Omicron CP TD1 User manual

CP TD1
User Manual

CP TD1 User Manual
2OMICRON
Manual Version: ENU 1035 05 03
© OMICRON electronics GmbH 2018. All rights reserved.
This manual is a publication of OMICRON electronics GmbH.
All rights including translation reserved. Reproduction of any kind, for example, photocopying,
microfilming, optical character recognition and/or storage in electronic data processing systems,
requires the explicit consent of OMICRON. Reprinting, wholly or in part, is not permitted.
The product information, specifications, and technical data embodied in this manual represent the
technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this manual is useful, accurate and entirely
reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be
present.
The user is responsible for every application that makes use of an OMICRON product.
OMICRON translates this manual from the source language English into a number of other languages.
Any translation of this manual is done for local requirements, and in the event of a dispute between the
English and a non-English version, the English version of this manual shall govern.

OMICRON 3
Contents
Contents
About this manual 5
Safety symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Related documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1 Safety instructions 7
1.1 Operator qualifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Safety standards and rules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2.1 Safety standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2.2 Safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2.3 Safety accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3 Operating the measurement setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.4 Handling cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 Orderly measures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.6 Static charges. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.7 Disclaimer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.8 Compliance statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.9 Recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2 Introduction 12
2.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2 Functional components of the Control Devices and the CP TD1 . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.3 CPC 100 and CP TD1 equipment trolley . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.4 Functional components of the CPC 100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.4.1 CPC 100 Front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.4.2 CPC 100 High-voltage and High-current outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4.3 CPC 100 ePC interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.5 Functional components of the CPC 80. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5.1 CPC 80 front panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5.2 CPC 80 mains power supply and Booster output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.5.3 CPC 80 ePC Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.6 TESTRANO 600 and CP TD1 equipment trolley . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.7 Functional components of TESTRANO 600. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.7.1 TESTRANO 600 front panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.8 TESTRANO 600 side panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.9 Functional components of the CP TD1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.9.1 CP TD1 grounding terminal and Booster input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.9.2 CP TD1 serial interface connector and measuring inputs . . . . . . . . . . . . . . . . . . . . . . . . 23
2.9.3 CP TD1 high-voltage connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.10 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3 Application 25
3.1 Preparations on site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2 Connecting the CP TD1 to the Control Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.3 Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.4 Disconnection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4 Introduction to capacitance and dissipation factor measurement 31
4.1 Theory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.2 Measurement of Capacitance and Dissipation Factor / Power Factor . . . . . . . . . . . . . . . . . . . . . . 37
4.3 "UST" and "GST" Measurements Using the Guard Technology . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5 Power transformers 39
5.1 Dissipation Factor Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.2 Capacitance Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

CP TD1 User Manual
4OMICRON
5.3 Two-winding transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.4 Measurements on two-winding transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.4.1 Measurements on a two-winding transformer with the CPC 100 and CPC 80. . . . . . . . . 45
5.4.2 Measurements on a two-winding transformer with TESTRANO 600 . . . . . . . . . . . . . . . . 45
5.5 Three-winding transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.6 Measurements on three-winding transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.6.1 Measurements on a three-winding transformer with the CPC 100 and CPC 80 . . . . . . . 51
5.6.2 Measurements on a three-winding transformer with TESTRANO 600. . . . . . . . . . . . . . . 56
5.7 Auto-Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
5.8 Reactors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6 High-voltage bushings 57
6.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.2 Types of bushings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.2.1 Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.2.2 Composite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.2.3 Compound-filled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.2.4 Dry or unfilled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.2.5 Oil-filled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.2.6 Oil-immersed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.2.7 Oil-impregnated paper-insulated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.2.8 Resin-bonded paper-insulated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.2.9 Solid, ceramic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.2.10 Gas insulated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.3 Capacitance and DF measurement on high-voltage bushings. . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.4 Ungrounded Specimen Test (UST) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.5 Grounded Specimen Test (GST) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
6.6 Hot collar test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7 Technical data 64
7.1 Technical data of the CP TD1 in combination with the Control Device . . . . . . . . . . . . . . . . . . . . . 64
7.1.1 High-voltage output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
7.1.2 Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
7.2 Mechanical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
7.3 Environmental Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
7.4 Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Support 69

