Operation Instructions
MVP-SSF PTRO/DMRO
DCN: E
IN
-
CP
-
O
P
-
2
113
Rev:
9
.0
Date:
02/22
/18
Orenco Systems
®
,Inc.
•
814 Airway Avenue, Sutherlin, Oregon 97479, USA
•
800-348-9843
•
541-459-4449
•
www.orenco.com
EIN-CP-OP-2113 Rev. 9.0 © 02/22/18 Page 1 of 4
Orenco’s Most Versatile Panel (MVP) line of control panels includes an easy-to-use programmable logic unit that
incorporates many timing and logic functions. This panel will accommodate timed dose septic tank systems and either
time dosed or on-demand sand filter systems. The panel’s default mode of operation for the sand filter pumping is on-
demand. This document describes each mode of operation.
Alar and Data Screens:
Alarm and data screens have been included with the panel to assist with panel monitoring and troubleshooting. The
following alarm and data screens have been included in your panel, look for the √to determine if the screen will be
displayed for timed dosed or on-demand modes. Navigation between the screens is accomplished by using the up and
down arrow keys. See “Screen Navigation” section for more details.
Screen
Description
Sand Filter
Ti ed
Sand Filter
De and
Data Type*
Alar Screens†
1 Sand filter high level alarm √ √
2 Septic tank high level alarm √ √
3 Sand filter low level alarm √ √
4 Septic tank low level alarm √ √
Data Screens
5 Sand filter float status and timer mode (default screen, see fig 1) √ √
Septic tank float status √ √
7 Sand filter pump cycles at top of screen and pump run time beneath √ √ T
8 Septic tank pump cycles at top of screen and pump run time beneath √ √ T
9 Sand filter high level alarms √ √ T
10 Septic tank high level alarms at top of screen and low level alarms beneath √ √ T
11 Sand filter override cycles at top of screen and timer float events beneath √ T
12 Septic tank override cycles √ √ T
13 Power faults at top of screen and time in service beneath √ √ T
14 Sand filter pump cycles at top of screen and pump run time beneath √ √ R
15 Septic tank pump cycles at top of screen and pump run time beneath √ √ R
1 Sand filter high level alarms √ √ R
17 Septic tank high level alarms at top of screen and low level alarms beneath √ √ R
18 Sand filter override cycles at top of screen and timer float events beneath √ R
19 Septic tank override cycles √ √ R
20 Power faults at top of screen and time in service since last reset √ √ R
† Alarm screens will only be displayed when alarms are active and include a date and time stamp of when the alarm started.
* Screens with “T” in the lower right corner have totalized values for the data. Screens with “R” in the lower right corner have resettable data and display the
accumulated values since the last reset. To reset the accumulated values, hold the silence button on the panel for 10 seconds.
Orenco Systems
®
,Inc.
•
814 Airway Avenue, Sutherlin, Oregon 97479, USA
•
800-348-9843
•
541-459-4449
•
www.orenco.com
EIN-CP-OP-2113 Rev. 9.0 © 02/22/18 Page 2 of 4
Sand Filter Float Status and Ti er Mode Screen:
This default screen will display the condition of the sand filter floats and the operation mode of the panel
for the sand filter pump. If the floats are lifted out of sequence, this screen will display “Float Error” while
showing the float status.
Digital Input and Digital Output Screens:
The unit will activate various inputs and outputs as it operates (see Figure 2).
Knowing what conditions cause the inputs and outputs to activate can be a helpful installation and troubleshooting tool.
The input functions will vary based on the mode of operation of the panel. The following inputs and outputs have been
used with your panel:
# Functions: Activation Conditions:
Inputs (Sand Filter On-De and Mode)
1 Septic Tank Redundant Off & Low Level Alarm Float Float in up position
2 Septic Tank Timer On & Off Float Float in up position
3 Septic Tank Override Timer On & Off Float Float in up position
4 Septic Tank High Level Alarm Float Float in up position
5 Sand Filter Redundant Off & Low Level Alarm Float Float in up position
Sand Filter Pump Off Float Float in up position
7 Sand Filter Pump On Float Float in up position
8 Sand Filter High Level Alarm Float Float in up position
9 Push To Silence
Pushbutton is pressed
10 Alarm Test Switch (Optional) Switch is activated
Alternate Inputs ( Sand Filter Ti ed Dose Mode)
Sand Filter Timer On & Off Float Float in up position
7 Sand Filter Override Timer On & Off Float Float in up position
Outputs
1 Septic Tank Pump Septic Tank Pump is called to run
2 Septic Tank Level Alarm Light Septic Tank Alarm Light is activated
3 Sand Filter Pump Sand Filter Pump is called to run
4 Sand Filter Level Alarm Light Sand Filter Alarm Light is activated
5 Audible Alarm Audible Alarm is activated
6 General Alarm (Optional) Alarm condition exists
I: 1/9
12 3 4 5 6 7 8 9
10+ 0123456789
20+ 0 12 3 4
Input Screen
Activated
Input/Output
Q: 2/9
123456789
10+ 0123456789
20+ 0
Output Screen
Inputs 1-9
Inputs 10-19
Inputs 20-24
Outputs 1-9
Outputs 10-19
Output 20
Figure 2. Input & Output Screens
Panel Operation:
Timed Dose Mode = On
On-Demand Mode = Off
Top Float Status
Bottom Float Status
Sand Filter
Float Status
Timed 3: own
ose 2: own
Mode=Off 1:Up
Figure 1. Sand Filter Float Status and Timer Mode Screen
Orenco Systems
®
,Inc.
•
814 Airway Avenue, Sutherlin, Oregon 97479, USA
•
800-348-9843
•
541-459-4449
•
www.orenco.com
EIN-CP-OP-2113 Rev. 9.0 © 02/22/18 Page 3 of 4
Screen Navigation:
The screens are arranged in the order shown in Figure 3 below. To move between screens, use the four arrow keys. The
screens of interest are shown in bold. Additional built-in screens will be present, but do not contain useful information.
Septic Tank Panel Operation:
Your control panel can perform the float functions listed below. Depending on the number of floats for your
