Omron S8V-CP Series User manual

1
DC Electronic Circuit Protector (24 VDC 4 Outputs/8 Outputs Type)
S8V-CP
Simplified safety design of DC circuits
Reliable DC circuit protection in the
event of short circuits or overcurrent
Saves space even with multi-channels
Sequential start-up of outputs
to avoid start-up trouble
• Push-in plus terminal block adopted
• Push button with indicator to help you understand
each output status at a glance
• Switch lets you set the rated output current appropriately
for each output depending on load
• Lineup of a UL Class 2 output-compatible model
Model Number Structure
Model Number Legend Not all combinations are possible. Refer to List of Models in Ordering Information, below.
(1) Number of Outputs
(2) Rated input voltage
(3) UL Class 2 output
List of Models
Unit
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
Refer to Safety Precautions on page 10.
S8V-CP @@ 24 @
Series name
(2) (3)(1)
Code Number of Outputs
04 4 outputs
08 8 outputs
Code Rated input voltage
24 24 VDC
Code UL Class 2 output certified
SYes
No No
Number of Outputs UL Class 2 output Model
4 outputs No S8V-CP0424
Yes S8V-CP0424S
8 outputs No S8V-CP0824

S8V-CP
2
Ratings, Characteristics, and Functions
*1. For power input terminals, use 35 A max. per pole.
*2. A voltage drop will occur in the S8V-CP. Consider the voltage drop at the output.
*3. When selecting the power supply, be sure to include the power consumption of the S8V-CP and not just the power consumption of the load.
*4. Outputs start in order from +VO1 to +VO8. +VO1 starts after the initialization time. Start-up delay time of each output is automatically decided
depending on the load. If the start-up delay time is over 5 s, the next output is forcibly started.
*5. Refer to Tripping Functions on page 3 for details.
*6. Refer to Current Tripping Characteristics and Current and Voltage Tripping Characteristics on page 7 for details.
*7. MTBF is calculated according to JEITA RCR-9102.
*8. Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 14 for details.
*9. UL Class 2 output applies for the S8V-CP0424S model only.
Model S8V-CP0424 S8V-CP0424S S8V-CP0824
Number of Outputs 448
Item UL Class 2 output No Yes No
I/O
characteristics
Rated input voltage
(Input voltage allowable range)
24 VDC
(20 to 30 VDC)
24 VDC
(20 to 28.8 VDC)
24 VDC
(20 to 30 VDC)
Allowable input current *140 A 15.2 A 70 A
Max. rated output current (per output) 10 A 3.8 A 10 A
Internal voltage drop *2180 mV typ. 180 mV typ. 200 mV typ.
Output leakage current 10 mA max.
Power
consumption
(at input voltage
24 VDC) *3
When all outputs are
connected 8 W typ. (at 10 A x 4 CH) 4 W typ. (at 3.8 A x 4 CH) 15 W typ. (at 10 A x 7 CH)
When all outputs are
tripped 0.7 W typ. 0.8 W typ. 1.1 W typ.
Start-up time *4Initialization time 250 ms typ.
Start-up delay time 50 ms to 5 s
Functions *5
Current tripping
function *6
Rated output current 2 A, 3 A, 4 A, 6 A,
8 A, 10 A 3.8 A 2 A, 3 A, 4 A, 6 A,
8 A, 10 A
Cutoff current 2.5 A, 3.5 A, 4.5 A, 6.5 A,
8.5 A, 10.5 A 3.8 A 2.5 A, 3.5 A, 4.5 A, 6.5 A,
8.5 A, 10.5 A
Over voltage tripping function *6No Yes No
Push button (ON/OFF/RESET)
with indicator Yes (LED colors: Red/Green/Yellow)
Reset signal input (RST) Yes (High level: 20 to 30 VDC, Low level: 0 to 5 VDC)
Alarm signal output (ALM1/ALM2) Yes (MOS FET relay output 30 VDC max., 50 mA max.)
Insulation Dielectric strength 1.0 kVAC for 1 min (between all terminals and DIN rail mounting parts), current cutoff 20 mA
Insulation resistance 100 MΩmin. (between all terminals and DIN rail mounting parts) at 500 VDC
Environment
Ambient operating temperature -25 to 70°C (Derating is required according to the temperature.) (with no condensation or icing)
Storage temperature -40 to 85°C (with no condensation or icing)
Ambient operating humidity 5% to 96% (storage humidity: 5% to 96%)
Vibration resistance 10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions
Shock resistance 294 m/s2, 3 times each in ±X, ±Y, ±Z directions
Reliability MTBF *7135,000 hrs typ. 60,000 hrs typ. 60,000 hrs typ.
Life expectancy *810 years min.
Construction
Weight 160 g max. 170 g max. 420 g max.
Cooling fan No
Degree of protection IP20 by IEC60529
Standards
EMI Conforms to EN 61000-6-3
EMS Conforms to EN 61000-6-2
Safety standards
UL 508 (CSA22.2 No.14-10) Listing Pol2
UL 2367 Recognition (Max. 100W per output, per Class 2 limitations) Pol2 *9
CE (EN 61000-6-2, EN 61000-6-3)