OMICRON 5
About this manual
About this manual
This User Manual provides information on how to use the CP TD1 test system safely, properly and
efficiently. The CP TD1 User Manual contains important safety rules for working with the CP TD1 and
gets you familiar with operating the CP TD1. Following the instructions in this User Manual will help you
to prevent danger, repair costs, and avoid possible down time due to incorrect operation.
The CP TD1 User Manual always has to be available on the site where the CP TD1 is used. The users
of the CP TD1 must read this manual before operating the CP TD1 and observe the safety, installation,
and operation instructions therein.
Reading the CP TD1 User Manual alone does not release you from the duty to comply with all national
and international safety regulations relevant to working on high-voltage equipment.
Safety symbols used
In this manual, the following symbols indicate safety instructions for avoiding hazards.
DANGER
Death or severe injury will occur if the appropriate safety instructions are not observed.
WARNING
Death or severe injury can occur if the appropriate safety instructions are not observed.
CAUTION
Minor or moderate injury may occur if the appropriate safety instructions are not
observed.
NOTICE
Equipment damage or loss of data possible

CP TD1 User Manual
6OMICRON
Related documents
The following documents complete the information covered in the CP TD1 User Manual:
Title Description
CPC 100 User Manual Contains information on how to use the CPC 100 test system and
relevant safety instructions.
CPC 100 Reference Manual Contains detailed hardware and software information on the
CPC 100 including relevant safety instructions.
CPC 80 User Manual Contains information on how to use the CPC 80 test system and
relevant safety instructions.
TESTRANO 600 User Manual Contains information on how to use the TESTRANO 600 test system
and relevant safety instructions.
CPC 100 PTM User Manual Contains information on how to use the Primary Test Manager PTM
together with the CPC 100.
CP CR500 User Manual Contains information on how to use the CP CR500 compensating
reactor and relevant safety instructions.
CP TC12 Reference Manual Contains information on how to use the CP TC12 oil test cell and
relevant safety instructions.
CP CAL1 User Manual Contains information on how to use the CP CAL1 calibration system
and relevant safety instructions.
TD1 C-Load User Manual Contains information on how to use the TD1 C-Load accessory and
relevant safety instructions.

OMICRON 7
Safety instructions
1 Safety instructions
1.1 Operator qualifications
Working on high-voltage assets can be extremely dangerous. Testing with the CP TD1 must be carried
out only by qualified, skilled and authorized personnel. Before starting to work, clearly establish the
responsibilities.
Personnel receiving training, instructions, directions, or education on the CP TD1 must be under
constant supervision of an experienced operator while working with the equipment. The operator is
responsible for the safety requirements during the whole test.
1.2 Safety standards and rules
1.2.1 Safety standards
Testing with CP TD1 must comply with the internal safety instructions and additional safety-relevant
documents.
In addition, observe the following safety standards, if applicable:
• EN 50191 (VDE 0104) "Erection and Operation of Electrical Test Equipment"
• EN 50110-1 (VDE 0105 Part 100) "Operation of Electrical Installations"
• IEEE 510 "IEEE Recommended Practices for Safety in High-Voltage and High-Power Testing"
Moreover, observe all applicable regulations for accident prevention in the country and at the site of
operation.
Before operating the CP TD1 and its accessories, read the safety instructions in this User Manual
carefully.
Do not turn on the CP TD1 and do not operate the CP TD1 without understanding the safety information
in this manual. If you do not understand some safety instructions, contact OMICRON before proceeding.
Maintenance and repair of the CP TD1 and its accessories is only permitted by qualified experts at
OMICRON Service Centers (see "Support" on page 69).
1.2.2 Safety rules
Always observe the five safety rules:
► Disconnect completely.
► Secure against re-connection.
► Verify that the installation is dead.
► Carry out grounding and short-circuiting.
► Provide protection against adjacent live parts.