application, some functions may be omitted or combined.
Septic Tank High Level Alarm: This float activates the septic tank alarm light (steady) and audible
alarm when lifted for longer than the high level alarm delay. The audible alarm may be silenced by
pressing the illuminated PUSH TO SILENCE button on the front of the control panel. The alarm light
(steady) will remain on until the float is lowered, and the audible alarm will reactivate in 12 hours if
condition is not corrected.
Septic Tank Override Timer On & Off: This float activates the override timer function when lifted for
more than 2 seconds. This timer function controls the septic tank pump cycles during high flow
conditions. The override timer function will remain active until at least the set minimum override time
has been completed and the float has lowered. When the override timer function has been completed,
normal timer operation will resume.
Septic Tank Timer On & Off: This timer will be activated as long as the timer on & off float is up.
This timer function controls the septic tank pump cycles during normal flow conditions.
Septic Tank Redundant Off & Low Level Alarm: This float turns off the septic tank pump when
lowered for more than 2 seconds. Pumping will be disabled in both the automatic and manual modes.
This float also activates the septic tank pump alarm light (flashing) and audible alarm. The audible
alarm may be silenced by pressing the illuminated PUSH TO SILENCE button on the front of the
control panel. The alarm light will remain flashing until the float is raised. If the alarm condition is not
corrected in 12 hours, the audible alarm will be reactivated.
Sand Filter Panel Operation:
This panel supports two different modes of operation based on selected parameter settings. See the
“Setting Instructions” for this panel for information on how to change the mode of operation and other
adjustable parameters. Float functions for both modes of operation are listed below. Depending on the
number of floats for your application, some functions may be omitted or combined.
…
Digital
Inputs
(#1-24)
Digital
Outputs
(#1-20)
Analog
Inputs
(#1-5)
Analog
Inputs
(#6-8)
Analog
Outputs
(#1-5)
Analog
Outputs
(#6-8)
Memory
(#50-64) ESC+C
Time
&
Date
System Alarm
Screen
System Data
Screen
Memory
(#1-49)
Figure 3. Screen Layout
Orenco Systems
®
,Inc.
•
814 Airway Avenue, Sutherlin, Oregon 97479, USA
•
800-348-9843
•
541-459-4449
•
www.orenco.com
EIN-CP-OP-2113 Rev. 9.0 © 02/22/18 Page 4 of 4
Sand Filter On-De and Operation (Default):
Sand Filter High Level Alarm: This float activates the sand filter alarm light (steady) and audible
alarm when lifted for longer than the high level alarm delay. The audible alarm may be silenced by
pressing the illuminated PUSH TO SILENCE button on the front of the control panel. The alarm light
(steady) will remain on until the float is lowered, and the audible alarm will reactivate in 12 hours if
condition is not corrected. Note: A high level condition in the sand filter basin will disable the septic
tank pump in automatic.
Sand Filter Pump On: This float activates the sand filter pump when lifted. The pump will run for the
minimum run time or until the pump off float (if used) is lowered.
Sand Filter Pump Off: This float turns off the sand filter pump when lowered if the minimum run time
has elapsed.
Sand Filter Redundant Off & Low Level Alarm: This float turns off the sand filter pump when lowered
for more than 2 seconds. Pumping will be disabled in both the automatic and manual modes. This float
also activates the sand filter pump alarm light (flashing) and audible alarm. The audible alarm may be
silenced by pressing the illuminated PUSH TO SILENCE button on the front of the control panel. The
alarm light will remain flashing until the float is raised. If the alarm condition is not corrected in 12 hours,
the audible alarm will be reactivated.
Sand Filter Ti ed Dose Operation:
Sand Filter High Level Alarm: This float activates the sand filter alarm light (steady) and audible
alarm when lifted for longer than the high level alarm delay. The audible alarm may be silenced by
pressing the illuminated PUSH TO SILENCE button on the front of the control panel. The alarm light
(steady) will remain on until the float is lowered, and the audible alarm will reactivate in 12 hours if
condition is not corrected. Note: A high level condition in the sand filter basin will disable the septic
tank pump in automatic.
Sand Filter Override Timer On & Off: This float activates the sand filter override timer function when
lifted for more than 2 seconds. This timer function controls the pump cycles during high flow
conditions. The override timer function will remain active until at least the set minimum override time
has been completed and the float has lowered. When the override timer function has been completed,
normal timer operation will resume.
Sand Filter Timer On & Off: This float activates the sand filter timer function when lifted. The timer
will be activated while the float is up and will be deactivated 30 seconds after the float is lowered. This
timer function controls the sand filter pump cycles during normal flow conditions. Note: The timer will
start with its off cycle.
Sand Filter Redundant Off & Low Level Alarm: This float turns off the sand filter pump when lowered
for more than 2 seconds. Pumping will be disabled in both the automatic and manual modes. This float
also activates the sand filter pump alarm light (flashing) and audible alarm. The audible alarm may be
silenced by pressing the illuminated PUSH TO SILENCE button on the front of the control panel. The
alarm light will remain flashing until the float is raised. If the alarm condition is not corrected in 12 hours,
the audible alarm will be reactivated.

