Orcon HRC 300 4B P Manual

Fitting and maintenance
instructions
Heat recovery unit
www.orcon.nl
Type: HRC 300/400 4B(P/RH)
Store near the appliance
This manual is intended for
users and installers of type
HRC 300/400 B(P/RH).
This manual contains impor-
tant about the operation
and installation of the
HRC 300/400 B(P/RH).

2
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
1. General 2
2. Version 3
2.1 General 3
2.2 Fitting HRC in brief 3
3. Installation 4
3.1 Mounting frame 4
3.2 Important Instruction 4
3.3 Connecting ducts 4
3.4 Connecting condensate discharge 5
3.5 Placing the heat recovery module 6
3.6 Replacing the cover 6
3.7 Electrical connections 6
3.7.1 HRC with 4 core and earth cable 6
3.7.2 HRC with wireless remote control 6
3.7.3 Speed control with 4 core and earth cable
(BP model only) 6
3.7.4 Speed control with a wireless remote control
(BRH model only) 6
3.8 Overview connection HRC 7
3.9 Adjusting the air performance 7
4. Maintenance 10
4.1 User maintenance 10
4.2 Installer maintenance 11
4.3 Mounting of the heat-exchanger and the motor plates 12
4.4 LED indication / Fault warnings 12
5. Technical specifications 13
5.1 Wiring diagram Orcon HRC 300/400 4B(P/RH) 13
5.2 Appliance data HRC 300 4B(P/RH) 14
5.3 Fan graph HRC 300 4B(P/RH) 15
5.4 Appliance data HRC 400 4B(P/RH) 16
5.5 Fan graph HRC 400 4B(P/RH) 17
5.6 Setting transmitter / receiver (RH model only) 18
6. Maintenance 19
6.1 Exploded view HRC 19
Declaration of conformity 19
To maintain a healthy indoor environment closely-controlled
ventilation is essential. There are many pollutants that will
affect the indoor air quality: human body waste products
in shape of CO2, dead skin, perspiration and moisture.
Add to this the waste product of cooking (cooking-smells),
showering (moisture), gases from building-materials and
the waste products of pets.
Without proper ventilation this environment would be perfect
for the growth of mould and subsequently damage to the
decoration and fabric of a dwelling.
The HRC unit is fitted with two fans: The exhaust fan ensures
that warm damp and polluted air as near as possible to
the source will be extracted. The exhausted air must be
replaced with fresh air and so the HRC heat recovery unit
has not only an exhaust fan but is also fitted with a supply
fan and air filters.
The supply air, which in winter is colder than the inside air, is
heated in the heat recovery unit using the heat of the exhaust
air by means of the heat-exchanger. This heat exchanger
has an efficiency of 97%, so a minimum loss of heat takes
place and the supply air temperature is at an acceptable
and comfortable level.
In the summer, when heat-recovery is not desirable, the air
does not go through the heat exchanger, but is diverted by
way of a bypass-valve. By doing this during the night, with
relatively cool supply air to ventilate the dwelling, a cooler
dwelling temperature is possible. This is automatically
detected and controlled by the unit electronics.
The electronics also ensures, that in winter, when ice-formation
in the exchanger is possible, the exchanger is defrosted, at a
time that is most comfortable to occupants of the dwelling.
Further the fan speed will automatically switch up to a
higher setting when a 5% increase in relative humidity is
detected within a 2 minute period (usually during showering
or cooking). After a preset period the unit will return to the
lower set speed. The fans are energy-low by the use of EC-
motors with a constant (adjustable) air volume.
The filters in the unit ensure that the fresh supply air is clean
as it enters the dwelling. Also the extract air from the property
is filtered, so that the pollution of the heat exchanger is
minimised.
These filters have to be cleaned every month, depending
on the pollution. The electronics in the unit is fitted with a
timer for filter cleaning which automatically indicates when
it is time to clean the filters. The maximum period between
replacements of the filters will be a year.
Contents 1. General