CP TD1 User Manual
8OMICRON
1.2.3 Safety accessories
OMICRON offers a range of accessories for added safety during the operation of our test systems. For
further information and specifications, refer to the corresponding Supplementary Sheet or contact
OMICRON Support.
1.3 Operating the measurement setup
The CP TD1 works as an add-on device to the CPC 100, CPC 80 or TESTRANO 600 which controls the
measurement. In this manual, those devices are collectively named Control Device if no specific device
is referred to. Do not connect the CP TD1 to any other device than the CPC 100, CPC 80 or the
TESTRANO 600.
Only personnel qualified in electrical engineering and trained by OMICRON are authorized to operate
the CP TD1.
► Before starting the work, clearly establish the responsibilities.
Personnel receiving training, instructions, directions, or education on the CP TD1 must be under
constant supervision of an experienced operator while working with the equipment.
The operator is responsible for the safety requirements during the whole test.
► Do not enter the high-voltage area if the red warning light of the Control Device is on since all outputs
can carry dangerous voltage or current!
► Always obey the five safety rules and follow the detailed safety instructions in the respective user
manuals.
Figure 1-1: Example of the separation of safe and high-voltage area using the CP TD1 with
TESTRANO 600
CP TD1
CPC 100
TESTRANO 600
Device under test
Safe area High-voltage test area
Barrier height:
1 - 1.4 m / 3.3 - 4.6 ft
Distance:
min. 1.5 m/5 ft

OMICRON 9
Safety instructions
Before performing tests using high voltage, observe the following instructions:
► Do not use the test equipment without a good connection to substation ground.
► Do not insert objects (for example screwdrivers, etc.) into any input/output socket.
► Do not operate the CP TD1 under ambient conditions that exceed the temperature and humidity limits
listed in 12.2 "Environmental Conditions" on page 109.
► Make sure to position the test equipment on dry, solid ground.
► Do not operate the CP TD1 in the presence of explosives, gas or vapors.
► Opening the CP TD1 invalidates all warranty claims.
► Do not use an extension cable on a cable reel to prevent an overheating of the cord; run out the
extension cord.
►If the CP TD1 does not seem to function properly, do not use it anymore. Please call the OMICRON
technical support.
1.4 Handling cables
► Always turn off the CP TD1 completely before you connect or disconnect any cable (disconnect the
CPC 100 from mains or press its Emergency Stop button).
► The high-voltage cable must always be well attached and tightly connected to both the CP TD1 and
the test object. A loose or even falling off connector at the test object carrying high-voltage is life-
hazardous. Make sure the connectors are clean and dry before connecting.
At the CP TD1, press the high-voltage cable’s plug to the connector tightly and turn the screw cap
until you feel a mechanical stop. If you notice a rough-running of the screw-cap, clean the screw
thread and use a lubricant (Vaseline recommended).
At the test object, insert the high-voltage cables’ plugs carefully until you feel a "click" position. Now
they are locked. Confirm this by trying to pull them out. This should not be possible now.
Note: Tighten the plugs manually. Do not use any tools for that because that can damage the plugs
or connectors.
Insert the yellow banana plug (the high-voltage cable’s grounding) into the respective plug socket.
► Do not connect any cable to the test object without a visible grounding of the test object.
► The high-voltage cable is double-shielded and therefore safe. However, the last 50cm (20 inch) of
this cable have no shield. Therefore, during a test consider this cable a life wire and due to the high-
voltage life-hazardous!
► When the CPC 100 is switched on, consider this part of the cable has to be in the high-voltage area
due to a hazard of electric shock!
► Never remove any cables from the CP TD1 or the test object during a test.
► Keep clear from zones in which high voltages may occur. Set up a barrier or establish similar
adequate means.
► Both low-voltage measuring cables must always be well attached and tightly connected to the
CP TD1’s measuring inputs IN A and IN B.
Make sure to insert the red and blue marked cables into the corresponding measuring inputs: IN A =
red, IN B = blue.
Tighten the plugs by turning them until you feel a stop.
Note: Tighten the plugs manually. Do not use any tools for that because that can damage the plugs
or connectors.
► Do not use any other cables than the ones supplied by OMICRON.