This manual suits for next models

1

Popular Control Panel manuals by other brands

Frick QUANTUM LX Control Panel Operation

Frick

Frick QUANTUM LX Control Panel Operation

Festo CDSA-D1-VX Assembly and installation

Festo

Festo CDSA-D1-VX Assembly and installation

ETC Echo Control Series installation guide

ETC

ETC Echo Control Series installation guide

olympia electronics BS-627 manual

olympia electronics

olympia electronics BS-627 manual

Hitachi PSC-5T Installation and operation manual

Hitachi

Hitachi PSC-5T Installation and operation manual

Frymaster Computer Magic user manual

Frymaster

Frymaster Computer Magic user manual

Fire-Lite Alarms ES-200XC manual

Fire-Lite Alarms

Fire-Lite Alarms ES-200XC manual

Sony DME-7000 Maintenance manual

Sony

Sony DME-7000 Maintenance manual

IBM Power System 9009-41A manual

IBM

IBM Power System 9009-41A manual

Satel VERSA IP Quick user manual

Satel

Satel VERSA IP Quick user manual

Atlantic EPIC 2D Series Installation and use manual

Atlantic

Atlantic EPIC 2D Series Installation and use manual

Extron electronics MMX 32 AAP installation guide

Extron electronics

Extron electronics MMX 32 AAP installation guide

GST GST301 Installation and operation manual

GST

GST GST301 Installation and operation manual

UltraLux SSW1Z instructions

UltraLux

UltraLux SSW1Z instructions

urmet domus 1067 Series Programming manual

urmet domus

urmet domus 1067 Series Programming manual

Sony ICP-X1116 Operation manual

Sony

Sony ICP-X1116 Operation manual

Satel VERSA Plus LTE Installer manual

Satel

Satel VERSA Plus LTE Installer manual

Toshiba RBC AIP4 installation manual

Toshiba

Toshiba RBC AIP4 installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.