S8V-CP
3
Tripping Functions
Current tripping
If the output current of each output exceeds the current tripping, the output is tripped by a semiconductor switch (MOS FET) in accordance with
the current tripping characteristic.
Over voltage tripping
With the S8V-CP0424S, if the input voltage exceeds 28.8 V, all outputs are tripped by a semiconductor switch (MOS FET).
If the input voltage becomes 28.8 V or less, all outputs automatically return to the previous state.
Reset Signal Input (RST)
Turning ON all outputs during in the Current tripping (enable to reset) state is called reset. All output terminals can be reset by an external input.
As shown in the following figure, input a high level signal of 0.5 s or more and reset.
Input voltage: 30 VDC max.
Input impedance: 22 kΩ
Note: 1. When Reset signal input terminal is used, a miss operation of reset may occur by a noise coming from the cable. Do not make an instable
potential of Reset signal input terminal.
Alarm Signal Output (ALM1/ALM2)
If any of the output is tripped, the MOS FET relay is turned OFF. The signal output comprises of MOS FET relays and therefore, does not have
polarity.
Input voltage: 30 VDC max., Input current: 50 mA max.
Residual voltage when ON: 2 V max.
Leakage current when OFF: 0.1 mA max.
Note: 1. Alarm signal output is not equipped with an internal current limiting circuit, so be sure that the current flowing to the alarm signal output
terminals does not exceed 50 mA.
2. Be sure to check that the Alarm signal outputs are working normally after wiring.
Output Status
The status of each output can be identified by the indicator or alarm signal output.
The status of each output is saved when the power is turned OFF. When the power is turned ON again, the status transits to that saved after
initialization.
All outputs are set to Output ON state by default.
*1. Each output transits automatically to Current tripping (disable to reset) state according to the Current tripping characteristics.
*2. The status remains on Current tripping (disable to reset) state during 500 ms to 20 s in order to protect the internal parts from heat.
After that, the status automatically transits to Current tripping (enable to reset) state.
*3. S8V-CP0424S only
*4. If an internal fuse blows, or an internal memory error occurs, the output will be disconnected.
*5. Always remove the cause of the output first and then reset the alarm when abnormal tripping operates.
Indicator Alarm Signal
Output Output Status Name Status Transition
by Push Button
Status Transition
by Reset Signal Input
Color Status
--- OFF OFF OFF Initialization --- ---
Green ON ON ON Output ON Manually output OFF ---
Yellow ON ON ON Over current *1 Manually output OFF ---
Red ON OFF OFF Manually output OFF Output ON ---
Red Blinking OFF OFF Current tripping (Disable to reset) *2 --- ---
Yellow Blinking OFF OFF Current tripping (Enable to reset) Manually output OFF
Output ON
(transition due to positive
pulse longer than 0.5 s)
*5
Red Blinking fast OFF OFF Over voltage tripping *3
Internal error detection *4--- ---
Reset (Connect)
0.5 s min.
High level
External input Low level: 0 to 5 VDC
High level: 20 to 30 VDC
S8V-CP
RST
22kΩ
-VI2
-VI1

