumination source, when it is powered by the
mains power supply or not.
Battery replacement.
It can be done only by a competent person and
after the mains interruption.
1. Follo w t he step 2 of the i n stallation
procedure.
2. Disconnect the cables and remove the old
battery.
3. Connect the new battery with the same type
(step 3 of the installation procedure) and place it
in the position of the old one.
4. Follow the step 5 of the installation procedure
and power the device..
3
4
L
N
1
Minimum distance from lighted objects.
NOTE!!
After finishing the installation you must power the luminaire at least for 24 hours for battery
charging to perform the named autonomy.
923029000_23_023
TEST
button
Cover
retaining
screws
Fig. 1
Mounting holes
Char ge
indicator
Powe r
indicator
This manual suits for next models
3
Popular Lantern manuals by other brands

Lighting Technologies
Lighting Technologies LZ Series manual

BION TECHNOLOGIES
BION TECHNOLOGIES tunableWhite linea xs hp user manual

WE-EF
WE-EF RMC320 LED Installation and maintenance instructions

DOTLUX
DOTLUX LENSplus 4864-050015 user manual

ILP
ILP D2D-50WLED-UNIV-00K Series installation instructions

GE
GE ABVG2 Series Install Instruction Guide