3
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
2.1 General
The Orcon HRC is a complete heat recovery unit, which is
fitted with an intelligent electronic control system to ensure
optimum efficiency and protection under all conditions.
The unit can easily be set up for left- or a right-handed opera-
tion. By changing the position of a module at the top of the
unit it can quickly be configured to accomodate the ducting
to outside on either the left or on the right side of the unit.
With the screws and plugs supplied fit the unit horizontally
to the wall. A standard the unit is delivered complete with a wall
mounting frame, fitting instructions, fixing kit and a condensate
discharge trap. A wireless remote control is an optional extra.
2.2 Fitting HRC in brief
A Mounting frame: Mounted by means of the screws and plugs
supplied horizontally to the wall. Use the fixing points on
the drawing attached to the mounting frame. When the frame
is mounted horizontally to the wall, the ducting runs can be
completed. Remember that both ducts to and from outside,
will be fitted to one side of the unit and the ducts to and from
the house are attached to the other side of the unit. Also
the condensate discharge under the unit can be fitted at
this stage.
B When the ducting runs are completed if an appropriate
electrical supply is present, the installation can be com-
pleted. Now the heat recovery module can be attached to
the frame. Ensure that the “tree” on the left/right module
corresponds to the side of the unit with the ducts to and
from outside and the “house” is on the internal side. On
the central PCB (3.1) adjust the air volume of the fans for
low, middle and high speed. Both fans are adjusted to the
same airflow to guarantee a balanced airflow. Push the heat
recovery module fully to the back of the mounting frame
and turn the handles at the bottom 180° to lock the unit
in place. Also the condensation trap under the unit can be
securely fastened with the wire clip supplied.
C The cover of the unit can now be replaced and secured with
the two screws and the power-supply can be connected. The
unit will start-up immediately and begin to run but must be
calibrated as described on page 13 in the start-up-procedure.
When there are no failures during the start-up, the unit is
ready and fully commissioned.
For further information about the operation, adjustment, failures
and maintenance of the unit, read the next pages carefully.
2. Version
A
B
C

4
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
3. Installation
1. Temperature sensor (4x)
Measures the temperatures in all connected ducts
2. Humidity sensor
Measures the relative humidity in the exhaust air
3. Central PCB ( 3.1)
This pcb controls the fans, sensors and decides which
function is activated
4. Dip switches
Used to adjust the airflow for each speed setting
5. Filters
Both supply and extract air is filtered
6. Left/Right module
For left or right-handed orientation (house-tree / tree-house)
7. Display Panel
Displays the current status and any failure of the HRC
8. Receiver PCB (only RH)
Pcb for wireless remote controlled HRC
9. Condensate-trap
Connection for condensate drain with water trap
10. Fan Right
Constant Flow fan with brushless EC motor supplies fresh
filtered air to the dwelling or extracts stale air from the
building depending on selected orientation of the HRC
11. Bypass valve
For supply of cool outside air in the summer
12. Heat exchanger
Takes care of the heat exchange between both airflows
13. Ventilator module left
Constant Flow fan with brushless EC motor supplies fresh
filtered air to or extracts stale air from the dwelling depending
on selected orientation of the HRC.
3.1 Mounting frame
The mounting frame of the HRC can be fitted directly to the wall
with the delivered screws and plugs. The distance between both
mounting-holes will be 53 cm. Under the mounting frame
ensure there is at least 50 cm for the condensate discharge
to be connected. On the mounting frame is a drawing, which
indicates where to fit the condensate discharge. The position
of the electrical power supply (an earthed wall socket or fused
switched spur) is also indicated. The unit must be secured
horizontally. Ensure sufficient angle for the condensate
discharge. The installation must be in a frost-free room.
Make sure there is a free space of at least 80 cm at the front of the
appliance for cleaning the filter and carrying out maintenance
on the appliance.
3.2 Important instruction
The HRC unit must be installed in accordance with all relevant
Building Regulations and Health & Safety requirements and the
fitting instructions of the HRC 300/400 4B(P/RH)
Connect mains after mounting the ducts!
3.3 Connecting ducts
When the mounting frame is fitted, the ducts can be fitted.
On one side of the unit the duct to and from the dwelling, on
the other side the ducts from and to outside.
To prevent condensation on the outside of the exterior air,
the inlet duct and the air outlet duct from the HRC must be
insulated.
It is recommended that the ducts from and to the dwelling
and to the appliance use flexible ducting with a minimum
length of 150 cm and flexible connections of the ducts to and
from the outside to the appliance use flexible ducting with
a minimum length of 50 cm. Flexible ducting should be fully
extended but should not place any strain on the terminal or
fixings.
Remember when sizing the ducts that this part of the installation
will affect energy efficiency. So remember that energy will be
wasted, during the passage of the air through the ductwork,
if the ducts are too small. If possible ensure that the total
resistance of the inlet- as well as the exhaustsystem does not
exceed 100 Pascal.
Figure 1: Parts of heat recovery module HRC 300/400 4B(P/RH)