S8V-CP
4
Connections
Block Diagrams
FUSE 15A
CONTROL CIRCUIT
INPUT
OUTPUT
SIGNAL
OUTPUT
SIGNAL
INPUT
MOS FET RELAY
MOS FET
ALM2
ALM1
RST
+VO4
+VO3
+VO2
+VO1
-VI2
-VI1
+VI2
+VI1
S8V-CP0424
CONTROL CIRCUIT
INPUT
SIGNAL
INPUT
OUTPUT
SIGNAL
OUTPUT
MOS FET RELAY
MOS FET
ALM2
ALM1
RST
+VO4
+VO3
+VO2
+VO1
-VI2
-VI1
+VI2
+VI1
S8V-CP0424S
FUSE 15A
OUTPUT
INPUT
CONTROL CIRCUIT SIGNAL
OUTPUT
SIGNAL
INPUT
MOS FET RELAY
+VO1
+VI2
+VI1
+VO2
+VO3
+VO4
+VO5
+VO6
+VO7
+VO8
-VI1
-VI2
RST
ALM2
ALM1
MOS FET
S8V-CP0824

S8V-CP
5
Connection Example
Note: 1. Wire so that the load current does not flow into -VI1 or -VI2.
2. Follow the figures below for wiring Reset signal input terminal.
POWER SUPPLY
LOAD
RESETSIGNAL
POWER LINE/LOAD LINE
SIGNAL LINE
INDICATOR
COMMON TERMINALBLOCK
S8V-CP
RST
+VDC
-VDC
+
ALM1
ALM2
L
N
PE
+VO1
+VO2
+VO3
+VO4
+VI1
+VI2
-VI1
-VI2
S8V-CP S8V-CPS8V-CP
RST
-VI2
RST
-VI2
RST
-VI2

S8V-CP
6
Construction and Nomenclature
Nomenclature
*1. Use a flathead screwdriver to change position of the switch.
*2. Do not connect the load wire to the Negative input terminal.
*3. +VO5 to +VO8 are only in the S8V-CP0824.
No. Terminal name Name Function
1---
Push button (ON/OFF/RESET)
with indicator
The indicator shows the connected/tripped status of each output.
The push button switch is used to switch between the connected/tripped status
of each output.
2---
Rated output current selector
switch Changes the rated output current of each output with the rotary switch. *1
3INPUT +VI1 Power input terminals Connects to the positive side of the power unit output.
4+VI2
5
SIGNAL
INPUT
-VI1 Negative input terminal Connects to the negative side of the power unit output.
This terminal is only used as a ground for the internal circuitry of the product. *2
6-VI2
7 RST Reset signal input terminal Resets all outputs by the external input. (Switches to the connected state.)
8SIGNAL
OUTPUT
ALM1 Alarm output terminal Turns OFF the MOS FET relay If any of the outputs trip due to over voltage or
current.
9ALM2
10
OUTPUT
+VO1
Output terminal *3 Connects the positive side of the load line.
11 +VO2
12 +VO3
13 +VO4
14 +VO5
15 +VO6
16 +VO7
17 +VO8
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
4 outputs type
S8V-CP0424
8 outputs type
S8V-CP0824
(1)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
S8V-CP0424S

S8V-CP
7
Engineering Data
Derating Curves
Current Tripping Characteristics
S8V-CP0424, S8V-CP0824
Note: If the power rating of the power supply unit is insufficient, the overcurrent protection characteristic can cause a voltage drop in all the outputs.
In order to trip the current according to the above characteristic, select a power supply unit with a current higher than the total tripping current
considering the power consumption of the S8V-CP.
Current and Voltage Tripping Characteristics
S8V-CP0424S
Note: 1. Input voltage 24 to 28.8 VDC tripping current is decreased to less than 3.2 A in accordance with the current and voltage tripping
characteristic.
2. Current tripping takes place between 250 ms to 5 s.
S8V-CP0424 S8V-CP0424S S8V-CP0824
-10-20-30 0 10 20 30 40 50 60 70 80
50
40
30
20
10
0
35
25
Ambient operating temperature (°C)
Total current (A)
-10-20-30 0 10 20 30 40 50 60 70 80
20
15
10
5
0
Ambient operating temperature (°C)
Total current (A)
-10-20-30 0 10 20 30 40 50 60 70 80
80
60
40
20
0
50
Ambient operating temperature (°C)
Total current (A)
100s
10 s
1 s
2 s
100 ms
10 ms
16 ms
11023456789 20 30
2A 3A 4A 6A 8A 10A
Output current (A)
Rated Output Current
Tripping time
Tripping region
3.8
3.2
2420 28.8
Tripping region
Input voltage (V)
Output current (A)
Power < 100 W