CP TD1 User Manual
10 OMICRON
1.5 Orderly measures
The CP TD1 User Manual or alternatively the e-book in PDF format has always to be available on site
where the CP TD1 is being used. It must be read and observed by all users of the CP TD1.
The CP TD1 may be used only as described in this User Manual. Any other use is not in accordance
with the regulations.
The manufacturer and/or distributor is not liable for damage resulting from improper usage. The user
alone assumes all responsibility and risk.
Following the instructions provided in this User Manual is also considered part of being in accordance
with the regulations.
Opening CP TD1 or its accessories invalidates all warranty claims.
1.6 Static charges
Static charges on bushings or other apparatus such as transformer windings may be induced by test
potentials. While the voltage may not be significant enough to do any damage to the equipment, it can
be a source for serious accidents due to falls caused by reflex action.
High static charges may also be encountered at the bushing capacitance taps if the covers are removed.
► Use safety grounds before handling.
Always observe the five safety rules!
1.7 Disclaimer
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the
equipment may be impaired.

OMICRON 11
Safety instructions
1.8 Compliance statement
Declaration of conformity (EU)
The equipment adheres to the guidelines of the council of the European Community for meeting the
requirements of the member states regarding the electromagnetic compatibility (EMC) directive, the low
voltage directive (LVD) and the RoHS directive.
FCC compliance (USA)
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
Changes or modifications not expressly approved by the party responsible for compliance could void the
user's authority to operate the equipment.
Declaration of compliance (Canada)
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
1.9 Recycling
This test set (including all accessories) is not intended for household use. At
the end of its service life, do not dispose of the test set with household waste!
For customers in EU countries (incl. European Economic Area)
OMICRON test sets are subject to the EU Waste Electrical and Electronic
Equipment Directive 2012/19/EU (WEEE directive). As part of our legal obligations
under this legislation, OMICRON offers to take back the test set and ensure that it is
disposed of by authorized recycling agents.
For customers outside the European Economic Area
Please contact the authorities in charge for the relevant environmental regulations in
your country and dispose the OMICRON test set only in accordance with your local
legal requirements.

CP TD1 User Manual
12 OMICRON
2 Introduction
2.1 Designated use
The CP TD1 works as an add-on device to the CPC 100, CPC 80 or TESTRANO 600 which controls the
measurement. In this manual, those devices are collectively named Control Device if no specific device
is referred to. Do not connect the CP TD1 to any other Control Device than the CPC 100, CPC 80 or the
TESTRANO 600.
The CP TD1 is an optionally available high-precision test system for on-site insulation tests of high-
voltage systems like power and measuring transformers, circuit breakers, capacitors and isolators. With
the add-on device CP TD1, the Control Device increases its range of possible applications into high-
voltage measurements.
The internal switched mode power amplifier enables measuring at different frequencies without
interferences with the mains frequency. Automatic test procedures reduce the testing time to a minimum.
Test reports are generated automatically.
When used with the CPC 100 or CPC 80, the CP TD1 comes with its own CPC test card named
TanDelta (Tangent Delta), which provides highly accurate measurements of the capacitance Cx and the
dissipation factor tanδ (DF) or power factor cosϕ (PF), respectively.
Additionally, the CP TD1 measures the following quantities:
• Actual, apparent and reactive power
• Quality factor QF
• Inductance
• Impedance, phase angle
• Test voltage & current
The CP TD1 can also be used as high-voltage source.
Any other use of the CP TD1 but the one mentioned above is considered improper use, and will not only
invalidate all customer warranty claims but also exempt the manufacturer from its liability to recourse.
2.2 Functional components of the Control Devices and
the CP TD1
On the following pages the functional components of the different Control Devices (CPC 100, CPC 80
and TESTRANO 600) and the CP TD1 as well as the trolley options for the different device combinations
are described.