5
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
A = No exhaust too close to an air inlet
B = Ventilation inlet possible near roof end
C = Inlet roof terminal
D = Ventilated ridge tile
E = Duct from and to outside - insulated
F = HRC (horizontal position)
G = Condensate discharge conforms to installation instructions
H = Ducts from and to the dwelling acoustically insulated
I = Ventilation exhaust roof terminal
Figure 2: Connection example HRC
Arrange the exterior air supply from the sheltered side of the
dwelling, for instance from the wall. Install the exterior air
supply duct in such a manner that surface condensation is
prevented.
A = 10mm above roofing
B = roof insulation
C = insulated with PUR
D = duct for air inlet - insulate carefully
Figure 3: Discharge duct through the roof.
Feed the discharge duct through the roof void in such a manner
as to prevent condensation; in addition, the discharge duct
between the HRC and the roof terminal must be designed to
prevent surface condensation.
The mechanical ventilation outlet, the air inlet and any soil &
vent pipes should each be separated by at least one meter.
A = Outlet valve ø125 plastic (MKL) or metal (EFF-125)
B = Inlet valve ø100 (TFF-100) or ø125 (TFF-125)
a = Gap under the door 2 cm.
Figure 4: Location outlet and inlet valves
Install sufficient overflow openings, door gap 2 cm.
3.4 Connecting condensate discharge
The condensation-trap must be mounted at the bottom of the
HRC with the wire clip supplied.
Caution! Before mounting you have to fill the trap with water.
The diameter of pipework to the air-trap is 32 or 40 mm. The
position of the drain is indicated at the drawing in the mounting
frame. The condensate water must leave through the drain
pipe. Take care that the distance between siphon and air-trap
will be enough for de-mounting and cleaning.
Figure 5: Connection of HRC to drain pipe

6
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
3.5 Placing the heat recovery module
After fitting all the ducts at the mounting frame, and after fitting
the condensate discharge, the “heart” of the unit can now be
installed. Take the heat recovery module from the carton and
push it from the front into the mounting frame.
Push the unit fully to the back and secure by turning the handles
at the bottom 180°.
Figure 6: Placing the heat recovery module of the HRC
After positioning the heat recovery module, the dip switches
can be adjusted to give the desired air volume. (See § 3.9)
Ensure that the filters are correctly located.
3.6 Replacing the cover
After the heat recovery module is fixed in place the cover
can be attached. Offer up the cover with its front pointing
downwards. Hook the two brackets on the lower part of the
cover into the slots in the mounting frame. Now you can fix
the upper side of the cover at the upper side of the mounting
frame with the two screws provided. If it is difficult to push
the cover totally against the unit open the flap in the cover.
After closing the cover (and flap) the unit can be connected
to the power supply.
3.7 Electrical connections
3.7.1 HRC with 4 core and earth cable
The electric installation must comply with the local regulations.
3.7.2 HRC with wireless remote control
The electric installation must comply with the local regulations.
3.7.3 Speed control with 4 core and earth cable (BP model only)
The unit requires a power supply of 230 Volt (terminal L3 and N).
The speed control takes place by means of a 3-speed switch and
utilising 4 core and earth cabling to the unit.
For the correct wiring diagram see § 5.1.
3.7.4 Speed control with a wireless remote control
(BRH model only)
The HRC 300/400 BRH is delivered prewired. The unit must be
connected to 230V~50Hz supply by means of a 3A fused spur.
Figure 7: Wireless remote control
See § 5.4.2 for settings of the wireless remote controller.
3 = High
2 = Middle
1 = Low
Auto = No function