S8V-CP
8
Dimensions (Unit: mm)
Unit
5.1
90 ±1
94.8±1
90.8
34.3
18.7
24
5
5
5
9
7.5
2
44.8±1
11.9
(1.1)
(10.4 max. when sliding)
(3.5)
Rail stopper
S8V-CP0424
(1.1)
94.8±1
90.8 9
44.8±1
11.9
5.1
(10.4 max. when sliding)
90 ±1
34.3
18.7
24
5
5
5
7.5
2
(3.5)
Rail stopper
S8V-CP0424S
(1.6)
4
(6.7 max. when sliding)
122.5±1
118.1
17.4
35.4
50.9
40.6
5
5
5
8.1
42±1
127±1
11
(10)
7.5
112.5
Rail stopper
S8V-CP0824

S8V-CP
9
DIN Rail Mounting (Order Separately)
Note: If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from
aluminum abrasion.
Mounting Rail (Material: Aluminum)
PFP-100N
PFP-50N
4.5
15 25 25
10 10
1,000 (500) *
25 25 15 (5) *
35
±0.3
7.3
±0.15
27
±0.15
1
* ( ) indicates the dimensions
of the PFP-50N.
Mounting Rail (Material: Aluminum)
PFP-100N2
4.5
15 25 25
10 10
1,000
25 25 15 1 1.5
29.2242735±0.3
16
1.3
4.8
35.5 35.5
1.8
1.8
M4 spring
washer
10
6.2
1
50
M4×8
pan-head
screw
11.5
10
End Plate
PFP-M

S8V-CP
10
Safety Precautions
Be sure to read the precautions for all models in the website at: http://www.ia.omron.com/.
Warning Indications
Meaning of Product Safety Symbols
If a wire is disconnected, electric shock may result.
Insert the solid wire or ferrule straight into the
terminal block until the end touches the terminal
block.
Minor burns may occasionally occur. Do not touch
the Product while power is being supplied or
immediately after power is turned OFF.
Minor electric shock, fire, or Product failure may
occasionally occur. Do not allow any pieces of metal,
conductors, or cuttings from installation work to
enter the Product.
The Product will be damaged. Do not incorrectly
connect the polarity of power input terminals.
Fire, or Product failure may occasionally occur.
Do not apply voltages that exceed the input voltage
allowable range.
Unexpected output may occasionally occur.
Be careful sufficiently not to accidentally press the
push button with indicator during Manually output
OFF state.
Indicates a potentially hazardous situation
which, if not avoided, may result in minor or
moderate injury or in property damage.
Precautions
for Safe Use
Supplementary comments on what to do or
avoid doing, to use the product safely.
Precautions
for Correct Use
Supplementary comments on what to do or
avoid doing, to prevent failure to operate,
malfunction or undesirable effect on product
performance.
Caution against electric shock
Used to warn of the risk of electric shock under
specific conditions.
Caution against high temperatures
Used to warn of the risk of minor injury caused by
high temperatures.
General instructions
Used for general mandatory action precautions for
which there is no specified symbol.
CAUTION
CAUTION