OMICRON 13
Introduction
2.3 CPC 100 and CP TD1 equipment trolley
High-voltage
output with
attached
screw plug
and yellow
grounding
plug.
Cable drum with
double-shielded
output cable to feed
the high voltage to the
test object.
Equipment trolley
Booster cable CPC 100 ⇔CP TD1
(short type). Via this cable CPC 100
controls the CP TD1 output voltage.
CPC 100
CPC 100, CP TD1 and the equipment
trolley connected to the trolley’s
grounding bar and led to earth.
Grounding cable min. 6mm².
CP TD1
Grounding terminal
Data cable CPC 100 ⇔ CP TD1
(short type). Via this data cable, the
CPC 100 software (test card
TanDelta) controls the CP TD1.
CP TD1’s measuring inputs IN A and
IN B, connected to the cable drum for
the measuring cables.
Swiveling mounting brackets for the
CPC 100 (top) and CP TD1 (bottom).
To secure the CPC 100 while pulling
the trolley, a safety belt is available
(not shown).
Cable drum for
measuring
cables

CP TD1 User Manual
14 OMICRON
2.4 Functional components of the CPC 100
2.4.1 CPC 100 Front panel
Figure 2-1: CPC 100 Front panel
Note: With the CPC 100 V0, the number of test cards in one test procedure should be limited to 15 to
avoid memory problems. The CPC 100 V1 allows using more test cards in one test procedure but we
recommend not to use more than 15 test cards or more than 50 test results to keep the tests clearly
structured.
Soft-touch
keyboard
Built-in ePC
Built-in ePC with front-panel control
We recommend not to use more than 15 test cards
or 50 test results in one test procedure
(see Note below).
I / 0
Warning lights that indicate either a safe operation,
that is, no voltage at the CPC 100 outputs (green
light "0" on), or an operation with possibly
hazardous voltage and/or current levels at the
CPC 100 outputs (red light "I" flashing).
Safety
key lock
Emergency
stop button
Navigation
elements
DC OUTPUT
6A DC output
Test
Start/Stop
BIN IN
Binary trigger input
INPUT
Measuring inputs
AC OUTPUT
Fuse-protected 6A or 130V output
Fuses for 6A AC and 6A DC
outputs

OMICRON 15
Introduction
2.4.2 CPC 100 High-voltage and High-current outputs
When the CPC 100 outputs high current, observe the allowed duty cycles that may apply to the selected
AC output range. For more information please refer to ”CPC 100 outputs” on page 14-288.
Figure 2-2: High-voltage and high-current outputs on left-hand side of the CPC 100
DANGER
Death or severe injury caused by high voltage or current
The connector "Ext. Booster" is always galvanically connected to mains, regardless
whether or not an external booster is selected on the software tab Options | Device
Setup, the green warning light (0) is on, the outputs are turned off or the Emergency Stop
button is pressed.
► Do not use any other booster cables than the ones supplied by OMICRON.
► Do not use booster cables that are frayed or damaged in any way
► Handle with extreme caution.
POWER ON /OFF
switch
Mains power supply,
1 phase, 85V-264V AC
2kV AC
High-voltage
output
Ext. Booster
for example, to
power the CP TD1
Automatic circuit
breaker I > 16A
Reference point
400A DC
(4-4.5V DC)
High DC current output
Grounding
terminal
800A AC
(6.1-6.5V AC)
High AC current
output

CP TD1 User Manual
16 OMICRON
2.4.3 CPC 100 ePC interfaces
The ePC interfaces are located on the right-hand side of the CPC 100 housing. The PC and network
interfaces differ depending on the CPC 100 version as described below.
Figure 2-3: ePC interfaces of the CPC 100 V1
The CPC 100 V1 supports the USB interface 1.1 and 2.0 for connecting the USB memory stick shipped
with the CPC 100.
Note: The full functionality is guaranteed only for the stick delivered with the CPC 100.
The serial and safety interfaces are identical with the CPC 100 V0 version (see above). The network
interface is an auto-crossover Ethernet connector that can be connected to a network hub or directly to
a PC or a notebook.
The CPC 100 V1 provides the following LEDs on the ePC interface:
• Green LED lights if the CPC 100 is properly connected to a PC or network.
• Yellow LED lights if data is transferred from or to the network.
• Red LED serves for diagnosis purposes.
USB connector for connecting
OMICRON USB memory sticks
(see below)
RJ-45 socket for connecting the
CPC 100 to a PC or a network hub
Serial interface connector for
connecting the CP TD1
Connector for external safety
functions
Red LED
Yellow LED
Green LED