7
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
3.8 Overview connection HRC
The HRC can be configured either as a standard or a mirrored
unit. As a standard unit, the duct connections on the left side
of the unit will go outside and the duct connections at the right
side go to the dwelling. The turn-module will show a “tree” on
the left and a “house” on the right side.
Figure 8: Turn-module
If the unit is to be configured as a mirrored unit, you can pull
the turn-module out of the unit and turn it 180° (reverse side
to the front) and insert it b ack into position. You will see that
now the “tree” is on the right side and the “house” on the left
side. The connections at the unit have now changed. The
connections on the left side now lead to the dwelling and the
connections on the right side lead outside.
Figure 9: Turn-module (detail)
The top connection is always the suction side (suction from
outside or from the dwelling) and the bottom connections are the
pressing connections (exhaust to outside or inlet to the dwelling).
The magnets on the turn-module are used to configure the unit
for left or right-handed operation and must not be changed or
removed after the initial set up.
Attention! Keep the magnet away from creditcards and other
objects sensitive to magnetic fields.
3.9 Adjusting the air performance
The HRC is provided with constant volume fans.
The integrated electronics controls the speed of each ventilator,
to keep the airflow equal conform the settings of the dipswitches
independent of the resistance of the system. For this reason
the speed of both fans will not always be equal, because the
resistance of the inlet and exhaust system will not always
will be equal.
By means of the dip switches on motor-pcb’s at both sides of
the unit, you can easily change the airflow of the highest speed.
To change the airflow of the ventilator follow instructions
below:
1. Remove the cover from the unit.
2. The dip switches on the motor-pcb’s on both sides of the unit
are now accessible
3. Set the dip switches on both pcb’s to the desired airflow after
checking the setting on the drawing below.
4. Refit the cover and make sure that the filters in the unit are
clean.
5. Restart the unit.
Important: Before removing the cover you must disconnect the
electrical power to the unit.

8
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
Dipswitch settings HRC 300 4B(P/RH)
ON
1 2
ON
5 6 7 8
ON
ON
ON
ON
ON
ON
ON
ON
ON
1 2
ON
ON
ON
ON
ON
3 4
3 4
ON
ON
ON
ON
ON
1 = OFF, 2 = ON
90 m3/h
5 = OFF, 6 = OFF, 7 = OFF, 8 = OFF
200 m3/h
5 = OFF, 6 = ON, 7 = OFF, 8 = OFF
220 m3/h
5 = OFF, 6 = OFF, 7 = OFF, 8 = ON
230 m3/h
5 = OFF, 6 = ON, 7 = ON, 8 = OFF
250 m3/h
3 = ON, 4 = OFF
125 m3/h
5 = ON, 6 = OFF, 7 = OFF, 8 = ON
270 m3/h
5 = OFF, 6 = ON, 7 = OFF, 8 = ON
280 m3/h
5 = OFF, 6 = ON, 7 = ON, 8 = ON
300 m3/h
5 = ON, 6 = ON, 7 = OFF, 8 = ON
300 m3/h
1 = ON, 2 = ON
100 m3/h
5 = ON, 6 = OFF, 7 = OFF, 8 = OFF
210 m3/h
5 = OFF, 6 = OFF, 7 = ON, 8 = OFF
225 m3/h
5 = ON, 6 = ON, 7 = OFF, 8 = OFF
240 m3/h
5 = OFF, 6 = OFF, 7 = ON, 8 = ON
260 m3/h
3 = OFF, 4 = ON
150 m3/h
5 = ON, 6 = OFF, 7 = ON, 8 = OFF
275 m3/h
5 = ON, 6 = ON, 7 = ON, 8 = OFF
290 m3/h
5 = ON, 6 = OFF, 7 = ON, 8 = ON
300 m3/h
5 = ON, 6 = ON, 7 = ON, 8 = ON
300 m3/h
3 = ON, 4 = ON
175 m3/h
Low
High
Middle
3 4
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
Factory setting:
L = 100m3/h
M = 150m3/h
H = 225m3/h
ON
1 2 3 4 5 6 7 8