S8V-CP
11
Ambient Operating and Storage Environments
• Store the Product at a temperature of −25 to 85°C and a humidity
of 5 to 96%.
• The internal parts may occasionally deteriorate or be damaged. Do
not use the Product in areas outside the derating curves.
• Use the Product at a humidity between 5 to 96%.
• Do not use the Product in locations subject to direct sunlight.
• Do not use locations where liquids, foreign matter, or corrosive
gases may enter the interior of the Product.
• If the Product has been accidentally dropped, do not use it as its
internal parts may be damaged.
• Minor electric shock, fire, or Product failure may occasionally
occur. Do not disassemble, modify, or repair the Product or touch
interior of the Product.
Installation Environment
• Do not use the Product in locations subject to shocks or vibrations.
In particular, install the product as far away as possible from
contactors or other devices that are a vibration source. Be sure to
mount End Plates (PFP-M) on both ends of the Product.
• Install the Product well away from any sources of strong, high-
frequency noise and surge.
Mounting
• Take adequate measures to ensure proper heat dissipation to
increase the long-term reliability of the Product. Mount the Product
so that air convection will occur around it. Use it in areas within the
derating curves (see Derating Curves on page 7).
• The internal parts may occasionally deteriorate and be broken due
to adverse heat radiation.
Do not loosen the screws on the Product.
• Mount as shown below.
• Only products of the same model can be combined and used if the
horizontal separation is less than 15 mm.
Wiring
• The property damage may occasionally occur due to fire If the
insertion distance is not sufficient. When wiring, insert the wiring
material securely all the way in.
• Minor fire may possibly occur. Ensure that input and output
terminals are wired correctly.
• Do not apply more than 40 N force to the terminal block when
inserting wiring or inserting a flat-blade screwdriver into the release
hole.
• Do not wire anything to the release holes.
• Do not tilt or twist a flat-blade screwdriver while it is inserted into a
release hole on the terminal block. The terminal block may be
damaged.
• Insert a flat-blade screwdriver into the release holes at an angle.
The terminal block may be damaged if you insert the screwdriver
straight in.
• Do not allow the flat-blade screwdriver to fall out while it is inserted
into a release hole.
• Do not bend a wire past its natural bending radius or pull on it with
excessive force. Doing so may cause the wire to break.
• Do not insert more than one wire into each terminal insertion hole.
• Do not pre-solder the ends of the wires. Doing so will inhibit proper
connection.
• If there is a possibility that the Unit will be subject to vibration or
shock, use Wires with Ferrules or Stranded Wires.
• Be sure to remove the sheet covering the product before Turn ON
so that it does not interfere with heat dissipation.
• To prevent wiring materials from smoking or ignition, confirm wire
ratings and use the wiring materials given in the following table.
Recommended Wire
• Use copper stranded wire or solid wire.
• Do not use the solid wire to the power input terminal.
• Use min. 75°C wire.
• Input crossover wiring can be used for the input side of the Product.
If you use crossover wiring for N number of the Products, a current
that is N times the current for a standalone the Unit may flow to the
input terminals. Take this into consideration when you select
wiring materials.
• Make sure that the current of the power input terminal does not
exceed 35A per pole.
• When connecting to the two poles of the power input terminals, be
sure that the length and thickness of wires are the same to allow
for well balanced current flows.
Precautions for Safe Use
*2
*2
*1*1*1
*1*1*1
*1. Direction of air circulation
*2. Space above and below
the Product: 25 mm min.
(S8V-CP0424@)
Space above and below
the Product: 20 mm min.
(S8V-CP0824)
Terminal Recommended wire gauge
(mm2)(AWG)
Power input terminals 0.25 to 6 24 to 10
Output terminals, Negative input
terminal, Reset signal input
terminal, Alarm output terminal
0.25 to 2.5 24 to 14

S8V-CP
12
Stripping length
Applicable to all the terminal blocks
Power input terminal block
Input Voltage
• The S8V-CP0424S provides over voltage tripping function. All
outputs will be tripped if the input voltage exceeds 28.8 VDC.
However, this function does not protect loads and internal parts
from high voltages in all cases.
Use the input voltage within the rated range.
• The S8V-CP0424S may operate the over voltage tripping for loads
that generate reverse peak electromotive force.
• The S8V-CP operates by DC input. Do not connect an AC power
source to the power input terminal.
Input Power Supply Selection
• Depending on the overcurrent protection characteristics of the
power supply connected to the input side can cause the failure of
S8V-CP operating or tripping by voltage drop occasionally.
• If the input power supply starts or stops too slowly, the overcurrent
protection characteristics of the power supply can cause the failure
of S8V-CP operating or tripping by voltage drop occasionally.
Tripping Performance
• Always remove the cause of the output first and then reset the
alarm when current tripping operates.
• When using a load that operates with constant power, the current
may be tripping when the power is turned OFF.
• Do not repeat the tripping and reset operations more than
necessary. Internal parts may possibly deteriorate or be damaged.
• Tripping performance depends on the ambient operating
temperature. Use the Product within the derating curve (see
Derating Curves on page 7).
• Internal parts may possibly deteriorate or be damaged. Do not use
the Product for applications with frequent inrush current or
overloading at the load end.
Dielectric Strength Test
• Always short the all terminals of the Product so that the voltage is
applied at the same time.
• There is no insulation between the power input terminal and the
output terminal. Do not perform dielectric strength tests or other
insulation appraisal testing between inputs and outputs.
Connecting the S8V-CP
It is possible to connect multiple units of this Product as shown below.
Serial connections, such as connecting an S8V-CP to the output
terminal of another S8V-CP, can not be established.
Do not establish a parallel connection with other outputs. Also, do not
establish a parallel connection between the output terminals of two
S8V-CP.
Rated output current selector switch
The rated output current selector switch may possibly become
damaged. Do not apply more than the required force.
Recommended Wire Type Stripping length
(Ferrules not used)
0.25 to 2.5 mm2/AWG 24 to 14 10 mm
Recommended Wire Type Stripping length
(Ferrules not used)
4 to 6 mm2/AWG 12 to 10 15 mm
+V +V
+V
+V
+V
-V
-V-V
POWER SUPPLY
S8V-CP
S8V-CP
+V
S8V-CP
S8V-CP
+V +V
-V-V
+V
-V
POWER SUPPLY
S8V-CP
S8V-CP
S8V-CP
+V
+V +V
-V
-V
+V
+V +V
-V
+V
+V
-V
-V
POWER SUPPLY
POWER SUPPLY