OMICRON 17
Introduction
2.5 Functional components of the CPC 80
2.5.1 CPC 80 front panel
Figure 2-4: CPC 80 front view
Soft-touch
keyboard
Safety
key lock
Emergency
stop button
Navigation
elements
Test
Start/Stop
Built-in ePC
Built-in ePC with front-panel control
We recommend not to use 50 test results in one
test procedure
(see Note below).
I / 0
Warning lights that indicate either a safe operation,
that is, no voltage at the CPC 80 outputs (green
light "0" on), or an operation with possibly
hazardous voltage and/or current levels at the
CPC 80 outputs (red light "I" flashing).

CP TD1 User Manual
18 OMICRON
2.5.2 CPC 80 mains power supply and Booster output
Figure 2-5: Mains power supply, booster output and grounding terminal
Mains power switchMains power supply
Ext. Booster
for example, to
power the CP TD1
Grounding
terminal
Automatic circuit
breaker

OMICRON 19
Introduction
2.5.3 CPC 80 ePC Interfaces
The ePC interfaces are located on the right-hand side of the CPC 80 housing.
Figure 2-6: ePC interfaces of the CPC 80
The CPC 80 supports the USB interface 1.1 and 2.0 for connecting the USB memory stick shipped with
the CPC 80.
The full functionality is guaranteed only for the stick delivered with the CPC 80.
The network interface is an auto-crossover Ethernet connector that can be connected to a network hub
or directly to a PC or a notebook.
The CPC 80 provides the following LEDs on the ePC interface:
• Green LED lights if the CPC 80 is properly connected to a PC or network.
• Yellow LED lights if data is transferred from or to the network.
• Red LED serves for diagnosis purposes.
The connector for external safety functions allows connecting:
• an external Emergency Stop or "dead man" button
• an external "test start / stop" push-button
• external I / O warning lights.
The attached plug contains a jumper for the emergency stop or "dead man" function, and as long as the
plug is placed on the connector, these functions are bridged. If the plug is removed, emergency stop is
active.
Serial interface connector for
connecting the CP TD1 Connector for external safety
functions (see below)
Red LED
Yellow LED
Green LED
USB connector for connecting
OMICRON USB memory sticks
(see below)
RJ-45 socket for connecting the
CPC 80 to a PC or a network hub

CP TD1 User Manual
20 OMICRON
2.6 TESTRANO 600 and CP TD1 equipment trolley
Grounding terminal
Swiveling mounting brackets for TESTRANO 600
(top) and CP TD1 (bottom).
To secure TESTRANO 600 while pulling the
trolley, a safety belt is available (not shown).
Data cable TESTRANO 600 ⇔ CP TD1 (short
type). Via this data cable, the TESTRANO 600
software controls the CP TD1.
CP TD1’s measuring inputs IN A and IN B,
connected to the cable drum for the measuring
cables.
Equipment trolley
Booster cable TESTRANO 600 ⇔CP TD1.
Via this cable TESTRANO 600 controls the
CP TD1 output voltage.
TESTRANO 600
CP TD1
TESTRANO 600, CP TD1 and the equipment
trolley connected to the trolley’s grounding bar
and led to earth.
Grounding cable min. 6mm².
Cable drum with double-
shielded output cable to
feed the high voltage to
the test object.
High-voltage
output.
Cable drum for
measuring
cables
Other manuals for CP TD1
1
Table of contents
Other Omicron Measuring Instrument manuals

Omicron
Omicron CMC 156 User manual

Omicron
Omicron Tip Etching Kit User manual

Omicron
Omicron CT Analyzer User manual

Omicron
Omicron Bode 100 User manual

Omicron
Omicron CT SB2 User manual

Omicron
Omicron Bode 100 User manual

Omicron
Omicron Bode 100 User manual

Omicron
Omicron DANEO 400 User manual

Omicron
Omicron COMPANO 100 Installation and operating instructions

Omicron
Omicron C-Probe 1 User manual