9
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
Dipswitch setting HRC 400 4B(P/RH)
ON
1 2
ON
5 6 7 8
ON
ON
ON
ON
ON
ON
ON
ON
ON
1 2
ON
ON
ON
ON
ON
3 4
3 4
ON
ON
ON
ON
ON
1 = OFF, 2 = ON
105 m3/h
5 = OFF, 6 = OFF, 7 = OFF, 8 = OFF
245 m3/h
5 = OFF, 6 = ON, 7 = OFF, 8 = OFF
270 m3/h
5 = OFF, 6 = OFF, 7 = OFF, 8 = ON
280 m3/h
5 = OFF, 6 = ON, 7 = ON, 8 = OFF
310 m3/h
3 = ON, 4 = OFF
150 m3/h
5 = ON, 6 = OFF, 7 = OFF, 8 = ON
330 m3/h
5 = OFF, 6 = ON, 7 = OFF, 8 = ON
345 m3/h
5 = OFF, 6 = ON, 7 = ON, 8 = ON
370 m3/h
5 = ON, 6 = ON, 7 = OFF, 8 = ON
390 m3/h
1 = ON, 2 = ON
120 m3/h
5 = ON, 6 = OFF, 7 = OFF, 8 = OFF
255 m3/h
5 = OFF, 6 = OFF, 7 = ON, 8 = OFF
275 m3/h
5 = ON, 6 = ON, 7 = OFF, 8 = OFF
295 m3/h
5 = OFF, 6 = OFF, 7 = ON, 8 = ON
320 m3/h
3 = OFF, 4 = ON
180 m3/h
5 = ON, 6 = OFF, 7 = ON, 8 = OFF
340 m3/h
5 = ON, 6 = ON, 7 = ON, 8 = OFF
355 m3/h
5 = ON, 6 = OFF, 7 = ON, 8 = ON
380 m3/h
5 = ON, 6 = ON, 7 = ON, 8 = ON
400 m3/h
3 = ON, 4 = ON
215 m3/h
Low
High
Middle
3 4
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
Factory setting:
L = 120m3/h
M = 180m3/h
H = 275m3/h
ON
1 2 3 4 5 6 7 8

10
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
4.1 User maintenance
User maintenance is limited to periodically cleaning the filters.
The unit is fitted with a filter timer. If you have to clean the
filters a red led in the panel will start flashing on/off. This filter
indication will start flashing each month. The unit should not
be used without filters.
Cleaning the filters by user
4. Maintenance
4
• After cleaning replace filters at same side
3
• Vacuum the outside of the filter
5
• Close the filter door.
• Switch on the power supply. Press and hold the reset button to ensure that the red led stops flashing.
2
• Remove the filters
1
• Switch off the power supply
• Open the filter door

11
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
4.2 Installer maintenance
Take out the heat exchanger (once every 3 years)
3
• Disconnect the power supply
• Pull the inner-assembly out of the frame
• Disconnect the wiring to the motor from the pcb
• Unscrew the 4 screws of the motor plate
• Take off the fan
4
• Clean the fan with a dry stiff brush
• Prevent damage to the fan blades
• Do not use water for cleaning
2
• Clean the heat-exchanger with warm water and a mild
detergent.
• Rinse with warm water
1
• Switch off the power supply and remove the cover
• Remove the bypass cover (1)
• Remove the press tray (2)
• Remove the heat-exchanger (3)
Clean the fans (if dirty)
The fans must be cleaned if they are dirty. Be sure not to bend the fan blades; this could cause a motor imbalance, unnecessary noise
and will shorten the life of the motor bearings.