S8V-CP
13
Connecting Backup Devices
Observe the following precautions when using a backup device, such
as one from OMRON's S8T Series.
• When a backup device is connected to the S8V-CP output, backup
current is supplied to the other output through the internal circuit,
and at the same time, internal components may be degraded or
damaged. When you use a backup device together, be sure to
connect it to the power input side of the S8V-CP.
• If you connect the backup device to the S8V-CP input terminal, the
backup time will be shorter than usual due to the consumption of
internal power. Always confirm the backup time when using a
backup device.
DIN rail mounting
S8V-CP0424/S8V-CP0424S
To mount the Product to a DIN rail, pull down the rail stopper until you
hear it clicks open, hook portion (A) of the Product onto the DIN rail,
press the Product in direction (B), and then push up the rail stopper to
lock the Product in place.
S8V-CP0824
To mounting on a DIN Rail, hook portion (A) of the Block onto the rail
and press in the (B) direction.
To dismount the Block, pull down portion (C) with a flat-blade
screwdriver and pull out the Block.
Connecting Wires to the Push-In Plus Terminal
Block
Part Names of the Terminal Block
Connecting Wires with Ferrules and Solid Wires
Insert the solid wire or ferrule straight into the terminal block until the
end touches the terminal block.
• If a wire is difficult to connect because it is too thin, use a flat-blade
screwdriver in the same way as when connecting stranded wires.
Connecting Stranded Wires
Use the following procedure to connect the wires to the terminal block.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole. The angle should be between 10° to 15°. If the flat-
blade screwdriver is inserted correctly, you will feel the spring in
the release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
insert the wire into the terminal hole until it strikes the terminal
block. Always twist stranded wires together before inserting them.
3. Remove the flat-blade screwdriver from the release hole.
Checking Connections
• After the insertion, pull gently on the wire to make sure that it will
not come off and the wire is securely fastened to the terminal block
• If you use the recommended ferrule, part of the conductor may be
visible after the ferrule is inserted into the terminal block, but the
Product insulation distance will still be satisfied.
Removing Wires from the Push-In Plus Terminal
Block
Use the following procedure to remove wires from the terminal block.
The same method is used to remove stranded wires, solid wires, and
ferrules.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
remove the wire from the terminal insertion hole.
3. Remove the flat-blade screwdriver from the release hole.
Precautions for Correct Use
(B)
(A)
Rail stopper
(C)
Release hole
Terminal (Insertion) hole
Ferrules and
solid wires
Release hole
Terminal (Insertion) hole
Flat-blade screwdriver
10° to 15°
23
1
Top View
Flat-blade screwdriver
10° to 15°
2
3
1
Top View

