OmniMetrix TrueGuard-PRO IM-735 User manual

TrueGuard-PRO™Generac E Panel/E Panel with Relay
Installation Guide
1. Unpack the monitor, antenna and the data/power cable. The 25
pin connector plugs onto the front of the OmniMetrix®monitor.
This cable includes wires to power the monitor as well as wires for
alarm inputs, relay outputs and analog inputs. Take a moment to
inspect all components to verify there is no shipping damage.
2. Locate the area behind the door where two panels come together
in the housing. Peel the weather stripping down and route the
antenna between the weather stripping and the housing. Place
the wire for the antenna in the slot between the two panels and
replace the weather stripping. Attach the antenna vertically to the
top of the enclosure. The antenna used for transmitting must be
installed to provide a separation distance of at least 20 cm from all
persons and must not transmit simultaneously with any other
antenna transmitters. BE SURE to provide a drip loop lower than
the monitor to keep water from running down the antenna cable
into the monitor connection
3. Program the unit according the Programming Instructions on the
following page.
4. Route the data/power cable to the interior of the generator control
housing on the right-hand side.
5. The monitor connects to the Generac E Panel using the wiring
definitions as shown in Table 1 (next page); and to the Relay Kit
as shown in Table 2.
6. Temporarily mount the monitor to the side of the control and
attach the 25 pin cable to the front of the monitor and tighten
screws. Attach the antenna cable to the front of the monitor, and
tighten thumb tight.
7. Turn on the monitor and confirm that the LEDs light up and blink.
If not, check for power on the terminal strip. If, after 5 minutes, the
only LED lit is the Power LED, check the antenna mount and
cable connection.
8. Allow 15 minutes for the monitor to log into the network and then
call OmniMetrix Tech Support at 770-209-0012 to confirm
installation. Access to machine data is through the OmniView®
web interface at www.omnimetrix.net. Contact OmniMetrix for
login instructions and web training.
9. Reassemble the controller and attach the monitor, via the
magnetic feet, to the top of the control panel or other appropriate
location. Horizontal surfaces are best, but the unit may be
mounted vertically or even upside down if necessary. Note: If
mounted vertically, install the monitor with the cables down to
prevent water from entering the enclosure.
Data/Power Cable
Generac E Panel Controller

Generac E Panel Wiring Instructions
OMN WIRE
FUNCTION
TERMINATION
Red
Power In
TB1 –13/218
Black
Ground
TB1 - 0
Orange
Generator Running
TB1 –14/219
Blue
Common Alarm
TB2 - Relay 1 Normally Open
Violet
Low Fuel
TB2 - Relay 3 Normally Open
Pink
Not in Auto
TB2 - Relay 2 Normally Open
White/Yellow
2-wire start
TB1 - 56
White/Brown
GND for 2-wire start
TB1 - 0
Generac E Panel w/Relay Kit Wiring Instructions
OMNI WIRE
FUNCTION
TERMINATION
Dip Switch
Red
Power In
TB1 –13/218
Black
Ground
TB1 - 0
Orange
Generator Running
Relay Kit 6 Normally Closed
S2 –4 ON
Blue
Common Alarm
TB2 –Relay 1 Normally Open
Yellow
Overcrank
Relay Kit 1 Normally Closed
S1-2 ON
Brown
Overspeed
Relay Kit 2 Normally Closed
S1-3 ON
Violet
Low Fuel
Relay Kit 5 Normally Closed
S1-10 ON
Gray
High Coolant Temp
Relay Kit 4 –Normally Closed
S1-5 ON
Pink
Not In Auto
TB2 –Relay 2 Normally Open
Tan
Oil Pressure Low
Relay Kit 3 Normally Closed
S1-4 ON
White/Yellow
2-Wire Start
TB1 -56
White/Brown
Ground for 2-Wire Start
TB1 - 0
Table 2 –E Panel w/Relay Kit Wiring Table
Table 1 –E Panel Wiring Table

4295 Hamilton Mill Road, Suite 100 ▪ Buford, GA 30518
www.omnimetrix.net ▪ 770-209-0012
IM-735 Rev E
June 2016
E Panel Programming Instructions
Programmable Relays:
1. Press the left or right arrow key until the display reads ‘Parameter Entry’, and press ENTER.
2. Enter your password and press ENTER. The password comes from the factory set to 000000. If this
does not work, call OmniMetrix at 770-209-0012 for a workaround.
3. Use the left and right arrow keys to find the ‘Digital I/O Menu’.
4. Use the up and down arrow keys to locate ‘Output 1 Function’. The bottom line of the display will
read the current setting. Press ENTER.
5. Use the up and down arrow keys to scroll through the list until ‘Common Alarm’ is displayed in the
bottom line. Press ENTER.
6. User Output #1 is now programmed to become active (relay energized) on any Common Alarm.
7. Press RESET. This exits the programming mode and returns back to the parameter entry screen.
8. Repeat for User Output #2: Not in Auto.
9. Repeat for User Output #3: Low Fuel.
Relay 1: Common Alarm (Blue Wire) Normally Open, located on TB2 (Program Relay #1).
Relay 2: Not in Auto (Pink Wire) Normally Open, located on TB2 (Program Relay #2).
Relay 3: Low Fuel (Violet Wire) Normally Open, located on TB2 (Program Relay #3).
If Low Fuel is not applicable:
Relay 3: Low Oil Pressure (Tan Wire) Normally Open, located on TB2 (Program Relay #3).
All jumpered to ground.
Generac E Panel Relay Board
If you have any questions, please call OmniMetrix Tech Support at 770-209-0012 or email at
techsupport@omnimetrix.net.