12
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
4.3 Mounting of the heat-exchanger and the motor plates
• Replace the heat exchanger and fans by reversing the
instructions in 4.2
• Replace the heat exchanger from above and ensure that there
is no leakage between supply and extract airflows.
• Push the pressure tray into position. This may require some
force as the seal between the exchanger and the housing is
a tight fit. Replace the filters.
• Replace the motor plates into the housing and fix the 4 screws.
Reconnect the wiring of the motor to the motor-pcb.
• Mount the cover of the unit.
• Reconnect the power to the unit and check that the unit
functions correctly.
4.4 LED indication / Fault warnings
When there is a failure or a certain scenario, this will be shown
on the display of the unit. The key to the meanings of the various
LED indications is located on the filter door of the cover. A red
LED indicates that action is required. A green LED indicates a
particular mode of operation. When the LED indication is not
in the key shown here stop the unit immediately and contact
your installer or the distributor of the unit.
Meaning LED-signs
Normal function
Filter polluted
Frost
Defrost-cycle
Moist detected
Summer/Comforttemp.
Failure Bypass valve
Failure temperature sensor
Failure moist sensor
= Green, short
= Red, short
= Green, long
= Red, long
= Red or green, long

13
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
5.1 Wiring diagram Orcon HRC 300/400 4B(P/RH)
5. Technical specifications

14
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
Fan settings Low speed Middle speed High speed Maximum speed
Ventilation capacity, factory settings [m3/h] 100 150 225 300
Rated power [W] 18-22 29-50 72-98 144-169
Rated current [A] 0.14-0.15 0.21-0.34 0.49-0.65 0.95-1.1
Cos ϕ 0.60-0.61 0.62-0.63 0.64-0.65 0.66-0.67
Permissable duct/ system resistance [Pa] 160 Pa at 300 m3/h
Dimensions (w x h x d) [mm] 706 x 780 x 565
Duct diameter [mm] Ø166 and Ø180 ( = Outside diameter ducts))
External diameter condensate discharge [mm] Ø20
Filter class G3 (F7 optional)
Weight [kg] 39 kg (frame 12 kg, unit 23 kg, cover 4 kg)
Supply voltage [V~/Hz] 230 / 50
Protection degree IP30
Temperature efficiency [%] 95
Factory Setting Middle speed
Independently laboratory tested to Dutch mechanical
ventilation with heat recovery test standard, NEN 5128.
ηWTW measured [%] 97.3
ηWTW NEN 5128 [%] 95
I [A] 0.155
U [V] 230
Cos ϕ0.62
No. of fans 2
5.2 Appliance data HRC 300 4B(P/RH)
Sound pressure level LpA [dB(A)]
Ventilation capacity [m3/h] Static pressure [Pa] 0 Pa 50 Pa 150 Pa 300 Pa
150
Breakout from unit 29.5 34.4 38.6 44.9
Supply air outlet 46.3 49.0 54.3 60
300
Breakout from unit 44.3
Supply air outlet 59.5

15
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
5.3 Fan graph HRC 300 4B(P/RH)
Point [m3/h] [Pa] U [V] I [A] cos ϕ P [W]
A 100 12 230 0,068 0,602 9,4
B 100 16 230 0,070 0,604 9,7
C 100 25 230 0,075 0,612 10,6
D 150 25 230 0,102 0,626 14,8
E 150 36 230 0,110 0,621 15,7
F 150 56 230 0,120 0,625 17,3
G 200 44 230 0,188 0,643 27,8
H 200 64 230 0,191 0,642 28,2
I 200 100 230 0,225 0,652 33,7
J 250 69 230 0,287 0,663 43,8
K 250 100 230 0,323 0,668 49,6
L 250 156 230 0,402 0,667 61,7
M 300 100 230 0,472 0,671 72,9
N 300 144 230 0,515 0,658 77,9
O 300 160 230 0,546 0,662 83,2
Resistance ducts system (Pa)
350
300
250
200
150
100
50
0
0 50 100 150 200 250 300 350
C
B
A
F
E
I
H
G
L
K
J
O
N
M
D
Power consumption per fan [w], see table
Airflow (m3/h)