S8V-CP
14
Recommended Ferrules and Crimping Tools
Recommended Ferrules
Applicable to all the terminal blocks
Note: 1. Make sure that the outer diameter of the wire is smaller than
the inner diameter of the insulating sleeve of the
recommended ferrule.
2. Make sure that the ferrule processing dimensions conform
to the following figure.
Power input terminal block
Note: 1. Make sure that the outer diameter of the wire is smaller than
the inner diameter of the insulating sleeve of the
recommended ferrule.
2. Make sure that the ferrule processing dimensions conform
to the following figure.
Recommended Flat-blade Screwdriver
Use a flat-blade screwdriver to connect and remove wires. Use the
following flat-blade screwdriver.
The following table shows manufacturers and models as of 2018/Dec.
*SZF 0-0,4X2,5 (manufactured by Phoenix Contact) is available to
order as OMRON's exclusive purchase model (XW4Z-00B).
Recommended Replacement Periods and Periodic Replacement for
Preventive Maintenance
The recommended replacement period for preventive maintenance is greatly influenced by the installation environment of the Power Supply. As
a guideline, the recommended replacement period is 7 to 10 years.*
To prevent failures or accidents that can be caused by using a Power Supply beyond its service live, we recommend that you replace the Power
Supply as early as possible within the recommended replacement period. However, bear in mind that the recommended replacement period is for
reference only and does not guarantee the life of the Power Supply.
Many electronic components are used in the Power Supply and the Power Supply depends on the correct operation of these components to
achieve the original Power Supply functions and performance. However, the influence of the ambient temperature on aluminum electrolytic
capacitors is large, and the service life is reduced by half for each 10°C rise in temperature (Arrhenius law). When the capacity reduction life of the
electrolytic capacitor is reached, the Power Supply failures or accidents may occur. We therefore recommend that you replace the Power Supply
periodically to minimize product failures or accidents in advance.
*The recommended replacement period applies under the following conditions: rated input voltage, load rate of 50% max., ambient temperature
of 40°C max., and the standard mounting method.
This product model is designed with a service life of 10 years minimum under the above conditions.
Applicable
wire
Ferrule
Conduct
or length
(mm)
Stripping
length
(mm)
(Ferrules
used)
Recommended Ferrules
(mm
2
)
(AWG)
Phoenix
Contact
Weid
muller Wago
0.25 24
8 12 AI 0,25-8
H0.25/12
FE-0.25-8N-YE
10 12 AI 0,25-10 --- ---
0.34 22
8 12 AI 0,34-8
H0.34/12
FE-0.34-8N-TQ
10 12 AI 0,34-10 --- ---
0.50 20
8 12 AI 0,5-8 H0.5/14
FE-0.5-8N-WH
10 12 AI 0,5-10 H0.5/16
FE-0.5-10N-WH
0.75 18
8 12 AI 0,75-8
H0.75/14
FE-0.75-8N-GY
10 12 AI 0,75-10
H0.75/16
FE-0.75-10N-GY
1/1.25 18/17
8 12 AI 1-8 H1.0/14
FE-1.0-8N-RD
10 12 AI 1-10 H1.0/16
FE-1.0-10N-RD
1.25/
1.5 17/16
8 12 AI 1,5-8 H1.5/14 FE-1.5-8N-BK
10 12 AI 1,5-10 H1.5/16 FE-1.5-10N-
BK
2.5 14 10 12 AI 2,5-10 H2.5/
16DS
FE-2.5-10N-
BU
Recommended crimp tool
CRIMPFOX6
CRIMPFOX6T-F
CRIMPFOX10S
PZ6 roto Variocrimp4
8to10mm
2.6mmmax. 2.8mmmax.
Applicable
wire
Ferrule
Conduct
or length
(mm)
Stripping
length
(mm)
(Ferrules
used)
Recommended Ferrules
(mm
2
)
(AWG)
Phoenix
Contact
Weid
muller Wago
4 12 12 14 AI 4-12 H4.0/20D
FE-4.0-12N-GY
6 10 12 16 AI 6-12 H6.0/20
FE-6.0-12N-YE
*
Recommended crimp tool
CRIMPFOX6
CRIMPFOX6T-F
CRIMPFOX10S
PZ6 roto
Variocrimp4
*
Use the
Variocrimp16.
Model Manufacturer
ESD 0,40×2,5 Wera
SZS 0,4×2,5
SZF 0-0,4×2,5 *Phoenix Contact
0.4×2.5×75 302 Wiha
AEF.2,5×75 Facom
210/-719 Wago
SDIS 0.4×2.5×75 Weidmuller
9900 (-2.5×75) VESSEL
12 mm
4 mm max. 4 mm max.
0.4 mm
2.5 mm dia.
2.5 mm
Side Front

Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.

Authorized Distributor:
In the interest of product improvement,
specifications are subject to change without notice.
Cat. No. T226-E1-01 0919 (0919)
© OMRON Corporation 2019 All Rights Reserved.
OMRON Corporation Industrial Automation Company
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
Contact: www.ia.omron.com
Kyoto, JAPAN
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Other manuals for S8V-CP Series
1
This manual suits for next models
3
Table of contents
Other Omron Circuit Breaker manuals