16
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
5.4 Appliance data HRC 400 4B(P/RH)
Fan settings Low speed Middle speed High speed Maximum speed
Ventilation capacity, factory settings [m3/h] 100 150 225 400
Rated power [W] 18-22 29-50 72-98 173-350
Rated current [A] 0.14-0.15 0.21-0.34 0.49-0.65 1.8-2.27
Cos ϕ 0.60-0.61 0.62-0.63 0.64-0.65 0.66-0.67
Permissable duct/ system resistance [Pa] 150 Pa at 400 m3/h
Dimensions (w x h x d) [mm] 706 x 780 x 565
Duct diameter [mm] Ø210 ( = Outside diameter ducts)
External diameter condensate discharge [mm] Ø20
Filter class G3 (F7 optional)
Weight [kg] 39 kg (frame 12 kg, unit 23 kg, cover 4 kg)
Supply voltage [V~/Hz] 230 / 50
Protection degree IP30
Temperature efficiency [%] 95
Factory Setting Middle speed
Independently laboratory tested to Dutch mechanical
ventilation with heat recovery test standard, NEN 5128.
ηWTW measured [%] 97.3
ηWTW NEN 5128 [%] 95
I [A] 0.155
U [V] 230
Cos ϕ0.62
No. of fans 2
Sound pressure level LpA [dB(A)]
Ventilation capacity [m3/h] Static pressure [Pa] 0 Pa 50 Pa 150 Pa 300 Pa
150
Breakout from unit 29.5 34.4 38.6 44.9
Supply air outlet 46.3 49.0 54.3 60
300
Breakout from unit 44.3
Supply air outlet 59.5

17
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
5.5 Fan graph HRC 400 4B(P/RH)
Point [m3/h] [Pa] U [V] I [A] cos ϕ P [W]
A 100 12 230 0.080 0.509 9
B 100 16 230 0.083 0.511 10
C 100 25 230 0.088 0.519 11
D 150 25 230 0.120 0.533 15
E 150 36 230 0.129 0.528 16
F 150 56 230 0.141 0.532 17
G 200 44 230 0.220 0.550 28
H 200 64 230 0.223 0.549 28
I 200 100 230 0.262 0.559 34
J 250 69 230 0.334 0.570 44
K 250 100 230 0.375 0.575 50
L 250 156 230 0.467 0.574 62
M 300 100 230 0.548 0.578 73
N 300 144 230 0.600 0.565 78
O 300 225 230 0.790 0.580 105
P 350 140 230 0.820 0.640 121
Q 350 200 230 0.960 0.590 133
R 375 175 230 1.115 0.590 156
S 400 150 230 1.29 0.590 175
Airflow (m3/h)
Resistance ducts system (Pa)
0
50
100
150
200
250
300
350
400
0 50 100 150 200 250 300 350 400 450
D
E
F
I
H
G
J
M
N
O
Q
S
R
K
L
C
B
A
Power consumption per fan [w], see table

18
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
5.6 Setting transmitter / receiver (RH model only)
When current is put on the device, the red LED is flashing 3x on
the receiver print.
Login for 1 remote.
Press the pushbutton on receiver print for 2 seconds. The red LED
is flashing 2x, followed by continuously burning red LED.
On the remote, press [auto] and [key 1] simultaneously. Keep
pressing until the green LED on the remote stays.
When the remote is logged in, the red LED on the receiver print is
flashing 10x, then the green LED on the remote flashes 3x. Now
the remote is ready for use.
Login of 2 remote controls.
Press the pushbutton on receiver print for 2 seconds. The red LED
is flashing 2x and goes.
On the remote, press [auto] and [key 1] simultaneously. Keep
pressing until the green LED on the remote goes.
When the remote is notified, the red LED on the receiver print is
flashing 10x, thereupon the green LED on the remote is flashing
3x. Now the remote is ready for use.
Remote 2 is logged in the same manner as remote 1.
When a third remote is notified, it will overwrite the second remo-
te. The first remote stays logged on.
To replace remote no. 1, it is necessary to erase the print of the
home ventilator. Only then it is possible to notify a new remote(s).
Logout of the remote controls.
Press the pushbutton on receiver print continuously until the red
LED goes. After releasing the button, the red LED on the receiver
print will flash 5x. The link with the remote is now erased
Battery replacement.
When the LED indication on the remote does not react when one
of the buttons on the remote is pushed, it is probably due to a
low battery. To replace the battery, you do not need to contact
your installer.
You can easily do it yourself. The battery is commercially availa-
ble (typ: 3V CR 2032).
To replace the battery, you first slide the remote in a vertical
upward direction in order to detach the remote from the holder.
At the back of the remote, you find two screws, unscrew them.
Now you can remove the back of the remote. Remove the old bat-
tery from the remote and replace it by a new one. Make sure the
positive side/plus of the battery faces you. Replace the back of
the remote and screw. Replace the remote in to the holder.
If there are still problems arising, please contact your installer.
Please do not mount the remote control under a metal cooker hood.
Mount on a flat surface with the screws and wall plugs supplied.
Figure 10: Battery replacement Figure 11: Remote control
Use
The remote control of the HRC is fitted with two keys:
• 1 = High: use this speed for cooking or showering
• 2 = Middle: for daily use by normal use of the dwelling
• 3 = Low: for use during the night or during vacations.
• AUT = Pressing this key, the unit works as Low.
Figure 12: Receiver print
3V CR2025
/ 3V CR2032
Green LED
ON
1 2
Drukknop
Rode Led
Antenne
Antenna
Red LED
Pushbutton

19
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
6. Maintenance
6.1 Exploded view HRC
When ordering parts, you have to mention the article code num-
ber (see exploded view), the type of heat recovery appliance,
serial number, production year and the name of the part:
Example: Appliance type : HRC 400-4BP
Serial number : 091180031
Year of production : 2009
Part : Motor HRC 400
Article code : 29190685
Quantity : 1
N.B.: Type and serial number are printed at the identification
plate on the top of the inner assembly.
Specifications may change
We continuously strive to improve our products and reserve the
right to change the specification without prior notice.
S1: Orcon 3.1
S2: Receiver pcb
S3: Filters
S4: Motor
S5: Heat exchanger
10: Turn-module
11: Profile
12: Bypass
13: Cover
Article codes service-articles HRC
Nr. Article description Article code
S1 Central PCB (Orcon 3.1) 22905024
S2 Receiver pcb (RH model only) 29190742
S3 Filter set (2 x G3 filter) 29199770
S3’ Pollen filter (1 x F6) 29190773
S4 Motor HRC 300 29190657
S4’ Motor HRC 400 29190685
S5 Heat-exchanger 29199771
S6 Humidity sensor 29199763
S7 Temperature sensor 29299755
S8 Condensate trap 29199836
Declaration of conformity
The heat recovery appliances type HRC 300/400 4B(P/RH)
manufactured by Orcon bv in Veenendaal, the Netherlands
bears the CE label and satisfies the machine directives
2006/42/EEG, the low voltage directives 2006/96 EEG,
The R&TTE directives 1999/5/EEG and the EMC-directives
2004/100 EEG. Orcon bv warrants that the heat recovery
appliances are manufactured from high-quality materials
and that continuous quality control ensures that they
comply with the above directives.
Orcon bv
M. Voorhoeve,
Director.

Storkstraat 23, 3905 KX Veenendaal (NL)
P.o. box 416, 3900 AK Veenendaal
t +31 (0)318 54 47 00
f +31 (0)318 54 47 06
Orcon bv
www.orcon.nl
Edition april 2010 29199185 orc10018
This manual suits for next models
3
Table of contents
Other Orcon Heating System manuals
Popular Heating System manuals by other brands

WILHELM KELLER
WILHELM KELLER OILPRESS 330.902 Installation, maintenance & use instructions

saro
saro PLC 250 instruction manual

ubbink
ubbink Ubiflux W450 + installation instructions

Broan
Broan ERV140 ECM installation guide

Dimplex
Dimplex DuoHeat Duo300N operating instructions

BVN
BVN BGK 100 User manual & certificate of warranty